Temperature input, 1-channel and 4-channel TI3-10B, TI3-40B
These units are designed for connection of one (TI3-10B) to four (TI3-40B) external
temperature sensors.
Units range TI3 support the connection of the following temperature sensors:
- TC / TZ - 2-wire connections
- Ni1000, Pt1000, Pt100 - 2-wire and 3-wire.
Used in when necessary to take temperatures from diff erent places (for example
large fl oor heating – diagonal layout of sensors, fl oor/space, indoor/outdoor
temperature, technological device – boiler, solar heating etc.)
Status of units indicated by green RUN LED on the front panel:
- If the supply voltage is connected (units are powered via the bus CIB),
but there is no communication with the master, RUN LED is lit
continuously.
- If the supply voltage is connected and the unit communicates via
standard CIB, RUN LED fl ashes.
TI3-10B-40B in TI3 version B is designed for mounting into an installation box.
Example of connection TI3-10B
Example of connection TI3-40B
EAN code
INPUT
COMMUNICATION
POWER SUPPLY
CONNECTION
OPERATING CONDITIONS
DIMENSIONS AND WEIGHT
1x/4xinputs for external thermo sensor TC, TZ,
Ni1000, Pt1000, Pt100, see accessories
by type of sensor, prob from -30°C to 250°C
14 bit
CIB
green LED RUN
27 V DC/25 mA, from CIB BUS
0.5 mm
2
- 1 mm
2
-20 to +55 °C
-30 to +70 °C
IP 30
II.
2
any
into installation box
49 x 49 x 13 mm
TI3-10B (22 g), TI3-40B (24 g)
Temperature input for
temperature measuring:
Emperature measurement range:
Converter resolution:
Installation BUS:
Status indication unit:
Supply voltage/rated current:
Terminal:
Operating temperature:
Storing temperature:
Protection degree:
Overvoltage category:
Pollution degree:
Operating position:
Installation:
Dimensions:
Weight:
TECHNICAL PARAMETERS
EAN code
temperature sensor
TC/TZ, Ni, Pt
temperature sensor
TC/TZ, Ni, Pt
temperature sensor
TC/TZ, Ni, Pt