Troubleshooting guide

26
Problem
HRV runs on
one speed only
Damaged duct
insulation jacket
Cold drafts in
living quarters
Poor air quality/
excess moisture
throughout the house
Air too dry in winter
Unusual noise and
vibrations
Possible causes and solutions
Check all switches for malfunctions by varying
the settings.
If unit remains on same speed, call a contractor.
If the insulation is wet, has any ice build-up or if
there is water on the floor, replace and properly
seal the damaged insulation.
If the insulation is not damaged, use duct tape
to repair any punctures in the jacket.
Check for blockage of exhaust air stream.
Check core for freezing.
If problem persists, ask installer to provide dif-
fusers, relocate fresh air outlets, add additional
outlets, or add a preheater, as appropriate.
Adjust dehumidistat.
Check core for freezing.
Reduce sources of humidity.
Run HRV at a higher speed.
Ensure HRV is operating properly (check
airflow using plastic trash bag technique on
pages 11 and 14).
If problem persists, the HRV’s minimum
continuous ventilation rate may be inadequate.
Call a contractor.
Adjust dehumidistat.
Run HRV on lowest setting.
Run HRV intermittently.
Consider installing a control to run
HRV intermittently.
Sensation of dryness may be caused by
chemicals. Control pollutant at the source.
Consider installing a humidifier (if you do so,
make sure you clean it regularly).
Consider installing an energy recovery ventilator
(ERV), which can help with humidity problems
(see “Energy Recovery Ventilators”, page 8). This
is a more expensive solution than any of the
above. Some HRVs can be converted to ERVs,
at less cost than installing a new unit.
Oil the fan motors (if not self-lubricating) using
non-detergent motor lubricating oil.
Inspect and clean fan blades and heat-exchange
core as required.
If problem persists, call a contractor.
00-211 english booklet 3/20/03 12:00 pm Page 26