Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Pressure Transmitter with FOUNDATION™ Fieldbus Protocol www.rosemount.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Rosemount 2051 Pressure Transmitter with FOUNDATION Fieldbus NOTICE Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product. For technical assistance, contacts are listed below: Customer Central Technical support, quoting, and order-related questions.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Table of Contents SECTION 1 Introduction Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 Service Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 Models Covered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2 SECTION 2 Installation Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Configure the AI block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5 Configuration Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6 Pressure transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6 Pressure transmitter used to measure level in an open tank . . . . 3-6 Differential pressure transmitter to measure flow . . . . . . . . . . . . . 3-8 Filtering . .
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Vibration Effect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3 Power Supply Effect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3 Electromagnetic Compatibility (EMC) . . . . . . . . . . . . . . . . . . . . . . A-3 Transient Protection (Option Code T1) . . . . . . . . . . . . . . . . . . . . . A-3 Functional Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Rosemount 2051 TOC-4 00809-0200-4101, Rev AA July 2008
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Section 1 Introduction USING THIS MANUAL The sections in this manual provide information on installing, operating, and maintaining Rosemount 2051 pressure transmitters with FOUNDATION fieldbus. The sections are organized as follows: SERVICE SUPPORT • Section 2: Installation contains mechanical and electrical installation instructions.
Reference Manual Rosemount 2051 MODELS COVERED 00809-0200-4101, Rev AA July 2008 The following Rosemount 2051 Pressure Transmitters are covered by this manual: Rosemount 2051C Coplanar™ Pressure Transmitter 2051CD - Differential Pressure Transmitter Measures differential pressure up to 2000 psi (137,9 bar) 2051CG - Gage Pressure Transmitter Measures gage pressure up to 2000 psi (137,9 bar) Rosemount 2051T In-Line Pressure Transmitter 2051TG - Gage Pressure Transmitter Measures gage pressure up to 10000 p
Reference Manual 00809-0200-4101, Rev AA July 2008 Section 2 Rosemount 2051 Installation Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1 General Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-2 Mechanical Considerations . . . . . . . . . . . . . . . . . . . . . . . . page 2-2 Environmental Considerations . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Electrical shock can result in death or serious injury. • Avoid contact with the leads and terminals. Process leaks could result in death or serious injury. • Install and tighten all four flange bolts before applying pressure. • Do not attempt to loosen or remove flange bolts while the transmitter is in service.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 INSTALLATION PROCEDURES Dimensional Drawings 2051C Coplanar Flange Dimensional Drawing 5.46 (138,7) 4.99 (127) 3.85 (98) 7.03 (179) 6.40 (163) 2051C Coplanar with Rosemount 305 Coplanar Integral Manifold 5.46 (138,7) 3.85 (98) 4.99 (127) 6.19 (157) 7.44 (189) Drain/ Vent Valve 5.50 (140) MAX OPEN 10.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Coplanar Flange Mounting Configurations with Optional Bracket (B4) for 2-in. Pipe or Panel Mounting 4.99 (127) 2.45 (62) 5 /16 ⫻ 11/2 Bolts for Panel Mounting (Not Supplied) PANEL MOUNTING 2.8 (71) 7.03 (179) 3 /8–16 × 11/4 Bolts for Mounting to Transmitter 6.15 (156) 2.81 (71) 3.4 (85) 4.73 (120) PIPE MOUNTING 2-inch U-Bolt for Pipe Mounting 3 /8–16 × 11/4 Bolts for Mounting to Transmitter 6.22 (158) 2-4 3.4 (85) 3.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 2051C Coplanar with Traditional Flange 5.46 (139) 4.99 (127) 3.85 (98) 7.76 (197) 1 /2 - 14 NPT Flange Adapter (optional) Drain/ Vent Valve 1.626 (41,3) 1.10 (28) 2.126 (54) 3.40 (86) 2051C Coplanar with Rosemount 305 Traditional Integral Manifold 5.46 (139) 3.85 (98) 6.19 (157) 4.99 (127) 1 /2 - 14 NPT Flange Adapter (optional) Drain/ Vent Valve 1.626 (41,3) 3.75 (95) MAX OPEN 1.05 (27) 3.50 (89) 1.10 (28) 6.