Specifications

30
OPTIONAL FACTORY INSTALLED DC2000
Plug in the 12 pin plug into the DC2000 control unit. Make sure the “System ON” and “Charge OK” LEDs are
lit. If the “Battery Low” led comes on, the battery needs to charge before it can be used.
Make sure “Gate Direction” setting on DC2000 is set the same as the gate operator's setting.
“Manual” setting: The DC2000 will respond to the input devices wired to the J 20 socket.
This mode can also be used as an emergency override. If 110 Vac power is on, but the system has an electronic
malfunction, the gate can be operated using the DC2000 system with input devices wired to J 20 socket.
“Auto” setting: The DC2000 opens the gate automatically upon 110 Vac power failure and stays open. When 110
Vac power is restored, the gate operator will return to normal operation. (The gate can be closed by manual
command)
Manual
Mode
Auto
Mode
Push and Hold to
operate gate
110 Vac Power
Failure
110 Vac Power On,
OmniControl™ Board Malfunction
110 Vac Power On,
Emergency Override
Gate automatically
opens
Turn the 110 Vac power off then
push and Hold to operate gate
Push and Hold to override
the OmniControl™ board
Push and Hold to override
the OmniControl™ board
Turn the 110 Vac power off then gate
opens automatically
CLASS I, II, III, IV
D
C
2
0
0
0
H
a
r
n
e
s
s
System Setup
Socket
Important: All devices
wired to the DC2000
MUST
be dedicated to it alone.
Normal operation will be
controlled by separate
devices wired to the
OmniControl™ board.
DO NOT wire 110 Vac power to the DC2000
1
3
2
7
6
5
4
1
2
Optional Factory Installed DC2000
Op
t
ional
P
roduct
Reset Button Wires
DO NOT Remove
CSW200A Manual.qxd 12/9/04 3:11 PM Page 30