Owner's Manual
Instructions Printed On Inside
828-397-4200 Voice
828-397-4415 Fax
http://www.elkproducts.com
email: info@elkproducts.com
PO Box 100 • Hwy. 70W • Hildebran, NC 28637 • USA
APPLICATION:
Allows the M1 to monitor remote temperatures.
Rules are used to activate outputs, dial phone
numbers, deliver voice alerts, etc. A sensor can
be interfaced to any of the 16 zones on the M1
Control. Available with short or long (7 ft.) Probe.
FEATURES:
• Measures Temperature From: -50 to +140 F
• Communicates to M1 Control Over 3 Wires
• Operates On Any Main Board Zone (1-16)
• Up to 16 Interfaces Allowed per M1 Control
• Interface May be Placed Up To 1000 ft From M1
• Suitable for Indoor/Outdoor Use in a Covered
Environment
• Available with Short Probe (M1ZTS)
or with 7 ft. Probe (ELK-M1ZTSR)
SPECIFICATIONS:
• Operating Voltage: 12 Volts D.C.
• Current Draw: 10mA
• Housing Dimensions: 2.375" x 1.25" x 1"
* * IMPORTANT NOTE * *
For full compatibility with the ELK-M1ZTS or ELK-
M1ZTSR the M1 Control must have firmware
version 4.2.5 or higher and the Elk-RP Software
must be version 1.4.1 or higher. Earlier version
firmware/software may appear to work but will
not produce accurate readings.
10/04
Auxiliary
+12VDC Power
Outputs
Master Power Switch (SW1),
disconnects AC and Battery
power from control
This example shows the
Temperature Interface
connected to Zone 15.
However, any of the 16 main
zones will accept a
Temperature Interface.
Zone Def=033 Temperature
ELK-M1
(Left Side Terminals)
Temperature
Sensor/Interface
with cover
removed
Four conductor cable from
Temperature Inteface to the M1 Control
(Maximum distance: 1000 ft.)
+SAUX
NEG
+VAUX
NEG
+VAUX
NEG
+VAUX
NEG
AC
ZONE 16
NORMAL
JP1
SW1
16.5 V
JUMPER TO
START W ITH NO
AC
POWER
TELCO SEIZED
AC
Z9
NEG
Z10
Z11
NEG
Z13
NEG
Z15
Z14
Z12
NEG
Z16
DIALER ACTIVE
2WIRE
SMOKE
STATUS
REVERSE
BAT LEADS
+
-
BATTERY
Red
Green
Black
ELK-M1ZTS "Short"
Temperature Probe
ELK-M1ZTSR "7 ft."
Temperature Probe plugs in here.
+12V ZN NEG
Red
Green
Black
CAL
+ T -
Calibration pads - DO NOT USE without
help from ELK Technical Support
INSTALLATION OF M1ZTS or ZTSR
1. Remove the cover from the base of the Interface.
2. Mount the base using a #6 x 3/4" sheet metal
screw though hole in center of circuit board.
NOTE: The Interface is not weatherproof. If mounted
outdoors, it should be placed under a roof or deck
overhang or in a weather resistant box. For freezer
monitoring or extreme conditions the model with 7 ft.
Probe model (M1ZTSR) is the best choice. This allows
the interface to be mounted away from the sensor
(indoors) or in a more suitable environment.
3. Turn the M1 Master Power Switch Off.
4. Run a four conductor cable (max. of 1000 ft.) from
the Interface to the M1 Control. Connect the wires
per and diagram steps below:
- Connect a Green wire from terminal ZN on the
interface to any unused Zone input terminal on the
main M1 board (Z1-Z16). No EOL resistor needed.
- Connect a Red wire from terminal +12V on the
Interface to one of the Aux. +12 Volt DC terminals
on the M1.
- Connect a Black wire from terminal NEG on the
interface to one of the NEG terminals on the M1.
5. After all connections are complete, place the
cover on the interface and turn the M1 power On.
Zone Temperature Sensor/Interface
ELK-M1ZTSR (7 ft Probe)
ELK-M1ZTS (Short Probe)
Zone Temperature
Sensor/Interface
ELK-M1ZTS (Short Probe)
ELK-M1ZTSR (7 ft. Probe)