Installation manual

20
Installation
Exhaust duct
• Theexhaustductmustbesmoothontheinside(lowairresistance).
• Theexhaustductmustleadtotheoutdoors.
• Theexhaustductmustleadclearofthebuildingascondensationmay
cause frost damage to the building.
• Theexhaustductmustbeprotectedagainstrainandforeignobjects.
• Theexhaustductmusthavegentlebends.
• Theexhaustductmustnotbeasharedductbetweendryersandappli-
ances using gas or other fuels as their energy source.
When several dryers share an exhaust duct
• Theexhaustductdiametermustincreaseaftereachdryer.
The table below shows the exhaust duct diameter and the necessary
fresh-air inlet area.
Note! It is recommended that each dryer is connected to a separate
exhaust duct.
The evacuation pipe diameter must not be reduced.
No. of dryers 1 2 3 4 5 6 7 8 9 10
Air outlet pipe
diameter in mm 200 280 315 355 400 450 475 500 535 560
Required area of
fresh-air inlet m
2
0.15 0.30 0.45 0.60 0.75 0.90 1.05 1.20 1.35 1.50
Each dryer requires a 400 x 400 mm fresh-air inlet opening.