Make-Up Air Application




OR



Insert Element Rack
EM-WC0515H - 4,800-watt, 240V
400 CFM rating, 8” x 10”d element rack
EM-WM1535L - 15,000-watt, 240V
1,100 CFM rating, 8” x 16”d element rack
EM-WM2035L - 20,000-watt, 240V
1,300 CFM rating, 8” x 16”d element rack
EM-WC0515L - 4,800-watt, 240V
400 CFM rating, 8” x 16”d element rack
EM-WC1025L - 9,600-watt, 240V
800 CFM rating, 8” x 16”d element rack
EM-WM1134H - 10,800-watt, 208V 3-phase
800 CFM rating, 8” x 10”d element rack
EM-WM1536L - 15,000-watt, 208V 3-phase
1,100 CFM rating, 8” x 16”d element rack
Electrical Source Power:
See nameplate for voltage rating, amp draw, and
maximum watts
120V single-phase, 240V single-phase, or 208V
three-phase - depending upon model and size
120V model has 8’ plug-in cord
All other models, terminal block connections (copper
wire only)
Units above 10 kW include internal fusing
24-volt control:
External 24-volt source is required for operation
Turn-on (on/off function) accomplished with the
presence of 24-volt source
System or external contact closure provides 24 volts
to this unit
Pressure differential switch
Inlet damper end switch
Relay connected to blower motor, contact closure
Exhaust motor current switch contact
Thermostat, blower function “G” (parallel connection)
Temperature sensing thermostat (must also operate
blower)
Packaged Units - Self-Contained, Blower
Contact Factory - Request Document EL007
#/.42/,,%2
%-7%
2
9
#
,
,
,
$5#4
3%.3/2
&//43%.3/2#!",%
0(/.%
-/.4)#%,,/-.
7%342)6%2342%%4
0/"/8
%,%#42/).$5342)%3).#
#OMFORT-ODULE
7ARM&LO
'2/5.$

%84%2.!,
#/.4!#4
6
%-7-,