Instructions

ELEQ b.v.
Tukseweg 130, 8331 LH Steenwijk
The Netherlands
+31 (0) 521 533 333
+31 (0) 521 533 391
info@eleq.com
www.eleq.com
Technical Specifications
Safety and environmental conditions
CE marking
LV directive 2006/95/EC
RoHS directive 2011/65/EU
Standard
EN 61010-2-032:2012
WEEE directive 2012/19/EU
This product is designed to be safe under the following
conditions:
Location
Altitude
Ambient temperature
Storage temperature
Relative humidity
Pollution degree
Degree of protection
Indoor use
Up to 2000m
TQ30: -5°C .. +40°C
TQ
40, TQ50: -10°C .. +55°C
-20°C .. +70°C
5% .. 85%, non condensing
2
IP20
The TQ is only suitable for insulated primary conductors.
Specifications
Standard
Rated short-time thermal
current (Ith)
Rated dynamic current (Idyn)
Rated continuous thermal
current (Icth)
Rated insulation level
Rated frequency
Class of insulation
Material (housing)
IEC 61869-2:2012
60 x Ipr / 1s
2,5 x Ith
100%
0,72/3/-kV
50/60Hz
E (120
°C)
PA 6.6, UL94: V2
Specifications per type
TQ30 TQ40-B TQ40-C TQ50-E TQ50-L
Suitable for
cable
ø
18mm
ø
18mm
ø
28mm
ø
42mm
2x
ø
42mm
../1A
Secondary
leads length
for 0,5mm
2
3m 3m 3m 3m 3m
Approximate
weight
360g 310g 450g 650g 200g
../5A
Secondary
leads format
/
0,5 meter
ø
1,5mm
0,5 meter
ø
1,5mm
3 meter
ø
1,5mm
3 meter
ø
1,5mm
Approximate
weight
/ 300g 250g 650g 850g
ELEQ reserves the right to carry out modifications on its products, in
order to improve them,
without prior notice.
Safety instruction
All activities for installation, commissioning and maintenance
of this current transformer must be performed by qualified
personnel that have the knowledge of applicable safety
precautions. This guide assumes that the reader of this
document has sufficient electro-technical knowledge to
understand the content of this
document.
General
The TQ split-core is a current transformer (CT) and can only
be used for measuring electrical alternating currents. The TQ
is suitable only for mounting on insulated primary conductors
in a weather protected and dry location.
Explanation of symbols
This product is designed according to the
EN-IEC 61010-2-032:2012 standards and therefore
this product meets the requirements of the Low
Voltage Directive 2006/95/EC.
Do not apply around or rem
ove from UNINSULATED
HAZARDOUS LIVE conductors, which may render
electric shock, electric burn, or arc flash.
Read the installation guide before mounting the
product. Unprofessional work activities on electrical
installations may result in a threat of danger to the life
and health of human beings and livestock!
Under no circumstances the secondary circuit of the
CT may be opened when the CT is closed and
current i
s flowing in the primary circuit. High voltages
may appear on the secondary leads when this circuit
is left open.
R
oHS Directive 2011/65/EU
ELEQ states that they only uses qualified components
in their products from manufacturers, whose
specifications meet or exceed the requirements of the
European Directive for the Restriction of use of
certain Hazardous Substances.
WEEE Directive 2012/19/EU
The 'crossed out whee
l
ed bin' symbol indicates that
the equipment should not be disposed as unsorted
municipal waste. Contact a qualified recycler for
disposal.
TQ Split-Core Current Transformer
Installation Guide
TQ30 (4M3Qxx)
TQ30 (4Q3Bxx)
TQ40-B (4Q4Bxx)
TQ40-C (4Q4Cxx)
TQ50-E (4Q5Rxx, 4Q5Exx)
TQ50-L (4Q5Mxx, 4Q5Lxx)
Read this installation guide before installing the product
83564 / EN1311
Technical Specifications
Safety and environmental conditions
CE marking
LV directive 2006/95/EC
RoHS directive 2011/65/EU
Standard
EN 61010-2-032:2012
WEEE directive 2012/19/EU
This product is designed to be safe under the following
conditions:
Location
Altitude
Ambient temperature
Storage temperature
Relative humidity
Pollution degree
Degree of protection
Indoor use
Up to 2000m
TQ30: -5°C .. +40°C
TQ
40, TQ50: -10°C .. +55°C
-20°C .. +70°C
5% .. 85%, non condensing
2
IP20
The TQ is only suitable for insulated primary conductors.
