User Manual Part 2
APPENDIX D
SOFTWARE COMMANDS
Revised: 13 Sep 05 APX D- 11 EST P/N AA104
S/N
Serial Number command. When executed from the Command Model will output the ESTeem serial number of the unit that is
defined at the time of manufacturer.
SQDCTRL (on/off)
This function enables the Square D controller protocol. For further detail Reference the EST Engineering Report on Square D
controller interfacing.
Factory default = OFF.
SQDADD (1-254)
This function is used with the SQDCTRL command to control the address fence when using SQ-D Network Interface Modules.
For further details reference the EST Engineering Report on the SQ-D controller.
Factory default = 0.
SQUELCH (0-3)
This command defines the squelch threshold of the receiver. Listed below are the settings:
0 = -101 dBm 2µV
1 = - 93 dBm 5µV
2 = - 87 dBm 10µV
3 = - 70 dBm 70µV
Factory default = 0.
TERMCont (on/off)
The RS-232C/422/485 receive termination timer.
ON: If there are characters in the RS-232 buffer and the modem is in Converse Mode, the termination timer starts from the
time the last receive character is updated in the buffer. If the termination time expires before another character is
received, the characters are transmitted.
OFF: Disabled
Factory default = OFF.
TERMTime (10-65535)
The RS-232C/422/485 receive termination timer value. This value can be 10 to 65535 milliseconds. This value is enabled by
TERMCONT. Factory default = 5O.
TRANSPAR (on/off)
The transparent mode command. This mode allows the ESTeem link to be completely transparent to the communicating
RS-232/422/485 devices. Reference Chapter 2.
ON: Enabled.
OFF: Disabled.
Factory default = OFF.
TXSTAT
This command outputs the total number of rf transmissions vs. the total number of retries. After output is completed, the counter
is zeroed.