Troubleshooting Guide

61
3UREOHP
3RVVLEOH&DXVH
5HSDLU
&RPPHQWV
Dryer is
switched on,
indicator light
is lit but the
refrigerant
compressor
does not turn on.
The connection has
inverted phases
Invert two phases
3-phase dryers are equipped with a phase
controller
to avoid the fans from turning in the
opposite
direction.
Refrigeration unit is not functioning
Check refrigeration
compressor
Several factors can cause compressor failure.
A qualified refrigeration technician needs to
check
all the electrical and refrigerant circuit and
controls.
The refrigerant high pressure protection
has tripped
The refrigerant safety high
pressure switch has tripped.
The dryer is protected against excessively high
refrigerant pressure. If the condenser efficiency has
reduced, the switch will trip. Manually reset the
switch.
In case of water cooled con-
densers, check the water
control valve
Excessive ambient temperature
Be sure that dryer is working
in temperatures lower than the
design conditions.
Designed conditions and
correction factors are described
in this manual.
A high ambient temperature may cause
the
refrigerant system to operate at higher than
normal
pressures. Results will be higher than
normal
evaporator temperature.
lmportant: adequate air circulation around the
dryer,
and proper ventilation in the equipment room
should
guarantee a low enough ambient
temperature.
Dryer is
switched on,
but the refrigerant
compressor
does not turn on.
Excessive temperature on
crankcase of compressor.
Allow time to compressor to
cool down. Reason may be a
possible incorrect adjustment
of hot gas bypass valve or
shortage of refrigerant
Compressor is protected against overly high
temperatures of the crankcase by a thermal switch.
Excessive compressed
air inlet temperature.
Be sure that dryer is working
in temperatures lower than
design conditions.
The dryer is designed for working in calculated
conditions (see description in this
manual).
If conditions are exceeded, the dryer will be
overflowed, dew point will go up and protecting
devices can switch off.
Clogged condenser fins or clogged
water condenser.
Possible high crankcase temperature
Possible loss of phase
Possible low voltage causing overload
trip Possible failed compressor
Clear fins or water condenser
of all obstructions.
The clogged fins in the condenser will restrict the
air passage and reduce the refrigeration capacity,
causing high temperature in the evaporator.
Same will occur if water condenser is clogged with
mud or dirt. Air condenser and water condenser
should be periodically checked and cleaned.
Protect water circuit by an adapted filter.
Too much compressed air flow.
Check actual flow
through the dryer.
This dryer is designed for a maximum air flow at
design conditions. If too much air is
pumped
into the dryer, water removal capacity may not
be
sufficient, resulting in liquid carryover down
stream.
Check the rated output the air
compressor.
Faulty electrical wiring
Inspect the circuit
The compressor-on light should be wired into the
refrigerant compressor circuit. See wiring
diagrams
in this manual.
One electrical protection
has tripped.
Reset the protection or
replace the blown fuse.
The dryer is protected against high amp draw
by
fuse and/or overload relay that can trip in case
of
need. Reset or replace fuse once, but do not
persist
if it trips again, request assistance from a
qualified
refrigeration contractor.
Dryer is switched
on but fan is not
running.
Fan has to run if refrigerant high
pressure reaches upper set point.
Check that compressed air
flows through the dryer. Check
that fan blades are free to
move.
Check the fan pressure switch.
Fan operates automatically to keep
refrigerant
pressure below the maximum value. The fan can
stop if pressure is under the recommended setting.
When compressor
starts, it vibrates
a lot and makes
mechanical noise.
Compressor is slugging liquid
refrigerant
at start up.
Be sure the pre-heating period
of at least 2 hours is
respected
Refrigerant may move between receivers when
refrigerant compressor is stopped and not
heated,
especially if stopped for a long time.
This migration may cause liquid shock (slugging) in
valves specially on large dryers containing more
refrigerant
7528%/(6+227,1*

Summary of content (3 pages)