Spec Sheet

07/15/2010 EL908
STANDARD EQUIPMENT
Stage LED indicators
Quiet DC power relays
Thermostat end switch connection point
Hi-limits, automatic reset - 135° F & 150° F/180° fused link
Compact enclosure
Two element sizes available - 8 x 10 or 8 x 16
5-year element warranty
2-year parts warranty
TEMPERATURE RISE CHART*
Temperature Rise Needed 80° F 70° F 60° F 50° F 40° F 30° F
Model Watts CFM CFM CFM CFM CFM CFM
EM-WM1134H 10800 425 486 567 680 850 1133
EM-WM1535L 14400 567 648 756 907 1133 1511
EM-WM1536L 15000 593 677 790 948 1185 1580
EM-WM2035L 19200 756 863 1007 1209 1511 2015
*Typically the maximum temperature rise for this product is 40° F for room air inlet. If used for make-up air, larger temperature rises are permissible, see table above.
ELECTRIC SUPPLY
Model kW Btu/h Amps Fuse Phase Voltage
Source
CB
Shipping
Weight
Installation
Manual
Minimum
CFM
EM-WM1134H 10.8 36,860 30 40 3-60 208 40 20 EI902 420
EM-WM1535L 14.4 51,190 60 50 + 30 1-60 240 80 19 EI902 560
EM-WM1536L 15 49,150 42 50 3-60 208 60 21 EI902 590
EM-WM2035L 19.2 65,530 80 50 + 50 1-60 240 100 21 EI902 750
CHIP CODE OPTIONS
Switch
Position
BCDEH
0 96° 20° 40° 60° 88°
1 100° 25° 52° 65° 90°
2 104° 30° 64° 70° 92°
3 108° 35° 76° 75° 94°
4 112° 40° 88° 80° 96°
5 116° 45° 100° 85° 98°
6 120° 50° 112° 90° 100°
7 124° 55° 124° 95° 102°
Comfort level temperature setting - choose correct chip code for application. Note: Unless otherwise speci ed, product will be shipped with a default “D” chip.
Specification Sheet - Electric Make-Up Air Heater
Speci cations subject to change without notice,
all rights reserved.
Temperature sensing with full modulation
Maintains speci c temperature set point
Unique design allows for simpli ed installation
Cooling mode element disable option
Requires 24V external control power supply
ARL listed
Made in the USA
Monticello, Minnesota
800.922.4138
www.electromn.com