WarmFlo Electric Plenum Duct Heater Technical Data Manual
SLC Series
This unit is specifi cally designed to be used in conjunction with Bryant Evolution
™
or Carrier
Infi nity
™
heat pump communicating thermostat systems. This unit allows for easy interface to
either the Evolution or the Infi nity system. This unit does not apply to Evolution or Infi nity air
conditioning systems, for air conditioning use WarmFlo Select SL1 Series. Note: The 286A or
288A outdoor unit and the “–B” thermostat control must be used in this application.
Features
▪ Specifi cally designed for Evolution
™
or Infi nity
™
▪ All-inclusive controls, for use with heat pump
▪ Modulates electric elements to maintain precise output temperature
▪ Quiet operation with individual DC relays
▪ Energy control selector
Support Documents
▪ Literature sheet - EL703
▪ Installation manual - EI711
▪ Wiring diagram - EH711
EZ-Mate Series
This unit can be used in conjunction with a single stage heat pump, with one or two-stage air
conditioning, or without air conditioning. This unit is compatible with single or multi-stage gas
or oil furnaces with or without variable speed blowers. This unit includes automatic dual fuel
control, with manual override switch. A conventional 4-wire thermostat must be used when
installing with a heat pump.
Features
▪ Load shed
▪ Application selection dial - HP or non-HP
▪ All-inclusive controls, can be used with either heat pump or air conditioning
▪ Stages electric elements to maintain precise output temperature
▪ Quiet operation with individual DC relays
▪ Energy control selector
Support Documents
▪ Literature sheet - EL830
▪ Installation manual - EI820
▪ Wiring diagrams - EH808, EH810, EH811
WarmFlo
®
Select SLC Series - Wiring & Specifications
EZ-Mate
™
Series - Wiring & Specifications
Upfl ow Downfl ow
kW @
240VAC
Btu/h Amps
Circuit
Breakers
EM-WU102D
†
-SLC EM-WD102D
†
-SLC
10 34,000 21-21 60
EM-WU153D
†
-SLC EM-WD153D
†
-SLC
15 51,000 21-21-21 60-30
EM-WU204D
†
-SLC EM-WD204D
†
-SLC
20 68,000 21-21-21-21 60-60
EM-WU254D
†
-SLC EM-WD254D
†
-SLC
25 85,000 21-21-32-32 60-60-30
†
5 = 15” Wide 8 = 18” Wide
Upfl ow Downfl ow
kW @
240VAC
Btu/h Amps
Circuit
Breakers
Load Shed
CT
EM-LV104L
†
EM-LD104L
†
10 34,000 21-21 60 Yes
EM-LV104Z
†
EM-LD104Z
†
10 34,000 21-21 60 No
†
5 = 15” Wide 8 = 18” Wide
!24
!24