Operating instructions
Installation / Initial Operation
-19-
6.1.2.1  Parameters of Time 
Position reached 
The output signal is based on a variable time during input of a time value or statically/maintained 
(axis in position) if the value is set to 0. 
 It is set if the according axis has reached the target position. 
Spindle compensation 
In the peak of the loop drive, the drive signals decline. The controller returns to the target value 
when the parameterized time has expired (adjustment range 0.0 sec. … 99.9 sec.). If the value is 
zero, there is no waiting period at the peak. 
Manual change 
Here the time in manual mode can be entered to set the speed from the low speed to the next 
higher speed. 
Monitoring 
Here a time (adjustment range 0.0 sec. ... 99.9 sec.) is set to monitor the measurement system. If 
there are no signals from the measuring system during the programmed period of time, the drive 
signals are switched off to stop the engine. If the value is zero the monitoring is deactivated. 
Delay control enable 
After the start command the output “control enable” is activated. After reaching the target position 
and only after the expiration of the programmed time (adjustment range 0.0 sec. … 99.9 sec.) in 
the parameter “fall delay time control enable” the output is set back. If the parameter “delay control 
enable” is at the value of zero, the output for the control enable is adjusted statically and remains 
set until a change of operation modes respectively until activating the stop key. 
Start delay 
  At a starting command the start of the positioning is delayed for the entered time. 
Shutdown control 
Here the time for shutdown after the position is reached is entered (adjustment range 0.0 sec. ... 
99.9 sec.). 
Retract time 
The dwell-time at the peak is entered here (adjustment range 0.0 sec. …99.9 sec.). After this time 
the position control is set back from the retract peak to the target value. In addition this value is also 
used for a retraction on time. 
Reference time 
In the peak of the reference run, the drive signals decline. The controller will continue positioning 
when this time has expired (adjustment range 0.1 sec. ... 99.9 sec.). 
Quantity reached 
Here the time is entered in 0.1 sec. for the signal “quantity reached”. If the value = 0, the output 
“quantity reached” is statically set. 










