6. Alarms
Several alarms are integrated in the product: gas level, temperature level, battery or
electronics alarm.
Gas alarm
An alarm is triggered if the measured gas level goes above one of the three thresholds
programmed in the product: small leak, alarming leak, large leak. Note that the levels
can be reprogrammed using downlink commands.
Threshold
Default value
Consequence
Small leak
10%LEL
o Alarm message sent through LoRaWAN, with
acknowledge, every 5min
o Red LED blink + Beep + Pre-recorded message, every
minute
o Stops when gas level drops below threshold for >5
minutes and a LoRaWAN message is sent
Medium leak
20%LEL
o Alarm message sent through LoRaWAN, with
acknowledge, every 5min
o Red LED blink + Beep + Pre-recorded message, every
minute
o Stops when gas level drops below threshold for >5
minutes and a LoRaWAN message is sent
Large leak
50%LEL
o Alarm message sent through LoRaWAN, with
acknowledge, every 2min
o Red LED blink + Beep + Pre-recorded message, every
minute
o Stops when gas level drops below threshold for >5
minutes and a LoRaWAN message is sent
Temperature alarm
An alarm is triggered if the measured temperature rises at a rate superior or equal to
3°C every 2 minutes (=37F every 2 minutes).
Threshold
Default value
Consequence
T° rise
3°C / 2min
(37F / 2min)
o Alarm message sent through LoRaWAN, with
acknowledge, every 2min
o Red LED blink + Beep, every minute
o Stops automatically after 15 minutes
Battery/electronics alarm
The product is constantly self-testing itself, so if a problem is detected an alarm is
immediately raised.
LoRaWAN
Product
Alarm message sent through
LoRaWAN, with acknowledge,
every 30min
Yellow LED blink, every minute
Beep, every minute