Spec Sheet
10/04/2016 EL910
STANDARD EQUIPMENT
▪ 120V, 14 AWG, SJT type, 15A plug (cord length ≈ 7 ft.)
▪ Hi-limits, automatic reset - 150° F/180° fused link
▪ 20-year element warranty
▪ 2-year parts warranty
▪ Temperature sensing with full modulation
▪ Maintains specifi c temperature set point
▪ 6” round duct section
TEMPERATURE RISE CHART*
Temperature Rise Needed 80° F 70° F 60° F 50° F 40° F 30° F
Model Watts CFM CFM CFM CFM CFM CFM
EM-WX01-120-1-06 1000 40 45 53 63 79 105
*Typically the maximum temperature rise for this product is 40° F for room air inlet. If used for make-up air, larger temperature rises are permissible, see table above.
ELECTRIC SUPPLY
Model kW Btu/h Amps Fuse Phase Voltage
Source
CB
Shipping
Weight
Installation
Manual
Minimum
CFM
Duct
Collar
EM-WX01-120-1-06 1 3,400 8.33 N/A 1-60 120 15 9 EI908 35 6”
CHIP CODE OPTIONS
†
Switch
Position
BCDEH
0 96° 20° 40° 60° 88°
1 100° 25° 52° 65° 90°
2 104° 30° 64° 70° 92°
3 108° 35° 76° 75° 94°
4 112° 40° 88° 80° 96°
5 116° 45° 100° 85° 98°
6 120° 50° 112° 90° 100°
7 124° 55° 124° 95° 102°
†
Comfort level temperature setting - choose correct chip code for application. Note: Unless otherwise specifi ed, product will be shipped with a default “D” chip.
Specification Sheet - Electric Make-Up Air/Boost Heater
Specifi cations subject to change without notice,
all rights reserved.
▪ Quiet DC power relays
▪ Thermostat end switch connection point
▪ Unique design allows for simplifi ed installation
▪ Cooling mode element disable option
▪ Requires external 24V control power supply
▪ Made in the USA
Monticello, Minnesota
800.922.4138
www.electromn.com