Specifications
Standard
Rated short-time thermal
current (Ith)
Rated dynamic current (Idyn)
Rated continuous thermal
current (Icth)
Rated insulation level
Rated frequency
Class of insulation
Material (housing)
IEC 61869-2:2012
60 x Ipr / 1s
2,5 x Ith
100%
0,72/3/-kV
50/60Hz
E (120
°C)
PA 6.6, UL94: V2
Specifications per type
TQ30 TQ40-B TQ40-C TQ50-E TQ50-L
Suitable for
cable
ø
18mm
ø
18mm
ø
28mm
ø
42mm
2x
ø
42mm
../1A
Secondary
leads length
for 0,5mm
2
3m 3m 3m 3m 3m
Approximate
weight
360g 310g 450g 650g 200g
../5A
Secondary
leads format
/
0,5 meter
ø
1,5mm
0,5 meter
ø
1,5mm
3 meter
ø
1,5mm
3 meter
ø
1,5mm
Approximate
weight
/ 300g 250g 650g 850g
ELEQ reserves the right to carry out modifications on its products, in
order to improve them,
without prior notice.
Safety instruction
All activities for installation, commissioning and maintenance
of this current transformer must be performed by qualified
personnel that have the knowledge of applicable safety
precautions. This guide assumes that the reader of this
document has sufficient electro-technical knowledge to
understand the content of this
document.
General
The TQ split-core is a current transformer (CT) and can only
be used for measuring electrical alternating currents. The TQ
is suitable only for mounting on insulated primary conductors
in a weather protected and dry location.
Explanation of symbols
This product is designed according to the
EN-IEC 61010-2-032:2012 standards and therefore
this product meets the requirements of the Low
Voltage Directive 2006/95/EC.
Do not apply around or remove from UNINSULATED
HAZ
ARDOUS LIVE conductors, which may render
electric shock, electric burn, or arc flash.
Read the installation guide before mounting the
product. Unprofessional work activities on electrical
installations may result in a threat of danger to the life
and health of human beings and livestock!
Under no circumstances the secondary circuit of the
CT may be opened when the CT is closed and
current is flowing in the primary
circuit. High voltages
may appear on the secondary leads when this circuit
is left open.
R
oHS Directive 2011/65/EU
ELEQ states that they only uses qualified components
in their products from manufacturers, whose
specifications meet or exceed the requirements of the
European Directive for the Restriction of use of
certain Hazardous Substances.
WEEE Directive 2012/19/EU
The 'crossed out wheeled bin' symbol indicate
s that
the equipment should not be disposed as unsorted
municipal waste. Contact a qualified recycler for
disposal.
TQ Split-Core Current Transformer
Installation Guide
TQ30 (4M3Qxx)
TQ30 (4Q3Bxx)
TQ40-B (4Q4Bxx)
TQ40-C (4Q4Cxx)
TQ50-E (4Q5Exx)
TQ50-L (4Q5Lxx)
Read this installation guide before installing the product
83564 / EN1311
ELEQ b.v.
Tukseweg 130, 8331 LH Steenwijk
The Netherlands
+31 (0) 521 533 333
+31 (0) 521 533 391
info@eleq.com
www.eleq.com
83564 / EN1311
Technical Specifications
Safety and environmental conditions
CE marking
LV directive 2006/95/EC
RoHS directive 2011/65/EU
Standard
EN 61010-2-032:2012
WEEE directive 2012/19/EU
This product is designed to be safe under the following
conditions:
Location
Altitude
Ambient temperature
Storage temperature
Relative humidity
Pollution degree
Degree of protection
Indoor use
Up to 2000m
-10°C .. +55°C
-20°C ..
