Product Overview

2004FC-118 R13 (01/14) Emerson Climate Technologies
SOL 16
Solenoid Valves & Coils
Features
Compact designs
Coil windings are insulated to provide shock and vibration
protection
ASC2 is designed to provide weather protection
Interchangeable housings
Voltage Options
24V 50/60 Hz
120V 50/60 Hz (standard)
208-220/208-240V 50/60 Hz
480V 50/60 Hz
120-240V 50/60 Hz
12V D.C. (MM Series recommended)
24V D.C. (MM Series recommended)
ASC2 – DIN
MMG – Special DC
AMC - 1/2” Conduit AMG - Junction Box
AMS - Open Frame
Nominal Voltage
and Frequency
Applied Voltage
and Frequency
204CD 214C 211CA 222CB 210CA
Inrush Holding Inrush Holding Inrush Holding Inrush Holding Inrush Holding
24/60 24/60 1.23 0.61 1.17 0.61 0.92 0.61 1.00 0.74 0.92 0.61
120/60 120/60 0.23 0.14 0.22 0.14 0.17 0.14 0.19 0.16 0.17 0.14
240/60 240/60 0.13 0.08 0.12 0.08 0.10 0.08 0.11 0.08 0.10 0.08
480/60 480/60 0.06 0.04 0.05 0.04 0.05 0.04 0.05 0.04 0.05 0.04
See the MM (MAGMAX) Series Coil for DC Applications
MAGMAX Coil (Type MM): For Use On DC Applications Only
Voltage
Amperes
Holding
Watts
Holding
12VDC 0.4 4
24VDC 0.4 4
Solenoid Coil Prefix Selection Table 1) Select Prex 2) Select Voltage 3) Select PCN
Valve Type J-Box Conduit Leads Spades Molded-DIN With Connector
50RB - - SML* - -
100RB AMG AMC AMF AMS ASC2
200RB / 200RD AMG AMC AMF AMS ASC2
222CB (Steam) AHG AHC - - -
500RB DMG - DMF DMS -
540RA - - - DMS ASC2
222CB (Water) AMG AMC AMF AMS ASC2
Special DC Application MMG - MMF - -
* SML is OEM - RMF is Wholesale replacement
Note - All coils NEMAI except ASC2 NEMA2
Nomenclature
Coil Code
A M G
Series Insulation Enclosure
A = 12 Watt
B = 15 Watt
C = 18 Watt
D = 7 Watt
M = 4 Watt
B or G = Class B
M = Class F
H = Class H
C = Conduit Connection
F = Open Frame Leads
G = Junction Box
L = Grommet 18” Leads
S = Spade Connection
Requires ASC2 female connector
(PCN 059261).
Coils for Solenoid Valves
AM/EM Coil:
204CD
214CB
211CA
222CB
210CA

Summary of content (4 pages)