Emax Air Dryer REFRIGERATED TYPE COMPRESSED AIR DRYERS EDRCF1150029 – EDRCF4602000 Instructions Manual
TABLE OF CONTENTS 1. Important safety notes - Please read ........................... 1 1.1. Transportation.................................................................. 1 1.2 Positioning ..................................................................... 1 1.3 Installation ......................................................................... 1 1.4 Before operating ............................................................ 1 1.5 Maintenance by an engineer ........................................
I. IMPORTANT SAFETY NOTES – Please READ A) When operating the air dryer the operator must apply safe working methods and observe all local safety instructions and relevant regulations. B) Prior to installation, the dryer and the compressed air system are to be depressurized and disconnected from the electrical main supply. C) The user is responsible for safe operating conditions. Parts and accessories must be replaced if inspection shows that safe operation cannot be assured.
D) For air cooled dryers, clean the air condenser as soon as it’s dirty or clogged. E) For optional water-cooled condensers, use only clean water and install a water filter if needed. Use water counter flow to clean condenser if need. F) Check the trouble-shooting list in case of maintenance troubles. G) Check operating pressures, temperatures and time settings after maintenance. If operating and safety devices function properly, the air dryer may be used. 2.
down to dew point and enters the separator where condensates are collected. The outgoing chilled air is then warmed up in the economizer by the hot incoming air. b) The condensates are collected after centrifugal separation and drained out through the automatic trap. c) As long as the compressed air temperature does not drop below dew point, there will be no condensation in the air circuit. 5) Refrigerant compressor Being of the hermetic type, it requires no servicing.
3. OPERATION 3.1.
3.2. During Operation Regularly check the digital temperature controller ESD3 or dew point indicator on dryer. B) Start up and shut-down Warning: Avoid leaving the dryer off when compressed air is still flowing through it. C) Starting for the first time or after a long stop 1) Set the rotary switch to “I” This preheats the dryer and turns the drain system on. It is recommended to leave the dryer power on permanently so the crankcase heater runs continuously.
Emax Air Dryer REFRIGERATED TYPE COMPRESSED AIR DRYERS Technical Specifications & Diagram
Voltage Total Electric Power 1/2" 115 0.42 R134a <3 232 122 140 3/4" 115 0.68 R134a <3 232 122 140 115 1 1/2" 115 0.93 R134a <3 232 122 140 EDRCF1150144 144 1 1/2" 115 1.28 R134a <3 232 122 140 EDRCF2300288 288 2" 230 1.94 R134a <3 232 122 140 EDRCF4600288 288 2" 460 1.94 R134a <3 232 122 140 EDRCF4600575 575 3" 460 3.01 R134a <3 232 122 140 EDRCF2300575 575 3" 230 3.01 R134a <3 232 122 140 EDRCF4600850 850 3" 460 4.
5.
EDRCF2300288-EDRCF4601200 IMPORTANT NOTICE: E: Timer in not used from EDRCF4600575-EDRCF4601200 F: Only from EDRCF4600288-EDRCF4601200 : Suction accumulator is not used in EDRCF2300288***
5.
EDRCF1150058-EDRCF1150144 Electrical Circuit
EDRCF2300288-EDRCF4600288 Electrical Circuit
EDRCF4600575-EDRCF4601200 Electrical Power Circuit
Emax Air Dryer REFRIGERATED TYPE COMPRESSED AIR DRYERS General Arrangements Main Settings Drawings
6.
Superheat of thermostatic expansion valve 41OF - 50OF Evaporating pressure 29.7 psi Fan pressure switch 130 - 174 psi Security (*) high pressure switch 362.5 psi (*)Available up to EDRCF1150029 and above (**) Available up to EDRCF4600575 and above (***) 1 min. - 5 sec. (up to EDRCF1150144 and above) 5 min. - 4 sec. (up to EDRCF2300288 and above) (****) Available up to EDRCF2300575 and above Security (**) low pressure switch 23.2 psi Drain timer (***) 1 min. - 5- sec. 5 min. - 4- sec. Low pres.
8.
EDRCF1150058
EDRCF1150115-EDRCF1150144
EDRCF2300288-EDRCF4600288
EDRCF4600575-EDRCF2300575
EDRCF4600850-EDRCF4601200
EDRCF1150029
EDRCF1150058
EDRCF1150115
EDRCF1150144
EDRCF2300288-EDRCF4600288
EDRCF4600575-EDRCF2300575
EDRCF4600850
EDRCF4601200
9.
10. TROUBLESHOOTING Problem Possible Cause Repair Dryer is switched on, indicator light is lit but the refrigerant compressor does not turn on. The connection has inverted phases Invert two phases Refrigeration unit is not functioning Check refrigeration compressor The refrigerant high pressure protection has tripped The refrigerant safety high pressure switch has tripped. Comments 3-phase dryers are equipped with a phase controller to avoid the fans from turning in the opposite direction.
Problem Possible Cause Repair Water in system Compressed Air Inlet and outlet connections are reversed. Check inlet and outlet connections. Drain system is clogged or inoperative. Restore a free flow of water condensate. Check water evacuation. Bypass system is open Check the valves Important: Bypass piping should be installed around the dryer so the dryer can be isolated for service without shutting down the air supply. During dryer operation, valves must be set so all air goes into the system.
Problem Possible Cause Repair Comments The unit will not run or cycles off and on. Excessive ambient temperature Designed conditions and correction factors are described in dryer . Be sure that dryer is working lower than design conditions. A high ambient temperature may cause the refrigerant system to operate at higher than normal pressures. Results will be a higher than normal evaporator temperature.