Instruction Manual
3
Table 1
Model Descripon
ELK-6052 Wireless 900MHz Smoke Detector
ELK-6053 Wireless 900MHz Heat and Rate of Rise
Detector
Indicator Summary
Normal
Operaon
Acon Red LED Yellow LED Sounder
Power Up Pull Baery
tab or insert
Baery
1 Flash 1 Flash O
Standby O O O
Sensing Fire Rapid
Flashing
O Full Sound
Fault Mode Acon Red LED Yellow LED Sounder
Low Baery O 1 Flash
every 48
sec
1 Beep with
1 Flash
Faulty Smoke
Sensor
O 2 Flashes
every 48
sec
2 Beeps
with 2
Flashes
Faulty Heat
Sensor *
O 2 Flashes
every 48
sec
2 Beeps
with 2
Flashes
End of Life O 3 Flashes
every 48
sec
3 Beeps
with 3
Flashes
Silence
Sounding
Detector
Press &
Release
Buon
1 Flash
every 8
sec
O O for 10
mins
Silence End of
Life indicaon
(up to 30
days)
Press &
Release
Buon
O O for 72
hours
O for 72
hours
Dusty
Chamber
Press Test
Buon to
acvate
beeps
O 4 ashes
every 48
seconds
Beep 4
mes on
test buon
press only
Test Mode Acon Red LED Yellow LED Sounder
Test Smoke
Detector
Press Buon Rapid
Flashing
O Full Sound
Detector
Memory
Acon Red Led Yellow LED Sounder
24 Hour
Memory
2 Flashes
every 48
sec for 24
hours
O O
Long Term
Memory
Press & Hold
Buon
Rapid
Flashing
O Rapid
Chirping
Normal Operation Indicators Explained
Power Up
Twist off the Detector from the mounting plate (see Quick
Start Guide). Remove the battery tab to power the Detector,
the red LED will flash once followed by one flash of the
yellow LED to indicate that the Detector has been powered
successfully and is now in standby mode.