User Manual

Gold Bassoon Installation Guide
MAN-G-BASIG-EC (Ver. 1.002)
|Hardware Requirements|www.elmomc.com
11
Table of Contents
Chapter 5:
Installation
The Gold Bassoon must be installed in a suitable environment and properly connected to its voltage
supplies and the motor.
5.1 Hardware Requirements
AC Input Requirements
Circuit Breakers & Contacts Supply Voltage
Circuit breaker current rating Single Phase operation:
For 3/230 :≈ 5A
For 6/230: ≈8A
For 10/230: ≈12A
Three phases operation:
For 3/230 : ≈3A
For 6/230: ≈6A
For 10/230: ≈10A
Type B
Circuit breaker voltage rating 250 VAC
Contactor Current rating similar to the circuit breaker current
ratings
Recommended Wire Cross-Sections (All Models)
Feature Connection Details
Recommended Maximum
Wire Gauge
Maximum Terminal
Capability
AC input
AC1, AC2, AC3
16 AWG 12 AWG
E
arth
Connection
PE
16 AWG 12 AWG
Note: The actual size is determined by the drive’s current model.