+70°C
5% .. 85%, non condensing
2
IP20
The TQ is only suitable for insulated primary conductors.
Specifications
Standard
Rated short-time thermal current (Ith)
Rated dynamic current (Idyn)
Rated continuous thermal current (Icth)
Rated insulation level
Rated frequency
Class of insulation
Material (housing)
IEC 61869-2:2012
60 x Ipr / 1s
2,5 x Ith
100%
0,72/3/-kV
50/60Hz
E (120°C)
PA 6.6, UL
94: V2
Specifications per type
TQ30 TQ40-B TQ40-C TQ50-E TQ50-L
Suitable for
cable
ø
18mm
ø
18mm
ø
28mm
ø
42mm
2x
ø
42mm
../1A
Secondary
leads length
for 0,5mm
2
3m 3m 5m 5m 3m
Approximate
weight
360g 310g 525g 725g 200g
../5A
Secondary
leads format
/
0,5 meter
ø
1,5mm
0,5 meter
ø
1,5mm
3 meter
ø
1,5mm
3 meter
ø
1,5mm
Approximate
weight
/ 300g 250g 650g 850g
ELEQ reserves the right to carry out modifications on its products, in
order to improve them, without p
rior notice.
ELEQ b.v.
Tukseweg 130, 8331 LH Steenwijk
The Netherlands
+31 (0) 521 533 333
+31 (0) 521 533 391
info@eleq.com
www.eleq.com
Technical Specifications
Safety and environmental conditions
CE marking
LV directive 2006/95/EC
RoHS directive 2011/65/EU
Standard
EN 61010-2-032:2012
WEEE directive 2012/19/EU
This product is designed to be safe under the following
conditions:
Location
Altitude
Ambient temperature
Storage temperature
Relative humidity
Pollution degree
Degree of protection
Indoor use
Up to 2000m
TQ30: -5°C .. +40°C
TQ
40, TQ50: -10°C .. +55°C
-20°C .. +70°C
5% .. 85%, non condensing
2
IP20
The TQ is only suitable for insulated primary conductors.
Specifications
Standard
Rated short-time thermal
current (Ith)
Rated dynamic current (Idyn)
Rated continuous thermal
current (Icth)
Rated insulation level
Rated frequency
Class of insulation
Material (housing)
IEC 61869-2:2012
60 x Ipr / 1s
2,5 x Ith
100%
0,72/3/-kV
50/60Hz
E (120
°C)
PA 6.6, UL94: V2
Specifications per type
TQ30 TQ40-B TQ40-C TQ50-E TQ50-L
Suitable for
cable
ø
18mm
ø
18mm
ø
28mm
ø
42mm
2x
ø
42mm
../1A
Secondary
leads length
for 0,5mm
2
3m 3m 3m 3m 3m
Approximate
weight
360g 310g 450g 650g 200g
../5A
Secondary
leads format
/
0,5 meter
ø
1,5mm
0,5 meter
ø
1,5mm
3 meter
ø
1,5mm
3 meter
ø
1,5mm
Approximate
weight
/ 300g 250g 650g 850g
ELEQ reserves the right to carry out modifications on its products, in
order to improve them,
without prior notice.
Safety instruction
All activities for installation, commissioning and maintenance
of this current transformer must be performed by qualified
personnel that have the knowledge of applicable safety
precautions. This guide assumes that the reader of this
document has sufficient electro-technical knowledge to
understand the content of this
document.
General
The TQ split-core is a current transformer (CT) and can only
be used for measuring electrical alternating currents. The TQ
is suitable only for mounting on insulated primary conductors
in a weather protected and dry location.
Explanation of symbols
This product is designed according to the
EN-IEC 61010-2-032:2012 standards and therefore
this product meets the requirements of the Low
Voltage Directive 2006/95/EC.
Do not apply around or rem
ove from UNINSULATED
HAZARDOUS LIVE conductors, which may render
electric shock, electric burn, or arc flash.
