Technical data
36
IM3-140M
+
-
CIB
CIB
+12 V
GND
IM3-140M 8595188132459
Binary input unit IM3-140M is designed to connect up to 14 devices with potentialless
contact (such as switches, buttons of other designs, fi re and glass detectors and others).
Inputs IN1 - IN7 can be balanced.
Contacts of external devices connected to the inputs of the drive can be NO or NC -
Input parameters are confi gured in the software IDM.
The unit generates a supply voltage of 12V DC/150 mA for powering external detectors,
so it can power PIR detectors, fi re and gas detectors.
Active use 12V DC output for powering detectors increases the nominal consumption
units from CIB (see technical data).
The unit can be used for counting pulses of energy meters with pulse output.
IM3-140M in 3 module is designed for switchboard mounting on DIN rail EN60715.
14x NO or NC against GND (-)
IN1 - IN7 -are balanced inputs
12 V DC/150 mA
CIB
yellow LED
27 V DC/25 mA, from CIB BUS
100 mA
max. 2.5 mm
2
/1.5 mm
2
with sleeve
-20 to +55 °C
-30 to +70 °C
IP 20 device, IP 40 mounting in the switchboard
II.
2
any
into a switchboard rail to DIN EN 60715
3-MODULE
90 x 52 x 65 mm
102 g
Input:
Output (power supply 12V for sensors):
Installation BUS:
Data transfer indication:
Supply voltage/rated current:
Rated current for full
load on output 12 V DC:
Terminal:
Operating temperature:
Storing temperature:
Protection degree:
Overvoltage category:
Pollution degree:
Operating position:
Installation:
Design:
Dimensions:
Weight:
Example of connection
CONNECTION
OPERATING CONDITIONS
DIMENSIONS AND WEIGHT
OUTPUTS
COMMUNICATION
POWER SUPPLY
INPUTS
TECHNICAL PARAMETERS
EAN code
Binary input unit IM3-140M
for POWER SUPPLY
external alarm
detectors
12 V DC / 150 mA