User guide

10
WARNING!! While working inside the panel be aware of the terminals located at the
bottom, they contain live electricity and caution should be exercised at all times.
MicroLogix 1400 Screens
With Power ON
1
RUN
CHANGE IP ADDR
192 . 168 . 032 . 010
=
010
RUN
ELKHART BRASS
INDUSTRIAL EQUIP
Equip
MODULAR
-
A
4
Steps to complete setup:
1. Turn the Power On Switch for all Panels to the 0(OFF) position.
2. Locate the OCP that will be the Remote (ROCP). This one will not be
wired to a Monitor Motor Control Panel (MMCP).
3. On the ROCP turn the Power On Switch to the 1(ON) position and open
the panel door. The MicroLogix 1400 and Park light may be clicking and
flashing. This is ok.
4. Using the [OK] key press and release until display 7 appears.
5. Using the Data from page 7 make the following changes for:
a. Monitor ID Number
b. Wired to MMCP
c. Change IP address
6. Repeat steps 4 thru 5 for the other controller.
7. Turn the Power On Switch, on the ROCP, to the 0(OFF) position
8. On the ROCP secure the door and place the Power On switch to the 1(ON)
position.
9. On the Local OCP (LOCP), the one wired to the MMCP, turn the Power
On Switch to the 1(ON) position.
10. If they are not already on turn the MMCPs to the 1(ON) position.
11. The system should now be ready to operate.
12. The park lights will continue to flash. This is an indication that the
monitors need to be parked. This will happen anytime the OCP power is
cycled on a LOCP. Press the park button on the OCPs that are associated
with the correct monitor. Once the monitors are parked the light will stay
on until the monitor is moved from that location.
13. If system does not function correctly, check the settings in the ROCP and
the LOCP per the Data from the previous sheet, repeating steps 4 thru 6.
For more detailed information consult the OCP Setup instructions.
2
3
4
5
6
7
8
9
PRESS
OK
PRESS
OK
PRESS
OK
PRESS
OK
PRESS
OK
PRESS
OK
PRESS
OK
PRESS
OK
PRESS
OK
RUN
MONITOR POSITION
VERTICAL =
45
HORIZONTAL =
130
RUN
ENTER NEW PARK
HORIZONTAL ANGLE
=
0154
RUN
ENTER NEW PARK
VERTICAL ANGLE
=
0045
RUN
ENTER NEW PARK
NOZZLE ANGLE
=
0030
RUN
ENTER MONITOR
ID NUMBER
=
1
RUN
ENTER HORIZONTAL
OSCILLATE ANGLE
=
0175
RUN
WIRED TO MMCP?
ENTER 1 FOR YES
=
1