Read the installation guide before mounting the
product. Unprofessional work activities on electrical
installations may result in a threat of danger to the life
and health of human beings and livestock!
Under no circumstances the secondary circuit of the
CT may be opened when the CT is closed and
current i
s flowing in the primary circuit. High voltages
may appear on the secondary leads when this circuit
is left open.
R
oHS Directive 2011/65/EU
ELEQ states that they only uses qualified components
in their products from manufacturers, whose
specifications meet or exceed the requirements of the
European Directive for the Restriction of use of
certain Hazardous Substances.
WEEE Directive 2012/19/EU
The 'crossed out whee
l
ed bin' symbol indicates that
the equipment should not be disposed as unsorted
municipal waste. Contact a qualified recycler for
disposal.
TQ Split-Core Current Transformer
Installation Guide
TQ30 (4M3Qxx)
TQ30 (4Q3Bxx)
TQ40-B (4Q4Bxx)
TQ40-C (4Q4Cxx)
TQ50-E (4Q5Rxx, 4Q5Exx)
TQ50-L (4Q5Mxx, 4Q5Lxx)
Read this installation guide before installing the product
83564 / EN1311
Technical Specifications
Safety and environmental conditions
CE marking
LV directive 2006/95/EC
RoHS directive 2011/65/EU
Standard
EN 61010-2-032:2012
WEEE directive 2012/19/EU
This product is designed to be safe under the following
conditions:
Location
Altitude
Ambient temperature
Storage temperature
Relative humidity
Pollution degree
Degree of protection
Indoor use
Up to 2000m
TQ30: -5°C .. +40°C
TQ
40, TQ50: -10°C .. +55°C
-20°C .. +70°C
5% .. 85%, non condensing
2
IP20
The TQ is only suitable for insulated primary conductors.
Specifications
Standard
Rated short-time thermal
current (Ith)
Rated dynamic current (Idyn)
Rated continuous thermal
current (Icth)
Rated insulation level
Rated frequency
Class of insulation
Material (housing)
IEC 61869-2:2012
60 x Ipr / 1s
2,5 x Ith
100%
0,72/3/-kV
50/60Hz
E (120
°C)
PA 6.6, UL94: V2
Specifications per type
TQ30 TQ40-B TQ40-C TQ50-E TQ50-L
Suitable for
cable
ø
18mm
ø
18mm
ø
28mm
ø
42mm
2x
ø
42mm
../1A
Secondary
leads length
for 0,5mm
2
3m 3m 3m 3m 3m
Approximate
weight
360g 310g 450g 650g 200g
../5A
Secondary
leads format
/
0,5 meter
ø
1,5mm
0,5 meter
ø
1,5mm
3 meter
ø
1,5mm
3 meter
ø
1,5mm
Approximate
weight
/ 300g 250g 650g 850g
ELEQ reserves the right to carry out modifications on its products, in
order to improve them,
without prior notice.
Safety instruction
All activities for installation, commissioning and maintenance
of this current transformer must be performed by qualified
personnel that have the knowledge of applicable safety
precautions. This guide assumes that the reader of this
document has sufficient electro-technical knowledge to
understand the content of this
document.
General
The TQ split-core is a current transformer (CT) and can only
be used for measuring electrical alternating currents. The TQ
is suitable only for mounting on insulated primary conductors
in a weather protected and dry location.
Explanation of symbols
This product is designed according to the
EN-IEC 61010-2-032:2012 standards and therefore
this product meets the requirements of the Low
Voltage Directive 2006/95/EC.
Do not apply around or remove from UNINSULATED
HAZ
ARDOUS LIVE conductors, which may render
electric shock, electric burn, or arc flash.
Read the installation guide before mounting the
product. Unprofessional work activities on electrical
installations may result in a threat of danger to the life
and health of human beings and livestock!
Under no circumstances the secondary circuit of the
CT may be opened when the CT is closed and
current is flowing in the primary
circuit. High voltages
may appear on the secondary leads when this circuit
is left open.
