Spec Sheet
10/06/2016 EL906
STANDARD EQUIPMENT
▪ 240V, single phase - hard-wired, external fusing required
▪ Hi-limits, automatic reset - 118° F/150° F/180° fused link
▪ 20-year element warranty
▪ 2-year parts warranty
▪ Temperature sensing with full modulation
▪ Maintains specifi c temperature set point
▪ 8” or 10” round duct section
TEMPERATURE RISE CHART*
Temperature Rise Needed 80° F 70° F 60° F 50° F 40° F 30° F
Model Watts CFM CFM CFM CFM CFM CFM
EM-WX02-240-1-08 2500 99 113 132 158 198 263
EM-WX05-240-1-08 5000 197 225 262 319 393 525
EM-WX10-240-1-10 10000 393 450 525 630 787 1050
*Typically the maximum temperature rise for this product is 40° F for room air inlet. If used for make-up air, larger temperature rises are permissible, see table above.
ELECTRIC SUPPLY
Model kW Btu/h Amps Fuse Phase Voltage
Source
CB
Shipping
Weight
Installation
Manual
Minimum
CFM
Duct
Collar
EM-WX02-240-1-08 2.5 8,500 10.41 N/A 1-50/60 240 15 31 EI909 90 8”
EM-WX05-240-1-08 5 17,000 20.83 N/A 1-50/60 240 30 32 EI909 190 8”
EM-WX10-240-1-10 10 34,000 41.66 N/A 1-50/60 240 60 36 EI909 390 10”
CHIP CODE OPTIONS
†
Switch
Position
BCDEH
0 96° 20° 40° 60° 88°
1 100° 25° 52° 65° 90°
2 104° 30° 64° 70° 92°
3 108° 35° 76° 75° 94°
4 112° 40° 88° 80° 96°
5 116° 45° 100° 85° 98°
6 120° 50° 112° 90° 100°
7 124° 55° 124° 95° 102°
†
Comfort level temperature setting - choose correct chip code for application. Note: Unless otherwise specifi ed, product will be shipped with a default “D” chip.
Specification Sheet - Electric Make-Up Air/Boost Heater
Specifi cations subject to change without notice,
all rights reserved.
▪ Quiet DC power relays
▪ Thermostat end switch connection point
▪ Unique design allows for simplifi ed installation
▪ Cooling mode element disable option
▪ Requires 24V external control power supply
▪ Made in the USA
Monticello, Minnesota
800.922.4138
www.electromn.com