When installing and using this electrical equipment, basic safety
precautions should always be adhered to, including the following:
1. READ AND FOLLOW ALL INSTRUCTIONS.
2. Read and follow all General Safety Instructions provided on pg. 4.
3. A terminal marked "GROUND" is provided within the motor
control enclosure. To reduce the risk of electrical shock, connect
this terminal to the grounding terminal of the electric supply
panel with a continuous green insulated copper wire equivalent in
size to the circuit conductors supplying this equipment, but no
smaller than NO. 8 AWG.
4. This equipment must be provided with a ground fault circuit
interrupter located in the power supply panel as installed by an
electrician. Before each use of your spa, with the power turned on,
push the test button. A red indicator should appear. Push the
reset button, and the red indicator should disappear. IF THE
INTERRUPTER FAILS TO OPERATE IN THIS MANNER, THERE
IS A GROUND CURRENT FLOWING, INDICATING THE
POSSIBILITY OF AN ELECTRIC SHOCK. Shut off the power to
the spa until the source of the breakdown has been identified and
corrected.
5. The electrical service panel should be equipped with a 50-amp
GFCI overcurrent protective device.
6. The minimum supply conductor capacity is 50 Amp and should be
sized as follows: No. 6 AWG 60
o
C, or No. 8 AWG 75
o
C.
7. The electrical supply for the spa must include a suitably rated
switch or circuit breaker to open all ungrounded supply
conductors, to comply with section 422-20 of the National
Electrical Code, ANSI/NFPA 70-1996. The disconnecting means
must be readily accessible to the spa occupant but must not be
within 5 feet of the spa.
240V Hard Wired
Connected
Systems
SAVE THESE INSTRUCTIONS