R
oHS Directive 2011/65/EU
ELEQ states that they only uses qualified components
in their products from manufacturers, whose
specifications meet or exceed the requirements of the
European Directive for the Restriction of use of
certain Hazardous Substances.
WEEE Directive 2012/19/EU
The 'crossed out wheeled bin' symbol indicate
s that
the equipment should not be disposed as unsorted
municipal waste. Contact a qualified recycler for
disposal.
TQ Split-Core Current Transformer
Installation Guide
TQ30 (4M3Qxx)
TQ30 (4Q3Bxx)
TQ40-B (4Q4Bxx)
TQ40-C (4Q4Cxx)
TQ50-E (4Q5Exx)
TQ50-L (4Q5Lxx)
Read this installation guide before installing the product
83564 / EN1311
ELEQ b.v.
Tukseweg 130, 8331 LH Steenwijk
The Netherlands
+31 (0) 521 533 333
+31 (0) 521 533 391
info@eleq.com
www.eleq.com
83564 / EN1311
Technical Specifications
Safety and environmental conditions
CE marking
LV directive 2006/95/EC
RoHS directive 2011/65/EU
Standard
EN 61010-2-032:2012
WEEE directive 2012/19/EU
This product is designed to be safe under the following
conditions:
Location
Altitude
Ambient temperature
Storage temperature
Relative humidity
Pollution degree
Degree of protection
Indoor use
Up to 2000m
-10°C .. +55°C
-20°C .. +70°C
5% .. 85%, non condensing
2
IP20
The TQ is only suitable for insulated primary conductors.
Specifications
Standard
Rated short-time thermal current (Ith)
Rated dynamic current (Idyn)
Rated continuous thermal current (Icth)
Rated insulation level
Rated frequency
Class of insulation
Material (housing)
IEC 61869-2:2012
60 x Ipr / 1s
2,5 x Ith
100%
0,72/3/-kV
50/60Hz
E (120°C)
PA 6.6, UL94: V2
Specifications per type
TQ30 TQ40-B TQ40-C TQ50-E TQ50-L
Suitable for
cable
ø
18mm
ø
18mm
ø
28mm
ø
42mm
2x
ø
42mm
../1A
Secondary
leads length
for 0,5mm
2
3m 3m 5m 5m 3m
Approximate
weight
360g 310g 525g 725g 200g
../5A
Secondary
leads format
/
0,5 meter
ø
1,5mm
0,5 meter
ø
1,5mm
3 meter
ø
1,5mm
3 meter
ø
1,5mm
Approximate
weight
/ 300g 250g 650g 850g
ELEQ reserves the right to carry out modifications on its products, in
order to improve them, without prior notice.
Safety instruction
All activities for installation, commissioning and maintenance
of this current transformer must be performed by qualified
personnel that have the knowledge of applicable safety
precautions. This guide assumes that the reader of this
document has sufficient electro-technical knowledge to
understand the content of this
document.
General
The TQ split-core is a current transformer (CT) and can only
be used for measuring electrical alternating currents. The TQ
is suitable only for mounting on insulated primary conductors
in a weather protected and dry location.
Explanation of symbols
This product is designed according to the
EN-IEC 61010-2-032:2012 standards and therefore
this product meets the requirements of the Low
Voltage Directive 2006/95/EC.
Do not apply around or remove from UNINSULATED
HAZ
ARDOUS LIVE conductors, which may render
electric shock, electric burn, or arc flash.
Read the installation guide before mounting the
product. Unprofessional work activities on electrical
installations may result in a threat of danger to the life
and health of human beings and livestock!
Under no circumstances the secondary circuit of the
CT may be opened when the CT is closed and
current is flowing in the primary
circuit. High voltages
may appear on the secondary leads when this circuit
is left open.
R
oHS Directive 2011/65/EU
ELEQ states that they only uses qualified components
in their products from manufacturers, whose
specifications meet or exceed the requirements of the
European Directive for the Restriction of use of
certain Hazardous Substances.
WEEE Directive 2012/19/EU
The 'crossed out wheeled bin' sym
bol indicate
s that
the equipment should not be disposed as
unsorted
municipal w
aste. Contact a qualified recycler for
disposal.