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Traditional Flange Mounting Configurations with Optional Brackets for 2-in. Pipe or Panel Mounting Panel Mount (Bracket Option B2 / B8) Pipe Mount (Bracket Option B3 / B9 / BC) 9.18 (233) 2.62 (67) 6.19 (157) 1.94 (49) 11.51 (292) 3.56 (90) 4.85 (123) 5.32 (135) 3.50 (89) 6.19 (157) Pipe Mount (Bracket Option B1 / B7 / BA) 6.76 (172) 3.56 (90) MAX OPEN 1.10 (28) 3.50 (89) 2.62 (67) 0.93 (24) 2-6 1.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 2051T Dimensional Drawings 5.46 (139) 4.99 (127) 3.85 (98) 7.15 (182) 2051T with Rosemount 306 Integral Manifold 3.85 (98) 5.46 (139) 4.99 (127) 7.15 (182) 4.10 (105) 4.85 (123) 6.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 2051T Typical Mounting Configurations with Optional Mounting Bracket Pipe Mounting Panel Mounting 3.85 (98) 5.16 (131) 1.99 (51) 2.81 (71) 6.21 (158) 3.49 (89) 2-8 4.72 (120) 6.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 2051L Liquid Level 2-in. Flange Configuration (Flush Mount Only) 3- and 4-in. Flange Configuration 3.85 (98) 3.85 (98) E D 2-in., 4-in., or 6-in. Extension (50.8, 101.6, 152.4) A H Optional Flushing Connection Ring (Lower Housing) A H 5.46 (138,7) 4.99 (127) G 6.60 (68) F 7.02 (178) E 8.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Table 2-1. 2051L Dimensional Specifications Except where indicated, dimensions are in inches (millimeters). Class ASME B16.5 (ANSI) 150 ASME B16.5 (ANSI) 300 DIN 2501 PN 10–40 DIN 2501 PN 25/40 Pipe Size 2 (51) 3 (76) 4 (102) 2 (51) 3 (76) 4 (102) DN 50 DN 80 DN 100 Flange Thickness A Bolt Circle Diameter B Outside Diameter C No. of Bolts Bolt Hole Diameter Extension Diameter(1) D O.D. Gasket Surface E 0.69 (18) 0.88 (22) 0.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Mounting Brackets Rosemount 2051 Transmitters may be panel-mounted or pipe-mounted through an optional mounting bracket. Refer to Table 2-2 for the complete offering and see Figure 2-1 through Figure 2-5 on pages 2-11 and 2-12 for dimensions and mounting configurations. Table 2-2.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Figure 2-2. Mounting Bracket Option Codes B1, B7, and BA 1.65 (42) 3.75 (95) 3.87 (98) 2.62 (67) 4.97 (127) 2.81 (71) Figure 2-4. Panel Mounting Bracket Option Codes B2 and B8 3.75 (95) 1.65 (42) Mounting Holes 0.375 Diameter (10) 3.87 (98) 1.40 (36) 1.40 (36) 2.81 (71) 4.5 (114) 1.40 (36) Figure 2-5. Flat Mounting Bracket Option Codes B3 and BC 2.125 (54) 1.62 (41) 8 (203) 2.81 (71) NOTE Dimensions are in inches (millimeters).
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Flange Bolts The 2051 is shipped with a Coplanar flange installed with four 1.75-in. (44 mm) flange bolts. See Figure 2-6 and Figure 2-7 on pages 2-14 and 2-14. Stainless steel bolts are coated with a lubricant to ease installation. Carbon steel bolts do not require lubrication. No additional lubricant should be applied when installing either type of bolt.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Figure 2-6. Traditional Flange Bolt Configurations DIFFERENTIAL TRANSMITTER GAGE TRANSMITTER Drain/Vent Plug Drain/Vent Drain/Vent 1.75 (44) × 4 NOTE Dimensions are in inches (millimeters). 1.75 (44) × 4 1.50 (38) × 4 Figure 2-7. Mounting Bolts and Bolt Configurations for Coplanar Flange TRANSMITTER WITH FLANGE ADAPTERS AND FLANGE/ADAPTER BOLTS TRANSMITTER WITH FLANGE BOLTS 2.88 (73) × 4 1.75 (44) × 4 Description Size in.
Reference Manual 00809-0200-4101, Rev AA July 2008 Impulse Piping Rosemount 2051 The piping between the process and the transmitter must accurately transfer the pressure to obtain accurate measurements. There are six possible sources of impulse piping error: pressure transfer, leaks, friction loss (particularly if purging is used), trapped gas in a liquid line, liquid in a gas line, and density variations between the legs.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Mounting Requirements Impulse piping configurations depend on specific measurement conditions. Refer to Figure 2-8 for examples of the following mounting configurations: Liquid Flow Measurement • Place taps to the side of the line to prevent sediment deposits on the process isolators. • Mount the transmitter beside or below the taps so gases vent into the process line. • Mount drain/vent valve upward to allow gases to vent.
