Spec Sheet

07/15/2010 EL907
STANDARD EQUIPMENT
240V, single phase, external fusing required
Quiet DC power relays
Thermostat end switch connection point
Hi-limits, automatic reset - 150° F/180° fused link
Compact enclosure
Two element sizes available - 8 x 10 or 8 x 16
5-year element warranty
2-year parts warranty
TEMPERATURE RISE CHART*
Temperature Rise Needed 80° F 70° F 60° F 50° F 40° F 30° F
Model Watts CFM CFM CFM CFM CFM CFM
EM-WC0515H 4800 198 216 252 302 378 504
EM-WC1025H 9600 378 432 504 604 756 1007
EM-WC0515L 4800 189 216 252 302 378 504
EM-WC1025L 9600 378 432 504 604 756 1007
*Typically the maximum temperature rise for this product is 40° F for room air inlet. If used for make-up air, larger temperature rises are permissible, see table above.
ELECTRIC SUPPLY
Model kW Btu/h Amps Fuse Phase Voltage
Source
CB
Shipping
Weight
Installation
Manual
Minimum
CFM
EM-WC0515H 4800 16,383 20 N/A 1-60 240 30 7 HI309 180
EM-WC1025H 9600 32,765 40 N/A 1-60 240 50 7 HI309 370
EM-WC0515L 4800 16,383 20 N/A 1-60 240 30 14 HI309 180
EM-WC1025L 9600 32,765 40 N/A 1-60 240 50 14 HI309 370
CHIP CODE OPTIONS
Switch
Position
BCDEH
0 96° 20° 40° 60° 88°
1 100° 25° 52° 65° 90°
2 104° 30° 64° 70° 92°
3 108° 35° 76° 75° 94°
4 112° 40° 88° 80° 96°
5 116° 45° 100° 85° 98°
6 120° 50° 112° 90° 100°
7 124° 55° 124° 95° 102°
Comfort level temperature setting - choose correct chip code for application. Note: Unless otherwise speci ed, product will be shipped with a default “D” chip.
Specification Sheet - Electric Make-Up Air/Boost Heater
Speci cations subject to change without notice,
all rights reserved.
Temperature sensing with full modulation
Maintains speci c temperature set point
Unique design allows for simpli ed installation
Cooling mode element disable option
Requires 24V external control power supply
ARL listed
Made in the USA
Monticello, Minnesota
800.922.4138
www.electromn.com