ELT-KLED EliteSuite LED Keypad Installation Manual ELT-KLED EliteSuite Installation Manual
PUBLICATION INFORMATION First Publication Draft Document Release Only Updated fire zone information Second Publication Option Menu Navigation Updated Card Reader Interface Options Added Third Publication Slave Keypad Options Added Slave mode Zone Wiring Diagrams Added ELT-KLED EliteSuite Installation Manual
CONTENTS INTRODUCTION ....................................................1 Hardware Compatibility ..................................................................................... 1 WIRING CONFIGURATION ....................................2 Introduction .................................................................................................... 2 Keypad Wire Loom Colour Coding ....................................................................... 2 Communication Connection ...................
INTRODUCTION This document details the wiring configuration of the EliteSuite condominium control keypad and installer programming functions. Hardware Compatibility This manual is written for hardware verison 208-4125-020 or higher and covers firmware application 1.00. This firmware communicates with a EliteSuite enabled Protégé System Controller firmware version 1.06 or above.
WIRING CONFIGURATION Introduction The wiring structure of the EliteSuite keypad uses an encrypted RS485 communication interface. Connections should be made in a daisy chain configuration, avoiding star and stub connections. Figure 1 - Condominium Keypad Communication Keypad Wire Loom Colour Coding The condominium keypads are supplied with a wire loom attachment and are connected using a keyed 10 position snap lock connector. The 10 way wiring loom connection uses the following colour coding.
Communication Connection Support for up to 250 keypads per condominium provided, connection to the system controller uses communication RS-485 interface. This interface is interface and requires power to be supplied to the terminals.
Zone Input Wiring The EliteSuite LED Keypad is capable of connecting to 4 zone inputs, each zone input can then be programmed to perform the required function in the system. The following diagrams show each of the zone wiring configuration settings that are possible. The programmed zone configuration for the EliteSuite LED Keypad is made in the option settings. Refer to the General Options Section on Page 17 for the programming of the zone configuration.
Figure 6 - 4 Zone Input Duplex Mode (1K and 2K4) Fire Zone Input Wiring When wiring a zone to be a fire zone input the current programmed zone options will determine what resistors and configuration is required, refer to the General Options Section on Page 17 and the zone configuration diagrams in the Zone Input Wiring Configuration on Page 4.
Slave Keypad Zone Wiring With one or more slave keypads connected, extra zones beyond the normal 4 are available on the suite system. There are 2 options for wiring the zones: - Duplex mode enabled, 8 zones in total available. This setup is shown in Error! Reference source not found.. - Standard wiring mode, 6 zones in total available. This setup is shown in Figure 9. The choice between the two wiring options will be dependent on the physical configuration of the sensors and wiring in each installation.
Figure 9 - Slave Keypad Standard Zone Wiring PGM (Programmable Output) The EliteSuite LED Keypad uses a programmable output (PGM) that will activate during an alarm condition. This output can be programmed to either: - Follow the status of the alarm siren time or the fire alarm setting - Follow the armed / disarmed status of the keypad. Connect a relay or other interface device to this open collector output for activation of ancillary devices.
Slave Reader Network The EliteSuite LED Keypad is capable of controlling a slave network of up to 8 proximity card reader devices from the following range: - PRX-NANO Nano Prox Small Form Factor Proximity Card Reader - PRX-VARIO Vario Prox Flush Mount Proximity Card Reader Each slave reader device communicates with the keypad via a PRX-SAM Standalone Module Board. This module also allows control of an electronic lock device with the onboard relay.
Slave Keypad Network The EliteSuite LED Keypad is capable of controlling a slave network of up to 4 other EliteSuite Keypads in Slave Mode (see Device Options for configuration). Each slave reader device communicates with the keypad via connection of their primary network lines to the secondary network lines of the master keypad, as shown below. Note that the Slave Reader Network Enabled option must be OFF to allow use of the slave keypad network.
Indicator Lights The EliteSuite™ LED keypad features three status indicator lights showing the condition of the EliteSuite™ Security System. Bypass Install Message Power/Trouble Ready Indicator Armed/Alarm Figure 13 - Indicator Lights Binary Number Display The EliteSuite™ LED keypad displays programming information such as timers and addresses using the 8 Zone LED’s. The Zone LED’s will be lit in binary mode, meaning that you must add the place value of each LED together to obtain the programmed value.
DEVICE CONFIGURATION Device Configuration Mode Access Before the EliteSuite LED Keypad module will communicate it must be assigned an address and programmed with specific options as to how it will operate. This is achieved by accessing the device configuration menu. The device configuration menu can only be accessed in the FIRST 2 SECONDS when the device powers up. It is not able to be accessed when the system is operational.
Device Options ([MENU] , [2]) The device options set options that relate to the mode of operation of the EliteSuite keypad. To enter the Device Options Menu, press [MENU] , [2] To toggle options press the keys [1] to [8] , and the corresponding Zone LED will be lit when that option is ENABLED. Pressing the [ENTER] key will save the options. Option 1 – Slave Keypad If this option is used, be sure to address the keypad as slave 1,2,3 or 4.
LOCAL INSTALLER LOGIN Introduction The default local installer code is [0000]. To access the local installation menu, press: [ENTER] , [0000] The INSTALL LED will then be lit to notify that Installer mode has been entered. One Zone LED will be lit to show you which selection from the current menu you are currently at. You can change your selection with the [Ï] and [Ð] keys and then press [ENTER] to access that menu item, or just press the number key corresponding to the menu item you wish to select.
