Technical data
38
+
-
CIB
CIB
TI3-60M 8595188132893
TI 3 -6 0M
A
A
COM
A
A
A
A
COM
tt
t t t t
6 x input to externa temperature sensor TC, TZ,
Ni1000, Pt1000, Pt100 see accessories
by type of sensor, probe from -30°C to 250°C
14 bit
6x red LED
CIB
green LED RUN
27 V DC/45 mA, from CIB BUS
0.5 mm
2
- 1 mm
2
-20 to +55 °C
-30 to +70 °C
IP 20 device, IP 40 mounting in the switchboard
II.
2
any
into a switchboard rail to DIN EN 60715
90 x 52 x 65 mm
102 g
Temperature input for
temperature measuring:
Emperature measurement range:
Converter resolution:
Overload indicator
or sensor break
Installation BUS:
Status indication unit:
Supply voltage/rated current:
Terminal:
Operating temperature:
Storing temperature:
Protection degree:
Overvoltage category:
Pollution degree:
Operating position:
Installation:
Dimensions:
Weight:
Thermo input, 6-channel TI3-60M
INPUT
COMMUNICATION
POWER SUPPLY
CONNECTION
OPERATING CONDITIONS
DIMENSIONS AND WEIGHT
Unit TI3-60M is designed to connect up to six external temperature sensors.
Units range TI3 support the connection of the following temperature sensors:
- TC / TZ - 2-wire connections
- Ni1000, Pt1000, Pt100 - 2-wire and 3-wire.
It is used in cases where it is necessary to read the temperature, eg fl oor/room, indoor/
outdoor temperature, process equipment - boiler, solar heating, etc.
Unit status is indicated by green RUN LED on the front panel:
- If the supply voltage is connected (the unit is powered via the bus CIB),
but there is no communication with the master, RUN LED is lit
continuously.
- If the supply voltage is connected and the unit communicates via
standard CIB, RUN LED fl ashes.
The status on individual temperature inputs is indicated by the relevant red LED on
the front panel – exceeding the scope or interruption of the sensor.
TI3-60M in 3 module is designed for switchboard mounting on DIN rail EN60715.
TECHNICAL PARAMETERS Example of connection
EAN code
temperature sensor
TC/TZ, Ni, Pt
temperature sensor TC/TZ, Ni, Pt
temperature sensor
TC/TZ, Ni, Pt