Shielding
All external signal wires have to be installed shielded:
1. Rotary encoder wires and analogue input wires
2. Wires for all other input signals
3. Wires for all output signals
4. Wires from the power supply to the controller
All shields have to be connected centrally low ohm to PE (connect only one-sided at the controller).
INFORMATION!
Do not connect the controller / measuring system GND to PE (protective earth).
Do not connect the shielding on both sides to PE (protective earth).
If the PE potential is heavily “contaminated” by interference voltages try to
connect the shielding to the GND potential instead of PE (protective earth).
9.2 Electrical Interference Suppression
Signal wires should be installed separately from load power lines and with a safe
distance of at least 0.5 m to capacitive and inductive interference sources such
as contactors, relays, motors, switching power supplies, timed controllers.
If interferences occur in spite of applying all above mentioned measures proceed
as follows:
1. Add RC elements over contactor coils of AC contactors (for example 0,1
µF/100 Ω)
2. Add recovery diodes over DC inductances
3. Add RC elements over each drive phase (in connector box of the drive).
4. Do not connect the GND potential with PE (earth potential)!
5. Install a power filter before the external power supply
9.3 Restart after Fault Clearance
After fault clearance:
1. Reset emergency stop switch.
2. Quit disturbance on controller.
3. Make sure that no person is located in the danger zone.
4. Start operating according to the information in the chapter “Operation”.