Make Up Air II Installation Manual

05/21/2019 28 EI914
Troubleshooting Solution
The blower is not turning on
Check unit display. Display should show “FAN OFF” or
temperature screen.
If screen is blank, check 2A fuse.
If screen displays the “FAN OFF” screen, unit is not being told to
turn on.
Verify field low voltage wiring is correct
o CT or R & W
If screen displays the temperature and blower is not on, check for
power to the blower motor.
If power present, verify switch R & W IN only closure
between circuit board T18 and T19 (must be active call).
If no switch closure between T18 and T19, replace circuit
board.
If power present and switch closure detected, replace
blower.
If power is not present, check high voltage wiring.
The blower runs in “high
speed” only
If using the “R & W” terminals (option 1), high speed blower is the
only option.
If using CTs, ensure correct wiring of CTs, make sure high speed
blower CT only connects to the CT terminal block (TB2) “HI”
input.
If using “Multi-Spd Setup” option, verify external exhaust blower
motor is not running high speed, once verified, it is suggested you
run through the “Multi-Spd Setup” again to verify correct
programming (see Basic Setup & Configuration section).
The blower runs in “MED
speed” only
If using CTs to turn this product on, ensure correct wiring of CTs,
make sure MED speed blower CT only connects to the CT
terminal block (TB2) “MED” input.
If using “Multi-SPD Setup” option, verify external exhaust blower
motor is not running medium speed, once verified, it is suggested
you run through the “Multi-Spd Setup” again to verify correct
programming (see Basic Setup & Configuration section).
The blower runs in “LOW
speed” only
If using CTs to turn this product on, ensure correct wiring of CTs,
make sure LOW speed blower CT only connects to the CT
terminal block (TB2) “LO” input.
If using “Multi-Spd Setup” option, verify external exhaust blower
motor is not running low speed, once verified, it is suggested you
run through the “Multi-Spd Setup” again to verify correct
programming (see Basic Setup & Configuration section).
Condensation or frost build-
up on cabinet or ductwork
Insulate sections of cabinet and ductwork.
Routine Maintenance
Filter – this unit includes an air filter which is a permanent and washable filter.
Suggest at least twice per year removing filter and using standard household water to back flush collected
dust/debris.
Open small door
Filter is simply held within channels