INSTRUCTION FOR SERIAL CONNECTION RS232 AND/OR RS485
NOTES ON THE WIRING: wrong wiring can damage both the controller and other devices connected to the
serial port.
Be careful to the following technical points below:
1. Use flexible, twisted pair, earth shielded cable, type 22 AWG.
2. The total length of the net has to be no more than:
- 5 m for serial connection through RS232
- 400 m for serial connection through RS485
3. In serial connection RS485 the maximum devices connectable are 32 units.
NOTES ON INSTALLATION
The signal wire must be placed in electrical trunk separated from power cables or dangerous cables like the wires
of lighting and so on….
Don’t place the signal wires near power bus-bar, lamps, transformers and high frequency antenna.
The signal cable must be minimum 2 m far from heavy inductive load (motors, inverters and control / patch
board).
Don’t pull the cables by strength over 12 Kg; stronger strength can damage the wires and reduce the signal
transmission on the line.
Don’t twist, knot, crush and fray the wires.
Use always a single cable without cut it to make the connection between two devices.
Pay attention to wire stripper.
To be sure that the connection is well done, sign the position of terminal block with the colour of the wire.