At the ROCP with water flowing out of the nozzle
and the Water Valve Opened light is not on
Check for a burned out bulb
Check that the networked LOCP water valve open
light is on
Check that the jumper is in place at terminals 67 to
71
At the ROCP with foam flowing out of the nozzle
and the Foam Valve Opened or Auxiliary Device
ON light is not on
Check for a burned out bulb
Check that the networked LOCP foam valve open or
Auxiliary Device ON light is on
Check that the jumper is in place at terminals 69 to
72
At the LOCP with a monitor oscillating the
indicator light is not on
Check for a burned out bulb
At the ROCP with a monitor oscillating the
indicator light is not on
Check for a burned out bulb
Check that the networked control panels have the
same Monitor ID number (Section 4)
Park Light continually flashes quickly
This is an indication that the monitor needs to be
calibrated and parked. Pressing the Park button will
cause the monitor to calibrate and the Park light will
flash slowly until the operation has completed.
Once the park procedure has been completed the
light will remain on until the monitor is moved from
the ROCP or LOCP by a joystick movement or by
starting oscillation.
Please refer to our website at www.elkhartbrass.com for any further information. Any problems that