Electric Furnace Installation & Operating Instructions HE-E-**-21 Series Application Special non-WarmFlo, non-heat pump, strip heat elements only, full kW turn-on from stat W input. ECM™ blower speed will have to be setup for full kW rating. Heat/cool conventional roomstat applies. DO NOT DESTROY THIS MANUAL. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY A SERVICE TECHNICIAN.
Table of Contents Configurator 1 Inlet Cabinets 2 General Comments 3 Application 4 Installation Requirements 6 Mechanical Installation 7 Electrical Installation 10 Setup or Programming 11 Operation Indicators 11 Replacement Parts 13 Drawings Included: NH808 NH809 NS803 EC001 02/14/2006 NI806
Configurator HE-T-KW-CW Type H, A, E, N (see below) Cabinet Width 21 = 21” 24 = 24”* kW Size 10 = 9.6 kW 15 = 14.4 kW 20 = 19.2 kW* 25 = 24 kW* 30 = 28.8 kW* Type All models – ECM™ blower motor, setup selection of four cooling sizes, 50% continuous air (fan – on setting). High efficient air circulation at about 50-watt. H = Full WarmFlo capability with outdoor sensor. This provides warm air outlet temperature dial selection and supply air ramp up with the decrease of outdoor temperature.
Inlet Cabinets Factory optional cabinets can be configured with this Electric Furnace. Typically these are designed for upflow applications; however, the heat pump coil cabinet could be used in other positions. Side Entry, Filter Cabinet Return air can be ducted into either side, 15-⅜” x 19” cutout hole is provided with one filler plate. Easy access door for checking and changing filter. Adjustable rails are provided for standard 4” x 20” x 20” pleated filter.
General Comments Upflow/Downflow/Horizontal The arrangement of refrigerant coil, hydronics coil, and built-in electric elements need to follow specific air direction or airflow rules, but the orientation of this Electric Furnace is not critical. For upflow and horizontal standard air conditioning applications, the A-coil is mounted at the blower outlet with field provided plenum or manufacturer’s case coil. All models contain GE ECM™ Series 2.3 blower motors.
Installation Checkout Attached to this manual is a warranty certification and checkout procedure. This must be completed and returned for warranty coverage. This is the responsibility of the contractor or company which “sold the job” and is assuming responsibility to the end customer. Warranty Statement See the last page of this manual for detailed limited warranty coverage explanation. Application General The configurator, previous page, details several product types.
Specification Chart Model Number Cabinet Width kW rating Btu/h Voltage/Phase Circuit Breaker Amps per CB Source Feed Elements Relays Heat CFM* Max. Temp.
Installation Requirements 1. All installation work must be performed by trained, qualified contractors or technicians. Electro Industries, Inc., sponsors installation and service schools to assist the installer. Visit our web site at electromn.com for upcoming service schools. WARNING ALL ELECTRICAL WIRING MUST BE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE AND LOCAL ELECTRIC CODES, ORDINANCES, AND REGULATIONS. WARNING OBSERVE ELECTRIC POLARITY AND WIRING COLORS.
Mechanical Installation Clearances and Accessibility Zero clearance is allowed on all sides for combustible materials. However, 36” should be allowed at the front for operation, maintenance, and service. To reduce the risk of rusting and appearance, do not install the unit directly on the ground or on a floor that is likely to be wet. In such environments the unit must be elevated by use of a sturdy non-porous material.
Whether this unit is sitting on or attached to an inlet cabinet, field designed inlet cabinet, or horizontal supports; verify proper support and mechanical strength is provided within the system installation. Rubber isolation pads should be used where possible to reduce sound and vibration transmission. WARNING WHEN HANGING THIS UNIT, THERE MUST BE UNDER SUPPORTS WHICH DISTRIBUTE THE HANGING CHAINS ACROSS THE SURFACE OF THIS UNIT, DO NOT SIMPLY DRILL A HOLE AND USE A COUPLE OF HANGING BOLTS.
Horizontal, Air Conditioning Similar to upflow above, the air conditioning coil is positioned at the blower outlet. Depending upon the coil type and drip pan it is positioned in a field constructed plenum as required. As horizontal, the return air would enter the blower end of the cabinet with a typical packaged 20” x 20” filter cabinet. Horizontal, Heat Pump As emphasized above, the heat pump coil must be at the blower inlet.
Electrical Installation WARNING TO AVOID THE RISK OF ELECTRIC SHOCK OR DEATH, WIRING TO THE UNIT MUST BE PROPERLY GROUNDED. FAILURE TO PROPERLY GROUND THE UNIT CAN RESULT IN A HAZARD LEADING TO PERSONAL INJURY OR DEATH. Line Voltage The nameplate and/or Installation and Operating Manual specification page provides kW rating and operating current requirements for each specific model. Select the proper wire size to comply with your type of wire routing and NEC field wiring requirements.
Cooling, Special Dehumidification The BK tab and the BK peg jumper provide the industry standard 12% blower speed reduction to “pull out” additional moisture from the air. Provide an external humidistat between BK and R and pull or permanently disconnect the BK jumper. With the BK terminal at 0 volts the 12% blower speed reduction is activated. Utility Load Control If applicable for your installation and your utility authorized electric rate, at the bottom of the control board is a blue wire jumper.
Electric Furnace Control – Inside View, Right Board Green, next to Fuse 24-volt power connected and fuse good. Red, next to W Call for electric heat, also represents the input signal (yellow wire) to the WarmFlo control board. Green, Cool Conventional H/C stat has an active Y function or heat pump stat reversing valve is in the cool mode (will depend upon proper setup with RV logic jumper). For 2-speed AC this LED is illuminating during high speed. Amber Represents action within ECM™ blower motor.
