Instruction Manual
5 
Before installing the hood 
1.  For the most efficient air flow exhaust, use a straight run 
or as few elbows as possible. 
  CAUTION: Vent unit to outside of building, only. 
2.  At least two people are necessary for installation. Wear 
gloves to protect against sharp edges. 
3.  Fittings material is provided to secure the hood to most 
types of walls/ceilings, consult a Qualified Installer, check 
if they perfectly fit with your cabinet/wall. 
4.  Do not use flex ducting. 
5.  COLD WEATHER installations should have an additional 
backdraft damper installed to minimize backward cold air 
flow and a nonmetallic thermal break to minimize 
conduction of outside temperatures as part of the 
ductwork. The damper should be on the cold air side of 
the thermal break.  
  The break should be as close as possible to where the 
ducting enters the heated portion of the house. 
6.  Make up air: Local building codes may require the use of 
Make-Up Air Systems when using Ducted Ventilation 
Systems greater than specified CFM of air movement. 
  The specified CFM varies from locale to locale. Consult 
your HVAC professional for specific requirements in your 
area. 
All fastener  location must span  the studs  otherwise proceed 
as follows: 
Cutout  drywall  along  marked  lines.  Install  wood  blocking 
between  studs  and  make  sure  it  is  flush  with  existing  stud 
front.  Make  sure  all  mounting  screws  will  anchor  to  added 
studs. Replace drywall and refinish. 
When used in recirculation mode, To Reduce the Risk of 
Fire and Shock use only conversion kit Model: KIT Long 
Life. 
Use 
The hood is designed to be used either for exhausting or filter 
version. 
 Extraction version 
In this case the fumes are conveyed outside of the building by 
means of a  special pipe  connected with  the connection ring 
located on top of the hood. 
 CAUTION!  
The exhausting pipe is not supplied and must be purchased 
apart. 
Diameter of the exhausting pipe must be equal to that of the 
connection ring. 
 CAUTION!  
If the hood is supplied with active charcoal filter, then it must 
be removed. 
Connect  the  hood  and  discharge  holes  on  the  walls  with  a 
diameter equivalent to the air outlet (connection flange). 
Using  the  tubes  and  discharge  holes  on  walls  with  smaller 
dimensions will cause a diminution of the suction performance 
and a drastic increase in noise. 
Any responsibility in the matter is therefore declined. 
!  Use a duct of the minimum indispensable length. 
!  Use  a  duct  with  as  few  elbows as  possible  (maximum 
elbow angle: 90°). 
!  Avoid drastic changes in the duct cross-section. 
 Filtration version 
The  aspirated  air  will  be  degreased  and  deodorised  before 
being fed back into the room. 
In order to use the hood in this version, you have to install a 
system of additional filtering based on activated charcoal. 
Installation 
Specialised personnel must carry out both the electrical 
and the mechanical installation. 
Do not cut a joist or stud unless absolutely necessary. If a joist 
or stud must be cut, then a supporting frame must be 
constructed. 
Fittings material is provided to secure the hood to most types 
of walls/ceilings. 
However, a qualified technician must verify suitability of the 
materials in accordance with the type of wall/ceiling. 
Before making cutouts, make sure there is proper clearance 
within the ceiling or wall for exhaust vent. 
Hood installation height above cooktop is the users 
preference. The lower the hood is above the cooktop, the 
more efficient the capturing of cooking odors, grease and 
smoke. 










