Operating instructions
02/14/2006 9  NI806 
Horizontal, Air Conditioning 
Similar to upflow above, the air conditioning coil is positioned at the blower outlet. Depending upon the 
coil type and drip pan it is positioned in a field constructed plenum as required. 
As horizontal, the return air would enter the blower end of the cabinet with a typical packaged 20” x 20” 
filter cabinet. 
Horizontal, Heat Pump 
As emphasized above, the heat pump coil must be at the blower inlet. Depending upon the coil physical 
arrangements and drip pan, it is installed in a field constructed plenum at the blower inlet. 
Typically a package filter cabinet is installed at the entrance (or ahead of) of the HP coil. 
The blower outlet goes directly into the distribution duct system. 
Blower Motor Orientation 
If the installation is not upflow, the blower motor shall be positioned so the power and control connectors 
are down. This will prevent water from entering the blower motor through the connector housing 
opening. 
Loosen motor mount clamp and rotate motor accordingly. 
Before tightening motor mount clamp be sure the blower wheel is properly centered inside the blower 
housing. 