Fig. 17 Since this application uses a 30:5 ratio cur-
rent transformer the AC-24 controller must be ad-
justed to read 30.0 full scale. Press and hold the 
Coarse Display Range and Down arrow until 30.0 is 
displayed. For finer adjustment use the Fine Dis-
play Range. 
Fig. 18 Start the wheel motor and 
place a clamp-on type ammeter on 
the motor leads to confirm calibration 
of both the panel ammeter and the 
AC-24 controller display. 
Note: The AC-24 controller zero and 
span have been factory set. Minor 
adjustments may be needed. Press 
the Span button along with up/down 
arrows to change value. Release the 
Span Button to see new amperage 
readings. Make the controller reading 
match the clamp-on ammeter read-
ing. Even though there is no shot 
flow, ammeter readings will show the 
no load or no flow rate values. Note 
that the clamp-on ammeter and the 
AC-24 Controller digital display show 
the no load motor amperage to be 
about 8.8 amps, while the panel me-
ter shows over 9 amps. 
Fig. 17 
Fig. 18  