- Emc Power Supply User Manual

30
Net Weight kg (lb)
W/O ISOTR
50 (110) 86.0 (189.2) 80(176)
Shipping Weight kg
(lb) W/O ISOTR
53 (116.7) 106.0 (233.2) 101.5(223.3)
Dimensions W x D
x H mm (inch) W/
ISOTR
257 x 590 x 700
(10.1"x23.2"x27.6")
342 x 690 x 715
(13.4" x 27.2" x
28.1")
Net Weight kg (lb)
W/ ISOTR
123.0 (270.6) 130 (286.0)
Shipping Weight kg
(lb) W/ ISOTR
145.0 (319.0) 151.5 (333.3)
Operating
Temperature
0~40°C / 32~104°F
Storage
Temperature
-20~50°C / -4~122°F
Altitude 3,500 meters max
Audible Noise (1
meter from surface)
50 dBA < 55 dBA
Environment
Relative Humidity 0 ~ 95% humidity, non-condensing
Safety UL 1778, CE
EMC (EMS / EMI) IEC 61000-4, FCC Part 15, CISPR 22
Conformance
Equipment
Protection Policy
Warranty policy may vary depends on region
Tower model (with LCD display) VGD-10000 VGD-12000 VGD-15000 VGD-20000
Capacity (VA) 10000VA 12000VA 15000VA 20000VA
Capacit
y
Capacity (W) 7000W 8400W 10500W 14000W
Voltage (on battery) 100V, 110V, 115V, 120V / 208V, 220V, 230V, 240V +/-2% (Selectable Output Voltage)
Frequency (on
battery)
50 / 60 Hz +/-0.5%
Transfer Time 0 ms
Overload Recovery Auto transfer to UPS
High Efficiency
mode (AC to AC)
> 97 %
UPS Design
Technology
On-Line / Fully digitized microprocessor controlled
Output Wave Form Sine wave
Harmonic distortion < 3% of T.H.D. at linear load
Output
Crest Factor 3 : 1
Surge Protection IEC61000-4-5 level 3
Overload Protection
125% for 1 minutes and 150% for 10 seconds (On-line) 130% for 10 seconds and 150%
for 1.5 seconds (On-battery)
Protection and
Filtering
Short Circuit
Protection
UPS output cut off immediately or input fuse / circuit breaker protection
Visual Display (LED
model)
UPS on(green), line-mode(green), battery mode(yellow), bypass(yellow), fault(red)
Visual Display
(LCD model)
Input / output voltage, input / output frequency, on-line mode, back up mode, battery
capacity, load level
Audible Alarm
(Battery back-up)
Beep every 5 sec
UPS Fault Continuous beeping sound and LCD display
System/Displa
y
/
Warning
Communication RS-232 Serial Port and USB
Type Sealed, maintenance-free lead acid batteries
DC Voltage (V)
Battery (Tower )
240V / 12V9AH
x 20
240V / 12V7.2AH
x 20 x 2SET
240V / 12V7.2AH
x 20 x 2SET
240V / 12V9AH
x 20 x 2SET
Typical Recharge
Time to 90% Full
4 hours
Management Self-test, adjustable battery transfer points and alarm settings
Batter
y
Battery Protection Cut off without draining any current when battery is low
31
Cold Start (DC
start)
YES
Back Up Time
(Tower model)
About 4~6 min Full load / 10~15min Half load
Input Inlet Hardwire
Receptacles Hardwire
Dimensions W x D
x H mm (inch) W/O
ISOTR
257 x 690 x 715
(10.1" x 27.2" x
28.1")
342 x 690 x 905
(13.5"x27.2"x35.6")
342 x 760 x 905 (13.5" x 29.9" x 35.6")
Net Weight kg (lb)
W/O ISOTR
80 (176) 130 (286) 207 (455.4)
Shipping Weight kg
(lb) W/O ISOTR
101.5 (223.3) 151.5 (333.3) 225 (495.0)
Dimensions W x D
x H mm (inch) W/
ISOTR
342 x 690 x 715
(13.4" x 27.2" x
28.1")
342 x 690 x 905
(13.5"x27.2"x35.6")
342 x 760 x 905 (13.5" x 29.9" x 35.6")
Net Weight kg (lb)
W/ ISOTR
130 (286) 180 (396) 274 (602.8)
Physical
Shipping Weight kg
(lb) W/ ISOTR
151.5 (333.3) 201.5 (443.3) 292 (642.4)
Operating
Temperature
0~40°C / 32~104°F
Storage
Temperature
-20~50°C / -4~122°F
Altitude 3,500 meters max
Audible Noise (1
meter from surface)
< 55 dB
Environment
Relative Humidity 0 ~ 95% humidity, non-condensing
Safety UL 1778, CE
EMC (EMS / EMI) IEC 61000-4, FCC Part 15, CISPR 22
Conformance
Equipment
Protection Policy
Warranty policy may vary depends on region
For Rack mount model
RM model (with LCD display) VGD-4000 VGD5000 VGD-6000 VGD-10000
Capacity (VA) 4000VA 5000VA 6000VA 10000VA
Capacit
y
Capacity (W) 2800W 3500W 4200W 7000W
Voltage (on battery) 208V, 220V, 230V, 240V +/-2% (Selectable Output Voltage)
Frequency (on
battery)
50 / 60 Hz +/-0.5%
Transfer Time 0 ms
Overload Recovery Auto transfer to UPS
High Efficiency
mode (AC to AC)
> 95 % > 97 %
UPS Design
Technology
On-Line / Fully digitized microprocessor controlled
Output Wave Form Sine wave
Harmonic distortion < 3% of T.H.D. at linear load
Output
Crest Factor 3 : 1
Surge Protection IEC61000-4-5 level 3
Overload
Protection
125% for 1 minutes and 150% for 10 seconds (On-line) 130% for 10 seconds and 150%
for 1.5 seconds (On-battery)
Protection and
Filtering
Short Circuit
Protection
UPS output cut off immediately or input fuse / circuit breaker protection
Visual Display
(LED model)
UPS on(green), line-mode(green), battery mode(yellow), bypass(yellow), fault(red)
Visual Display
(LCD model)
Input / output voltage, input / output frequency, on-line mode, back up mode, battery
capacity, load level
Audible Alarm
(Battery back-up)
Beep every 5 sec
System/Displa
y
/
Warning
UPS Fault Continuous beeping sound and LCD display