TIMING (MENU 1) ALL 3 Digits of the timer value MUST be entered when programming a timer. This means that for addresses below 100, you must enter [0] then the 2 digits of the address. For addresses below 10, you must enter [0] , [0] followed by the address digit. Entry Delay Timer ([MENU] [1], [1]) The entry delay timer is programmable from 000 to 255 seconds (Default 30 Seconds).
Alarm/Siren ([MENU] , [1] , [3]) The siren/alarm timer is programmed from 000 to 250 minutes (Default 4 minutes). To program the timer value, press [MENU] , [1] , [3] , [TIM 1], [TIM 2] , [TIM 3] , [ENTER] Where TIM 1 ~ 3 are the timer value digits, entered using the 0 to 9 number keys.
Reader Pre-Alarm Timer ([MENU] , [1] , [4]) The Reader Pre-Alarm Timer is programmable from 0 to 255 seconds (Default 30 Seconds). This is only used when the Reader Slave Network is enabled. To program the timer value, press [MENU] , [1] , [4] , [TIM 1], [TIM 2] , [TIM 3] , [ENTER] Where TIM 1 ~ 3 are the timer value digits, entered using the 0 to 9 number keys.
OPTIONS (MENU 2) General Options ([MENU] , [2] , [1]) The general options set options that relate to the general operation of the EliteSuite keypad. To enter the General Options Menu, press [MENU] , [2] , [1] To toggle options press the keys [1] to [8] , and the corresponding Zone LED will be lit when that option is ENABLED. Pressing the [ENTER] key will save the options.
6 Disabled no trouble beep will be generated. Option 4 - Device Power Up Disarmed 5 Enabled the system will power up disarmed regardless of the system status at the time power was lost. 6 Disabled the system will power up in an exit delay condition if the power to the EliteSuite device was turned off during an exit delay cycle or if the system was in alarm or armed.
Arming Options ([MENU] , [2] , [2]) The arming options set functions that relate to the arming of the EliteSuite system. To enter the Arming Options Menu, press [MENU] , [2] , [2] To toggle options press the keys [1] to [8] , and the corresponding Zone LED will be lit when that option is ENABLED. Pressing the [ENTER] key will save the options. Option 1 - Allow Fast Regular Arming 5 Enabled the system can be FAST ARMED by pressing and holding the closed padlock key. 6 Disabled FAST ARMING is disabled.
Reporting Options ([MENU] , [2] , [3]) The reporting options are a set of functions that relate to the reporting of information to the on site monitoring application or offsite central station. The system can further be configured for each reportable event to go to monitoring station and the local on site monitoring. To enter the Reporting Options Menu, press [MENU] , [2] , [3] To toggle options press the keys [1] to [8] , and the corresponding Zone LED will be lit when that option is ENABLED.
Option 4 - Report Zone Fault 5 Enabled the system will report any zone fault trouble condition to the system controller. This will not indicate the zone that has the fault as this will be shown on the local keypad and in the trouble view menu. 6 Disabled no zone fault message will be sent. Option 5 - Report User Menu Access 5 Enabled the system will report when the master user has accessed the main menu. 6 Disabled no message will be sent when the master access's the main menu.
Panic Options ([MENU] , [2] , [4]) The panic options set functions that relate to the panic processing of the EliteSuite system. To enter the Panic Options Menu, press [MENU] , [2] , [4] To toggle options press the keys [1] to [8] , and the corresponding Zone LED will be lit when that option is ENABLED. Pressing the [ENTER] key will save the options. Option 1 - 1+3 Silent Panic 5 Enabled the system will send a silent panic alarm to the front desk when the 1+3 keys are held for a period of 2 seconds.
Option 4 - User 8 Duress Code Enabled 5 Enabled the system will enable user code 8 to be a duress code user and on login will send a duress code to the central station or on site monitoring system. 6 Disabled user code 8 will operate as a standard user. Option 5, 6, 7 and 8 - Reserved 5 Reserved. 6 Reserved. Do not modify the reserved options configuration.
ZONES ([MENU] , [3]) Selecting a Zone To enter the Zone number selection menu, press [MENU] , [3] To select a zone to modify use the [Ï] and [Ð] keys to scroll through the available zones, and press the [ENTER] key to move to the next configuration menu for the selected zone. You may also shortcut to a particular zone configuration menu by pressing: [MENU] , [3] , [ZONE NUMBER] Where ZONE NUMBER is the number button corresponding to the required zone.
Use this to set the zone type for a motion detector that is located in an entrance area. 4 5 6 Instant 24HR Fire Zone will cause an alarm immediately. Zone will always cause an alarm immediately. Zone is a fire zone and will generate an instant alarm. 7 Fire Delay Zone is a delayed fire zone and will generate the fire delay beeping and require the user to follow the delay fire zone procedures to prevent a full fire alarm from being activated.
Option 3 - Force Zone 5 Enabled the zone can be force armed when it is not ready to be armed. A force armed zone will automatically be included in the alarm processing when the zone restores from the not ready condition. 6 Disabled the zone is not able to be force armed. Option 4, 5, 6, 7 and 8 - Reserved 5 Reserved. 6 Reserved. It is recommended not to enable/disable or modify the settings of reserved options.
CONTACT Contact Integrated Control Technology welcomes all feedback. Please go to our website or use the information below. Integrated Control Technology P.O. Box 302-340 North Harbour Post Centre Auckland New Zealand Phone: Fax: Unit C 6 Ascension Place Mairangi Bay Auckland New Zealand +64-9-476-7124 +64-9-476-7128 www.integratedcontroltechnology.
Unit C, 6 Ascension Place, Mairangi Bay, P.O. Box 302-340 North Harbour, Auckland, New Zealand. Phone: +64 (9) 476 7124 y Fax: +64 (9) 476 7128 www.integratedcontroltechnology.