Operating instructions
Installation / Initial Operation
-22-
D-portion 
  Differential voltage: setting 1...1000 
 General:  
  The D-controller (differential controller) determines the control value from the derivative with respect   
to time of the offset. 
 P40: 
At offset a short voltage pulse proportional to the rate of change will be put out to compensate 
quickly without sacrificing the stability of the control loop permanently. The value of the voltage 
pulse is entered. (max + / - 10 V). 
Impulses encoder (rotary encoder resolution) 
The number of pulses per revolution of the engine is entered in this parameter. This enables 
amongst others the calculation of speed to be effected (max. 9999 pulses per revolution). 
Stop mode 
Value
Mode
0 
thevoltageoftheanalogueoutputissetto0V
1 
thedriveissettoshutdownthroughthehighestpossibleacceleration
2 
thedriveissettoshutdownthroughanaccelerationaccordingtotheadjusted
parameter
Manual fast 
  Here the speed “fast” for moving the axis in manual mode can be defined. 
Manual slow 
Here the speed „slow“ for moving the axis in manual mode can be defined. 
v Reference mode 1 
Here the reference run speed of the stopping point until reaching the initiator is defined. 
v Reference mode 2 
Here the reference run speed of stopping point until reaching the index pulse is defined. 










