Operating instructions

Operation SW 5250A•SW 3500A•SW 1750A
3-6 Operation Manual
*
Reference Section 3.4,
Front Panel Programming Conventions
.
**
There is only one frequency setting for all three phases. Changing the frequency
of one phase changes the frequency for all phases.
***
The SW can accept only positive numbers when programming phase angle
offset. Because phase angle offset represents a phase lead with respect to the
internal reference, the formula below should be used for a selected phase to
represent phase angle in terms of phase lag:
Desired Phase Angle Lag = 36 – (Ph.B
θ
Angle – Ph.A
θ
Angle)
The examples below are for a two–phase quadrature system:
For phase angles Ph.A = 0°, Ph.B = 270°, phase lag would be 90°.
90° = 360° – (270° – 0°)
For phase angles Ph.A = 4, Ph.B = 120°, phase lag would be 285°.
285° = 360° (120° – 4)
****
To operate the SW as a DC supply, select the function as “DC+” or “DC-” for
positive and negative DC. “AC+DC Coupling” must also be selected from the
INSTRUMENT menu. The AMPL field is programmed to 0V as a precaution
when changing to or from the “DC+” or “DC-” function.
"4#33'* #%+ (
For two- or three-phase systems, individual programming fields of amplitude, current
limit, phase angle, and function may be “locked” so that any change made to phase A
will be made to phases B and C. The Lock function is intended for front panel
operation. When using GPIB, use the SOURCE0 command.
To lock a field:
1. Move the field select cursor to the field to be locked in the Phase A Program
menu.
2. Press the
F1
function key. The “¥” symbol should appear to the right of the field
indicating the lock mode is active.
3. Enter the value to be locked into the field.
 The lock will not be active until a value is entered; previously entered
values are not locked.
To unlock a field:
1. Move the field select cursor to the locked field in the Phase A Program menu.
2. Press the
F1
function key. The “¥” symbol should disappear.