User's Manual

E2 Wireless I/O Page 39
COS Enabled
Can enable or disable the COS message. If disabled
messages would only be sent on the update period.
COS Resets Update
Timer
Enabling this timer will mean If a COS is received in between
update messages it will reset the Update timer, meaning it will
not receive another update until the further Update period has
passed.- used to reduce the amount of radio traffic
Force Reg
Register location that when written to will force the Write
Mapping to be sent. E.g. External device can initiate the
transmissions.
Fail Reg
Register location that will indicate a failure to communicate
with the remote Destination Address configured
First Local Reg
Starting Local address that values will be written to.
First Remote Reg
Starting Remote address that the values will read from.
Reg Count
Total number of register values (consecutive)
Save Changes
Save changes to non-volatile memory. The module will need
to be restarted before the changes take effect.
Save Changes and
Reset.
Save settings to non-volatile memory, and reboot E2. Once
the module has completed the reboot sequence, all changes
are in effect.
Read Mappings
Block Read Mapping
Destination IP
This is the Module IP address that you wish to read I/O from.
Invert
This will allow the mapping to be inverted. E.g. if the digital
input is on and inverted then the output will be off and visa
versa. Applies to all the I/O in the mapping and can only be
used with Words and Bits, No Floating Point or Long values
Update Period
This is the period that the mappings are sent as an update or
check signal.