Technical data
46
WSB3-20 WSB3-40
+
-
CIB
CIB
Wall switch button
WSB3
CIB+
CIB
I
CIB+
CIB
I
AIN1/DIN1
AIN1/DIN1
AIN2/DIN2
AIN2/DIN2
WSB3-20 8595188132343
WSB3-40 8595188132336
WSB3-20 WSB3-40
YES, built-in temperature sensor, NTC
0 to +55°C ; 0.3°C from the range
2 4
2x AIN/DIN
by setting, bit 10
Yes, the connection between
AIN1/DIN1 and AIN2/DIN2
TC/TZ
-20°C to +100°C
+0,5°C from range
two-colored LED (red, green)
1 2
CIB
27 V DC/25 mA, from CIB BUS
0.5 - 1 mm
2
-20 to +55 °C
-30 to +70 °C
IP 20
II.
2
any
into installation box
85.6 x 85.6 x 30 mm
94 x 94 x 30 mm
70 g (without frame)
Temperature measuring:
Scope and accuracy of temp. measurement:
Number of control buttons:
Inputs:
Resolution:
Ext. temperature sensor:
Type ext. sensor:
Temperature measurement range:
Temperature measurement accuracy:
Indication:
Number of outputs:
Installation BUS:
Supply voltage/rated current:
Terminals:
Operating temperature:
Storing temperature:
Protection degree:
Overvoltage category:
Pollution degree:
Operation position:
Installation:
Dimensions (plastic):
Dimensions (metal, glass, wood, granite):
Weight:
OUTPUTS
COMMUNICATION
POWER SUPPLY
CONNECTION
OPERATING CONDITIONS
DIMENSIONS AND WEIGHT
INPUTS
TECHNICAL PARAMETERS
Example of connection
Wall group controllers with low-upstroke control WSB3
Wall controllers with low-upstroke control (line) WSB3 are the main and most frequently
used units (controller) in the iNELS system.
Built-in micro-buttons with low upstroke off er elegant and easy control.
Two-colored indication LED, located in each position of controller, can signal status
of controlled appliance, and also status of any sensor or actuator in the system.
Controllers are designed as two-channel (WSB3-20) or four-channel (WSB3-40).
All versions are in the same dimension as a basic modular wall-switch (94x94 mm), in
Logus
90
design and can be combined into multiframes with other devices of this line.
Each controller is equipped with a temperature sensor. It is also equipped with two
analog/digital inputs (AIN/DIN), which can be used to connect two potentialless
contacts or one external temperature sensor TC/TZ (e.g. for measuring fl oor
temperature).
Advantages over conventional switches / buttons include space saving, signaling of
any output system, the ability to measure temperature and the possibility to connect
external buttons or detectors.
Each channel (button) can control any actuator (appliance) in the system. It is also
possible to program various functions or macro function (set of functions) to each
button. Allowing you to control several appliances with one button simultaneously.
Each button (fold) can have diff erent functional modes beside lighting control:
a) Classic wall switch:
- upper button ON, bottom button OFF
b) Button controller (impulse relay):
- fi rst press ON, second press OFF
c) Dimmer:
- short press – ON/OFF,
d) Time switch:
- ON after press, automatically OFF after set time
e) Setting light scenes – for example: for watching TV:
- shutters down
- TV ON
- main light 30% intensity
- wall lamps 50% intensity
WSB3 in LOGUS
90
design is designed for mounting into an installation box.
temperature sensor TC/TZ
EAN code
EAN code