TQ Split-Core Current Transformer
Installation Guide
TQ30 (4M3Qxx)
TQ30 (4Q3Bxx)
TQ40-B (4Q4Bxx)
TQ40-C (4Q4Cxx)
TQ50-E (4Q5Exx)
TQ50-L (4Q5Lxx)
Read this installation guide before installing the product
83564 / EN1311
ELEQ b.v.
Tukseweg 130, 8331 LH Steenwijk
The Netherlands
+31 (0) 521 533 333
+31 (0) 521 533 391
info@eleq.com
www.eleq.com
Technical Specifications
Safety and environmental conditions
CE marking
LV directive 2006/95/EC
RoHS directive 2011/65/EU
Standard
EN 61010-2-032:2012
WEEE directive 2012/19/EU
This product is designed to be safe under the following
conditions:
Location
Altitude
Ambient temperature
Storage temperature
Relative humidity
Pollution degree
Degree of protection
Indoor use
Up to 2000m
TQ30: -5°C .. +40°C
TQ
40, TQ50: -10°C .. +55°C
-20°C .. +70°C
5% .. 85%, non condensing
2
IP20
The TQ is only suitable for insulated primary conductors.
Specifications
Standard
Rated short-time thermal
current (Ith)
Rated dynamic current (Idyn)
Rated continuous thermal
current (Icth)
Rated insulation level
Rated frequency
Class of insulation
Material (housing)
IEC 61869-2:2012
60 x Ipr / 1s
2,5 x Ith
100%
0,72/3/-kV
50/60Hz
E (120
°C)
PA 6.6, UL94: V2
Specifications per type
TQ30 TQ40-B TQ40-C TQ50-E TQ50-L
Suitable for
cable
ø
18mm
ø
18mm
ø
28mm
ø
42mm
2x
ø
42mm
../1A
Secondary
leads length
for 0,5mm
2
3m 3m 3m 3m 3m
Approximate
weight
360g 310g 450g 650g 200g
../5A
Secondary
leads format
/
0,5 meter
ø
1,5mm
0,5 meter
ø
1,5mm
3 meter
ø
1,5mm
3 meter
ø
1,5mm
Approximate
weight
/ 300g 250g 650g 850g
ELEQ reserves the right to carry out modifications on its products, in
order to improve them,
without prior notice.
Safety instruction
All activities for installation, commissioning and maintenance
of this current transformer must be performed by qualified
personnel that have the knowledge of applicable safety
precautions. This guide assumes that the reader of this
document has sufficient electro-technical knowledge to
understand the content of this
document.
General
The TQ split-core is a current transformer (CT) and can only
be used for measuring electrical alternating currents. The TQ
is suitable only for mounting on insulated primary conductors
in a weather protected and dry location.
Explanation of symbols
This product is designed according to the
EN-IEC 61010-2-032:2012 standards and therefore
this product meets the requirements of the Low
Voltage Directive 2006/95/EC.
Do not apply around or rem
ove from UNINSULATED
HAZARDOUS LIVE conductors, which may render
electric shock, electric burn, or arc flash.
Read the installation guide before mounting the
product. Unprofessional work activities on electrical
installations may result in a threat of danger to the life
and health of human beings and livestock!
Under no circumstances the secondary circuit of the
CT may be opened when the CT is closed and
current i
s flowing in the primary circuit. High voltages
may appear on the secondary leads when this circuit
is left open.
R
oHS Directive 2011/65/EU
ELEQ states that they only uses qualified components
in their products from manufacturers, whose
specifications meet or exceed the requirements of the
European Directive for the Restriction of use of
certain Hazardous Substances.
WEEE Directive 2012/19/EU
The 'crossed out whee
l
ed bin' symbol indicates that
the equipment should not be disposed as unsorted
municipal waste. Contact a qualified recycler for
disposal.
