Spec Sheet

10/06/2016 EL906
STANDARD EQUIPMENT
240V, single phase - hard-wired, external fusing required
Hi-limits, automatic reset - 118° F/150° F/180° fused link
20-year element warranty
2-year parts warranty
Temperature sensing with full modulation
Maintains speci c temperature set point
8” or 10” round duct section
TEMPERATURE RISE CHART*
Temperature Rise Needed 80° F 70° F 60° F 50° F 40° F 30° F
Model Watts CFM CFM CFM CFM CFM CFM
EM-WX02-240-1-08 2500 99 113 132 158 198 263
EM-WX05-240-1-08 5000 197 225 262 319 393 525
EM-WX10-240-1-10 10000 393 450 525 630 787 1050
*Typically the maximum temperature rise for this product is 40° F for room air inlet. If used for make-up air, larger temperature rises are permissible, see table above.
ELECTRIC SUPPLY
Model kW Btu/h Amps Fuse Phase Voltage
Source
CB
Shipping
Weight
Installation
Manual
Minimum
CFM
Duct
Collar
EM-WX02-240-1-08 2.5 8,500 10.41 N/A 1-50/60 240 15 31 EI909 90 8”
EM-WX05-240-1-08 5 17,000 20.83 N/A 1-50/60 240 30 32 EI909 190 8”
EM-WX10-240-1-10 10 34,000 41.66 N/A 1-50/60 240 60 36 EI909 390 10”
CHIP CODE OPTIONS
Switch
Position
BCDEH
0 96° 20° 40° 60° 88°
1 100° 25° 52° 65° 90°
2 104° 30° 64° 70° 92°
3 108° 35° 76° 75° 94°
4 112° 40° 88° 80° 96°
5 116° 45° 100° 85° 98°
6 120° 50° 112° 90° 100°
7 124° 55° 124° 95° 102°
Comfort level temperature setting - choose correct chip code for application. Note: Unless otherwise speci ed, product will be shipped with a default “D” chip.
Specification Sheet - Electric Make-Up Air/Boost Heater
Speci cations subject to change without notice,
all rights reserved.
Quiet DC power relays
Thermostat end switch connection point
Unique design allows for simpli ed installation
Cooling mode element disable option
Requires 24V external control power supply
Made in the USA
Monticello, Minnesota
800.922.4138
www.electromn.com