User's Manual

E2 Wireless I/O Page 31
4Chapter 4 – Configuration
4.1 First time
The E2 has a built-in web server, containing web pages for analyzing and modifying the
module’s configuration. The configuration can be accessed using Microsoft® Internet
Explorer.
Default Configuration
The default factory configuration of the E2 is
IP address192.168.0.1XX, where XX is the last two digits of the serial number (the
default IP address is shown on the printed label on the back of the module)
netmask 255.255.255.0
Username is “user” and the default password is “user”
The E2 will temporarily load some factory-default settings if
powered up with the #6 dipswitch under the side configuration
panel switched on. When in SETUP mode, wireless operation is
disabled. The previous configuration remains stored in non-volatile
memory and will only change if a configuration parameter is
modified and the change saved.
Do not forget to set the switch back to the OFF position and re-cycle the
power at the conclusion of the configuration for normal operation otherwise, it
will continue to boot into the default IP address.
Accessing Configuration for the first time
The Default IP address is in the range 192.168.0.XXX
and so will require a PC on this network or be able to
change the network settings to access the module
configuration.
This is the procedure for changing A PC network
settings.
methods for accessing the configuration for the first
time.
You will need a “straight-through” Ethernet cable
between the PC Ethernet port and the E2. The factory
default Ethernet address for the E2 is 192.168.0.1XX
where XX are the last two digits of the serial number
(check the label on the back of the module).
Connect the Ethernet cable between unit and the PC
configuring the module.