TQ Split-Core Current Transformer
Installation Guide
TQ30 (4M3Qxx)
TQ30 (4Q3Bxx)
TQ40-B (4Q4Bxx)
TQ40-C (4Q4Cxx)
TQ50-E (4Q5Rxx, 4Q5Exx)
TQ50-L (4Q5Mxx, 4Q5Lxx)
Read this installation guide before installing the product
83564 / EN1311
Technical Specifications
Safety and environmental conditions
CE marking
LV directive 2006/95/EC
RoHS directive 2011/65/EU
Standard
EN 61010-2-032:2012
WEEE directive 2012/19/EU
This product is designed to be safe under the following
conditions:
Location
Altitude
Ambient temperature
Storage temperature
Relative humidity
Pollution degree
Degree of protection
Indoor use
Up to 2000m
TQ30: -5°C .. +40°C
TQ
40, TQ50: -10°C .. +55°C
-20°C .. +70°C
5% .. 85%, non condensing
2
IP20
The TQ is only suitable for insulated primary conductors.
Specifications
Standard
Rated short-time thermal
current (Ith)
Rated dynamic current (Idyn)
Rated continuous thermal
current (Icth)
Rated insulation level
Rated frequency
Class of insulation
Material (housing)
IEC 61869-2:2012
60 x Ipr / 1s
2,5 x Ith
100%
0,72/3/-kV
50/60Hz
E (120
°C)
PA 6.6, UL94: V2
Specifications per type
TQ30 TQ40-B TQ40-C TQ50-E TQ50-L
Suitable for
cable
ø
18mm
ø
18mm
ø
28mm
ø
42mm
2x
ø
42mm
../1A
Secondary
leads length
for 0,5mm
2
3m 3m 3m 3m 3m
Approximate
weight
360g 310g 450g 650g 200g
../5A
Secondary
leads format
/
0,5 meter
ø
1,5mm
0,5 meter
ø
1,5mm
3 meter
ø
1,5mm
3 meter
ø
1,5mm
Approximate
weight
/ 300g 250g 650g 850g
ELEQ reserves the right to carry out modifications on its products, in
order to improve them,
without prior notice.
Safety instruction
All activities for installation, commissioning and maintenance
of this current transformer must be performed by qualified
personnel that have the knowledge of applicable safety
precautions. This guide assumes that the reader of this
document has sufficient electro-technical knowledge to
understand the content of this
document.
General
The TQ split-core is a current transformer (CT) and can only
be used for measuring electrical alternating currents. The TQ
is suitable only for mounting on insulated primary conductors
in a weather protected and dry location.
Explanation of symbols
This product is designed according to the
EN-IEC 61010-2-032:2012 standards and therefore
this product meets the requirements of the Low
Voltage Directive 2006/95/EC.
Do not apply around or remove from UNINSULATED
HAZ
ARDOUS LIVE conductors, which may render
electric shock, electric burn, or arc flash.
Read the installation guide before mounting the
product. Unprofessional work activities on electrical
installations may result in a threat of danger to the life
and health of human beings and livestock!
Under no circumstances the secondary circuit of the
CT may be opened when the CT is closed and
current is flowing in the primary
circuit. High voltages
may appear on the secondary leads when this circuit
is left open.
R
oHS Directive 2011/65/EU
ELEQ states that they only uses qualified components
in their products from manufacturers, whose
specifications meet or exceed the requirements of the
European Directive for the Restriction of use of
certain Hazardous Substances.
WEEE Directive 2012/19/EU
The 'crossed out wheeled bin' symbol indicate
s that
the equipment should not be disposed as unsorted
municipal waste. Contact a qualified recycler for
disposal.
TQ Split-Core Current Transformer
Installation Guide
TQ30 (4M3Qxx)
TQ30 (4Q3Bxx)
TQ40-B (4Q4Bxx)
TQ40-C (4Q4Cxx)
TQ50-E (4Q5Exx)
TQ50-L (4Q5Lxx)
Read this installation guide before installing the product
83564 / EN1311
ELEQ b.v.
