4.4: Periodic Test Timer Reset 
The control panel sends the periodic test event code (address 57) to the central station 
once every 24 hours. The first transmission of this code is sent 12 hours after power is 
applied to the control panel. If a different time is required, you can program the control 
panel to send the first periodic test message 24 hours after the periodic test timer is 
reset. 
To reset the periodic test timer: 
1. Press 
4, 7 to enter programming mode. 
2.  Enter the Installer Code; the Armed LED lights up and the System LED flashes. 
3. Enter 
99; the periodic test timer is reset and the periodic test code is sent to the 
central station. 
4. Press 
# to exit programming mode. 