Installation Manual Gas Fires Cupido 70 CF

APPENDICES
25
D LOCATION TERMINAL
D.1 Terminal location with vertical exhaust (B11)
Distance Exhaust 1,2 of 3
At the same roof level > 6m *
At a different roof level > 3m * & **
On a lower wall > 2m *
On a higher sloping surface > 6m ***
Distance” = minimum distance required to position the exhaust
in order to prevent adverse e ects in relation to;
1. A ventilation opening of a used room, toilet or bathroom
2. Supply of heated air when the supply flows through a used
room.
3. A window that can be opened and located in the vicinity of
a used room, toilet or bathroom.
* If the required distance is not feasible, the rules regarding the exit
position have priority.
** If the exhaust is placed at least one meter higher than the inlet
opening, or a window that can be opened.
*** If the required distance is not feasible, the exhaust must be placed at
least one meter above the highest façade / roof.
(4) The terminal may not be placed closer than 300 mm to an opening in
the building such as a window frame.
P
Q
Q
Q
C
D,E
A
B
J
J
F
I
Q
N
M
K
H
H
Figure D.1 - Terminal Location