Energy Guide
04.24.13 Rev. 0.3a 13
MENU 0 = PRESSURES
Fun
ction
Descri
ption
Setting values
Default
Password level
WP1 Top range transducer 15 ÷60 15 3
WP2
High p
ress
. alarm
(WP3+0,5) ÷ (W P1
-
0,5 )
11,0 bar
2
-
3
WP3 Stop pressure (WP4+0,2) ÷ (WP2-0,2) 10,0 bar 0-1-2-3
WP4 Start pressure 3 ÷ (WP3-0,2) 8,5 bar 0-1-2-3
WP5 Start press. slave 2,8 ÷ (WP4-0.2) 8,3 bar 0-1-2-3
WP6 Offset -2,0 ÷ +2,0 0 bar 2-3
NOTE: the parameter WP5 is visualized only if the compressor has been set for Master/Slave operation (see menu 11
COMPRESS. CONFIG.).
MENU 3 = TEMPERATURES
Function
Descri
ption
Setting values
Default
Password level
WT1 High temp. alarm (WT2+2°) ÷ 125 110 °C 3
WT2
High temp.
warning
(WT3
+2°) ÷ (WT1
-
2°C)
105 °C
3
WT3 Temp. Start fan 30 ÷ ( WT2-2° ) 70 °C 2-3
WT4 Delta T Stop fan 5 ÷ 15°C 10 °C 2-3
WT5 Low temp. alarm -10 ÷ +15 0 °C 2-3
WT6 Offset -10 ÷ +10 °C 0 °C 3
MENU 5 = WORKING TIMER
Fun
ction
Descri
ption
Setting values
D
efa
ult
Password level
Wt1
Star
2 ÷ 20 sec
5 sec.
3
Wt2 Star/Delta 10 ÷ 50 m.s. 20 m.s. 3
Wt3 Before loading 1 ÷ 900 sec. 2 sec. 3
Wt4
Unload
1 ÷ 10 min
4 min.
2
-
3
Wt5 Safety 10 ÷ 240 sec. 60 sec. 3
Wt6 RL6 On 1 ÷ 10 sec 2 sec 1-2-3
Wt7 RL6 Off 1 ÷ 10 min 3 min. 1-2-3
NOTE: changing the set value, the new data is loaded once the timer in progress is elapsed.
MENU 6 = FILTERS – OIL HOURS
Fun
ction
Descri
ption
Setting values
Counter
Reset
Default
Password level
CAF Change air filter 100 ÷ 3.000 h. xxxxxx h. NO 2.000 1-2-3
COF
Change o
il filter
100 ÷ 10.000 h
xxxxxx h.
NO
2.000
1
-
2
-
3
CSF Change sep. filter 100 ÷ 10.000 h xxxxxx h. NO 4.000 1-2-3
C-- Change oil 100 ÷ 10.000 h xxxxxx h. NO 8.000 1-2-3
C--h Check compressor 100 ÷ 10.000 h xxxxxx h. NO 500 1-2-3
BL Maintenance bearings 100 ÷ 29.999 h xxxxxx h. NO 29.999 1-2-3
NOTE:
- setting the parameter C--h to 10.000 the maintenance alarm “CHECK COMPRESSOR” will not be visualized.
- leaving the parameter BL at the default value (29.999) the alarm “BEARING LUBRICATE” will not be visualized.
The counter is the ON time of the line contactor (RL1) and it comes backwards; when the timer goes to 0, the LCD
visualizes the pertinent message and the counter will go on negative.
By the button and/or select the parameter to change and confirm it by the button ; the LCD visualizes the
message: on the first row CAF = xxh xxm (xxhxxm is the time to elapse), on the second row CHANGE AIR FILTER
Confirm by again and the LCD visualizes:
On the first row “CAF- SET:10.000 – RESET”
On the second row “COUNTER: - 3.500 - |NO| (YES)”
“CAF” is the short name of the parameter with the value previously changed.