Replacement Parts @HEIBG6707 PCB Electric Furnace ECM™ Motor H/C and HP Stat @EMD3I6600 PCB EM DI 3-Stage 5850 Motor ½ HP ECM™ GE 5541 Transformer 120/240:24 40VA 4038 Triac SSR 50-amp 24VDC 5127 Relay NO 25A@277 24VDC Coil 6630 Limit O-150/O-180 25A@240V ST-CLSD 5636 Limit O-135/C-120 25A@240V DP-CLSD 6615 Element DI 4800W@240V 5652 Circuit Breaker SD 60A 5650 Circuit Breaker SD 30A 5651 Circuit Breaker SD 45A 02/14/2006 13 NI806
NON-WARMFLO, HEAT/COOL STAT, A/C (1 SPEED) HE-E-**-21 0 60 70 60 70 8 0 5 5 0 0 8 RV LOGIC-HI T12 J1 COOL R W W G Y UPCB6600B CS Y/Y2 ROOM THERMOSTAT Y1 O G E Y T13 LED6 F Y/Y2 K1 T8 RV(O) TB1 C Y1 T5 K4 T7 Y COM A/C DF(W1) T6 J7 HP RED BRN GRY WHT TO HEAT/COOL R LED1 G C SET JUMPER HEAT TB2 OUTDOOR UNIT J4 ON @EMD3I6600 J4 R HEAT/COOL DETAIL A T1 T14 K2 T1 T2 K3 T4 LED4 T3 RV LOGIC-HI T5 J1 COOL R T3 T7 K6 NO T4 HEAT/COOL Y1 O COM
NON-WARMFLO, HEAT/COOL STAT, A/C (2 SPEED) HE-E-**-21 CONVENTIONAL STAT R W1 G DETAIL A J4 ON A/C Y2 @EMD3I6600 Y1 RV LOGIC-HI R W G W Y2 G TO HEAT/COOL T13 ROOM THERMOSTAT JUMPER Y1 O G E Y LED6 F K1 T8 TB1 C T5 K4 T7 RV(O) T6 Y1 Y2 Y2 C C Y1 DF(W1) J7 HP RED BRN WHT GRY UPCB6600B CS SET Y/Y2 LED1 Y/Y2 C Y1 HEAT R TB2 OUTDOOR UNIT W2 J4 Y1 J1 COOL R HEAT/COOL T12 T1 T14 K2 T1 T2 K3 T4 LED4 T3 RV LOGIC-HI T5 J1 COOL R T3 T7 K6 NO T4 HEAT
Air Handler (HE-E-20-21), Basic Staging ECM WIRING SCHEMATIC AIR HANDLER MODEL: UPCB6600B CS BASIC RW T13 J1 COOL RW T1 T14 RW 135°F ROOM THERMOSTAT R DI K6 K6 Y/Y2 C T8 Y1 T6 T2 K3 E T4 COM R LED4 T3 BK T15 J5A J5B J4 COOL K5 BK J2 C T11 R HECBW5844 150°F E2 6 8 9 9 8 7 BR W 10 T11 24 VAC F1 T12 T9 INTERFACE T10 T14 10 6 5 3 2 1 7 LED3 PWR COM 4 GY 5 BLU/WHT BLUE PC1 BK BK 150°F R HL2 BR R 3 HECBW5848 L2 CB2 W L1 J3 T13 J4
Air Handler (HE-E-15-21), Basic Staging ECM WIRING SCHEMATIC AIR HANDLER MODEL: UPCB6600B CS BASIC STAGING ECM HE-E-15-21 RW T13 RV LOGIC-HI J1 COOL LED6 RW T1 T14 RW 135°F ROOM THERMOSTAT R DI PC2 K6 T4 K6 C T8 Y1 K4 T7 T6 T2 K3 E T4 COM R LED4 T3 BK T15 J5A J5B J4 COOL K5 BK J2 C T11 K7 R NO W1 T10 A J2 B C D ECM 3 LO MED HI 4 6 HECBW5844 150°F T11 24 VAC F1 T12 9 8 7 T9 INTERFACE T10 T14 10 5 6 1 3 2 4 BR W BLU/WHT BLUE PC1 BK BK
Air Handler (HE-E-10-21), Basic Staging ECM WIRING SCHEMATIC AIR HANDLER BASIC STAGING ECM MODEL: HE-E-10-21 UPCB6600B CS RW T13 RV LOGIC-HI J1 COOL LED6 RW T1 T14 RW 135°F ROOM THERMOSTAT R DI PC2 K6 T4 K6 C T8 Y1 K4 T7 T6 T2 K3 E T4 COM R LED4 T3 BK T15 C T11 NO W1 K7 J2 B C D J2 ECM 3 LO MED HI 4 6 J3 8 LED3 9 T11 24 VAC F1 T12 INTERFACE T13 L2 E2 9 8 7 10 5 6 1 3 2 T9 T10 T14 BLU/WHT BLUE PC1 R 150°F BR GY BK W HL2 BK R 4
Electro Industries, Inc. Limited Product Warranty Effective February 5, 2009 Electro Industries, Inc. warrants to the original owner, at the original installation site, for a period of two (2) years from date of installation, that the product and product parts manufactured by Electro Industries are free from manufacturing defects in materials and workmanship, when used under normal conditions and when such product has not been modified or changed in any manner after leaving the plant of Electro Industries.
THESE WARRANTIES DO NOT COVER: 1. Costs for labor for removal and reinstallation of an alleged defective product or product parts, transportation to Electro Industries, and any other materials necessary to perform the exchange, except as stated in this warranty. Replacement material will be invoiced to the distributor in the usual manner and will be subject to adjustment upon verification of defect. 2.