27
Thermal Expansion Valves
The T-series Take-Apart valves, with adjustable superheat and
replaceable, interchangeable components are ideal for original
equipment and eld replacements in air conditioning, heat pump,
and refrigeration applications.
T-Series – Take-Apart
Features
Take-Apart construction for easy eld service
External superheat adjustment
Bi-Flow capability
Stainless steel power assembly up to 18 tons
Options
Interchangeable, replaceable cages
Interchangeable body anges
Interchangeable power assemblies
1/4 to 100 tons capacity
Specifications
Maximum working pressure: 450 psig
Torque Bolts: 300 in. lb.
Nomenclature example: TCLEB 5 HC 5 FT 3/8 x 1/2 SAE ANG
TCL E B 5 H C 5 FT 3/8 x 1/2 SAE ANG
Valve Series
Take-Apart
Adjustable
Equalizer
E=External
(Omit for Internal)
Bleed Hole
(optional)
B=Bleed Hole
(Omit for no bleed
hole)
Capacity
Nominal Rating
in Tons
(See Cage
Assembly
Interchangeability
Tables)
Refrigerant Code
+F = R-12
• H = R-22
+M = R-134a
• N = R-407C
*P = R-507
*R = R-502
*S = R404A
Charge Code
C = medium temp
CA = heat pump
W(MOP) = press. limiting
Z = low temp
Capillary Tube Length Inlet x Outlet
Connection Sizes
Various sizes are
available (valve is also
available less ange)
Connection Type
SAE=are
ODF=solder
Conguration
ANG = 90° angle
S/T=straight-thru
Single Outlet “T” Series Body Flanges with Bleed Hole for Use with PSC Compressors
Valve Type Bleed Hole Diameter
1
for % Capacity Bypass
R-12/R-134a R-22/R-407C
R-507/R-
502/R-404A
10% 15% 20% 25% 30% 40%
Dia.
(In)
Drill
Size
Dia.
(In)
Drill
Size
Dia.
(In)
Drill
Size
Dia.
(In)
Drill
Size
Dia.
(In)
Drill
Size
Dia.
(In)
Drill
Size
TCL1/4F TCL1/2H TCL1/2R 0.02 1/64 0.02 77 0.02 76 0.02 74 0.03 72
TCL1/2F TCL1H TCL1/2R 0.02 77 0.02 75 0.02 73 0.03 71 0.03 69 0.04 65
TCL1F TCL2H TCL1R 0.03 71 0.03 1/32 0.04 64 0.04 60 0.05 56 0.05 55
TCL2F TCL3H TCL2R 0.03 70 0.04 65 0.04 60 0.04 57 0.05 3/4 0.06 54
TCL3F TCL5H TCL3R 0.04 65 0.04 57 0.05 55 0.06 54 0.06 1/16 0.07 50
TCL4F TCL7-1/2H TCL4-1/2R 0.04 57 0.05 55 0.06 53 0.07 51 0.08 48 0.09 44
TCL6-1/2F TCL10H TCL7R 0.05 55 0.06 53 0.07 50 0.08 47 0.09 44 0.10 39
TCL7-1/2F TCL12H TCL8R 0.05 55 0.06 53 0.07 50 0.08 47 0.09 44 0.10 39
1
Bleed hole sizes shown above are based on a percent of full effective port area of the valve. This does not necessarily indicate the percent of valve capacity that will be bypassed. The hole sizes shown
above should be used for reference only. Normal industry practice is to equalize systems 3 to 5 minutes.
+ = R-12 and R-134a are interchangeable refrigerant charges
* = R-507, R-502 and R-404A are interchangeable refrigerant charges
• = R-22 and R-407C are interchangeable refrigerant charges