Installation Instruction

19 ENGLISH
3.7 Water-pump drainage
The maximum lifting height is 750mm.
Fig.24
3.8 Drainage pipe installation
1. Installation principle
Ensure at least 1/100 slope of the
drainage pipe.
Adopt suitable pipe diameter
Adopt nearby condensate water
discharge.
Before installing condensate water
pipeline, determine its route and
elevation to avoid intersection with
other pipelines and ensure slope is
straight.
In general, the supporter gap of the
drainage pipe horizontal pipe and
vertical pipe is respectively 1m~1.5m
and 1.5m~2.0m.
Fig.25
2. Drainage pipe selection
The drainage pipe diameter shall not
small than the drain hose of indoor unit.
According to the water owrate and
drainage pipe slope to choose the
suitable pipe, the water owrate is
decided by the capacity of indoor unit.
Capacity(Btu/h) Water owrate(l/h)
9000 2
12000 2.4
18000 4
According to the above table to
calculate the total water owrate for the
conuence pipe selection.
The horizontal pipe layout should avoid
converse ow or bad ow(Fig 26):
Fig.26
<200mm
1-1.5M
<750mm
Lean over 1/50
Pump-pipe clasp
(the ttings)
Too long distance
Gas bag
Drainage pipe
Water ow
Water ow
Water ow
Water ow
Water ow
Water ow
Drainage pipe
Drain tee
Drain tee