User guide

18
Power converts to 24
VDC in control panel
IV SPECIFICATIONS
General Specs
Input Power 120/240 VAC (50/60Hz.) 1 Phase
240 VA max. power
Electrical Load 2 AMPS MAX
Panel Dimensions 24” x 36” (610mm x 914mm) – 2 Monitor OCP
20” x 24” (508mm x 610mm) – 1 Monitor OCP
Panel Weights Approx. 100 lbs. (45 kg) – 2 Monitor OCP
Approx. 80 lbs. (36 kg) – 1 Monitor OCP
Operating Temperature Range +14
o
F to +140
o
F (-10
o
C to +60
o
C)
UL Product Marking
UL Listed and Labeled (Class 1, Division 2)
V MAINTENANCE
Monthly Inspection and Maintenance
1. Check all terminal blocks and connections for being properly taut to 4.5 – 7.1 in-lbs (0.508 – 0.802
Nm).
2. Check all contact blocks and operators for functionality. If there are loose connections tighten them. If
a contact block is not functioning properly, replace it.
3. Check all light bulbs on outside of the panel. If any are burnt out, replace the bulb.
4. Check for proper operation of system overall. Please refer to the Troubleshooting section if you are
experiencing problems.
Attention: When cycling the monitor through the motions (up, down, left, right), be
sure to exercise the system a minimum of 2 (two) complete cycles. This will help redistribute
the grease inside the monitor for improved operation and extended durability.