Tukseweg 130, 8331 LH Steenwijk
The Netherlands
+31 (0) 521 533 333
+31 (0) 521 533 391
info@eleq.com
www.eleq.com
83564 / EN1311
Technical Specifications
Safety and environmental conditions
CE marking
LV directive 2006/95/EC
RoHS directive 2011/65/EU
Standard
EN 61010-2-032:2012
WEEE directive 2012/19/EU
This product is designed to be safe under the following
conditions:
Location
Altitude
Ambient temperature
Storage temperature
Relative humidity
Pollution degree
Degree of protection
Indoor use
Up to 2000m
-10°C .. +55°C
-20°C ..
+70°C
5% .. 85%, non condensing
2
IP20
The TQ is only suitable for insulated primary conductors.
Specifications
Standard
Rated short-time thermal current (Ith)
Rated dynamic current (Idyn)
Rated continuous thermal current (Icth)
Rated insulation level
Rated frequency
Class of insulation
Material (housing)
IEC 61869-2:2012
60 x Ipr / 1s
2,5 x Ith
100%
0,72/3/-kV
50/60Hz
E (120°C)
PA 6.6, UL
94: V2
Specifications per type
TQ30 TQ40-B TQ40-C TQ50-E TQ50-L
Suitable for
cable
ø
18mm
ø
18mm
ø
28mm
ø
42mm
2x
ø
42mm
../1A
Secondary
leads length
for 0,5mm
2
3m 3m 5m 5m 3m
Approximate
weight
360g 310g 525g 725g 200g
../5A
Secondary
leads format
/
0,5 meter
ø
1,5mm
0,5 meter
ø
1,5mm
3 meter
ø
1,5mm
3 meter
ø
1,5mm
Approximate
weight
/ 300g 250g 650g 850g
ELEQ reserves the right to carry out modifications on its products, in
order to improve them, without p
rior notice.
Safety instruction
All activities for installation, commissioning and maintenance
of this current transformer must be performed by qualified
personnel that have the knowledge of applicable safety
precautions. This guide assumes that the reader of this
document has sufficient electro-technical knowledge to
understand the content of this
document.
General
The TQ split-core is a current transformer (CT) and can only
be used for measuring electrical alternating currents. The TQ
is suitable only for mounting on insulated primary conductors
in a weather protected and dry location.
Explanation of symbols
This product is designed according to the
EN-IEC 61010-2-032:2012 standards and therefore
this product meets the requirements of the Low
Voltage Directive 2006/95/EC.
Do not apply around or remove from UNINSULATED
HAZ
ARDOUS LIVE conductors, which may render
electric shock, electric burn, or arc flash.
Read the installation guide before mounting the
product. Unprofessional work activities on electrical
installations may result in a threat of danger to the life
and health of human beings and livestock!
Under no circumstances the secondary circuit of the
CT may be opened when the CT is closed and
current is flowing in the primary
circuit. High voltages
may appear on the secondary leads when this circuit
is left open.
R
oHS Directive 2011/65/EU
ELEQ states that they only uses qualified components
in their products from manufacturers, whose
specifications meet or exceed the requirements of the
European Directive for the Restriction of use of
certain Hazardous Substances.
WEEE Directive 2012/19/EU
The 'crossed out wheeled bin' sym
bol indicate
s that
the equipment should not be disposed as
unsorted
municipal w
aste. Contact a qualified recycler for
disposal.
TQ Split-Core Current Transformer
Installation Guide
TQ30 (4M3Qxx)
TQ30 (4Q3Bxx)
TQ40-B (4Q4Bxx)
TQ40-C (4Q4Cxx)
TQ50-E (4Q5Exx)
TQ50-L (4Q5Lxx)
Read this installation guide before installing the product
83564 / EN1311
ELEQ b.v.
Tukseweg 130, 8331 LH Steenwijk
The Netherlands
+31 (0) 521 533 333
+31 (0) 521 533 391
info@eleq.com
www.eleq.com
ELEQ b.v.
Tukseweg 130, 8331 LH Steenwijk
The Netherlands
+31 (0) 521 533 333
+31 (0) 521 533 391
info@eleq.com
www.eleq.com
83564 / EN1501