User Manual

2        
WHEEL
MOTOR
WIRE CONNECTIONS FOR VLP-24 OR LP-24 TO AN AC-24 AMPERAGE CONTROLLER
L1
L2
L3
Customer CT
100:5 etc.
0-5 amps
Current Shunt
.05 ohm 5 watt.
P/N 999200
Included with
controller.
NOTE : The valve must be located as close to the wheel
    as possible for best servo control stabilit
y
.
(
 5 feet or closer
)
0
100
(0-5A)
PANEL METER
(IF USED)
www.magnavalve.com
Remote setpoint can come 
from customer potentiometer 
or 0-10 Vdc signal. Also see 
model Pot-24 remote pot.
7
5
2
CW
*
0 Vdc
common
.05 Ohm shunt
.05 Ohm shunt
VLP-24 Orange
VLP-24 Blue +24Vdc to VLP-24 RED
0Vdc to VLP-24 BLACK
Note: Connect power supply directly to the MagnaValve first and then run power back to the control using minimum 16 AWG 
wire size to prevent (high current ) voltage drops. Power supply should be regulated and rated at 50VA per valve.
Alternate: Long length of current loop may cause 
inaccuracy. To keep the 0-5 Amp current loop short 
you may place the .05 ohm shunt at the transformer 
terminals and run 18AWG shielded cable from shunt 
to control.
NOTE: The Controller's Full Scale display (typical 
100.0) must match the customer's current 
transformer rating (typical 100:5 ratio). Adjust the 
control display range to match the actual 
transformer ratio. See instruction manual. 
1
2
4
5
6
3
1. WHITE
2. RED
3. GREEN
4. ORANGE
5. BLACK
6. BLUE
VLP-24/LP-24
4) Orange 0-10 Vdc input
6) Blue 24 Vdc Enable
2) Red 24 Vdc Supply
5) Black 0 Vdc Common
AC-24 Controller
 8) Servo Out
 9) Valve Enable
19) 24 Vdc Supply
20) 0 Vdc Common
Use 12 AWG wire for current loop. Use 
10 AWG or larger  for runs over 15 ft. 
AC-24 Rear Terminal