Reference Manual 00809-0200-4101, Rev AA July 2008 Process Connections Rosemount 2051 Coplanar or Traditional Process Connection Install and tighten all four flange bolts before applying pressure, or process leakage will result. When properly installed, the flange bolts will protrude through the top of the sensor module housing. Do not attempt to loosen or remove the flange bolts while the transmitter is in service.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 O-rings: The two styles of Rosemount flange adapters (Rosemount 1151 and Rosemount 3051/2051/2024/3095) each require a unique O-ring (see Figure 2-9). Use only the O-ring designed for the corresponding flange adaptor. Figure 2-9. O-Rings. Failure to install proper flange adapter O-rings may cause process leaks, which can result in death or serious injury. The two flange adapters are distinguished by unique O-ring grooves.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Inline Process Connection Do not apply torque directly to the sensor module. Rotation between the sensor module and the process connection can damage the electronics. To avoid damage, apply torque only to the hex-shaped process connection. Sensor Module Process Connection Housing Rotation The electronics housing can be rotated up to 180 degrees in either direction to improve field access, or to better view the optional LCD display.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 LCD Display Transmitters ordered with the LCD option are shipped with the display installed. Installing the display on an existing 2051 transmitter requires a small instrument screwdriver. Figure 2-11. LCD Display . Jumpers (Top and Bottom) LCD Display Extended Cover Tagging Commissioning (Paper) Tag When commissioning more than one device on a fieldbus segment, it can be difficult to identify which device is at a particular location.
Reference Manual 00809-0200-4101, Rev AA July 2008 ELECTRICAL CONSIDERATIONS Rosemount 2051 NOTE Make sure all electrical installation is in accordance with national and local code requirements. Conduit Installation If all connections are not sealed, excess moisture accumulation can damage the transmitter. Make sure to mount the transmitter with the electrical housing positioned downward for drainage.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Wiring Wiring and power supply requirements can be dependent upon the approval certification. As with all FOUNDATION fieldbus requirements, a conditioned power supply and terminating resistors are required for proper operation. The standard 2051 pressure transmitter terminal block is pictured in Figure 2-13. The terminals are not polarity sensitive. The transmitter requires 9-32 Vdc to operate.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Perform the following procedure to make wiring connections: 1. Remove the housing cover on terminal compartment side. Do not remove the cover in explosive atmospheres when the circuit is live. Signal wiring supplies all power to the transmitter. 2. Connect the leads to the two FOUNDATION fieldbus wiring terminals. Refer to Figure 2-14. 3.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 NOTE The transient protection terminal block does not provide transient protection unless the transmitter case is properly grounded. Use the guidelines to ground the transmitter case. Refer to page 2-25. Do not run the transient protection ground wire with signal wiring as the ground wire may carry excessive current if a lightning strike occurs.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Figure 2-15. Transmitter Jumper Locations Simulate Jumper Security Jumper Grounding Use the following techniques to properly ground the transmitter case: Transmitter Case Always ground the transmitter case in accordance with national and local electrical codes. The most effective transmitter case grounding method is a direct connection to earth ground with minimal impedance.
Reference Manual Rosemount 2051 Figure 2-16. Internal Ground Screw 00809-0200-4101, Rev AA July 2008 Internal Ground Connection Screw Figure 2-17. External Ground Assembly External Ground Assembly NOTE Grounding the transmitter case via threaded conduit connection may not provide sufficient ground continuity.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 HAZARDOUS LOCATIONS CERTIFICATIONS Individual transmitters are clearly marked with a tag indicating the approvals they carry. Transmitters must be installed in accordance with all applicable codes and standards to maintain these certified ratings. Refer to Appendix B: Approval Information for information on these approvals.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Rosemount 305 Integral Manifold Installation Procedure To install a 305 Integral Manifold to a 2051 transmitter: 1. Inspect the PTFE sensor module o-rings. Undamaged o-rings may be reused. If the o-rings are damaged (if they have nicks or cuts, for example), replace with o-rings designed for Rosemount transmitter.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Integral Manifold Operation Three-valve configuration shown. In normal operation the two isolate valves between the process and instrument ports will be open and the equalizing valve(s) will be closed. L H Drain/ Vent Valve Drain/ Vent Valve Equalize (closed) Isolate (open) Isolate (open) Process To zero the 2051, close the isolate valve to the low pressure (downstream side) of the transmitter first.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 The manifold valves are now in the proper configuration for zeroing the transmitter. To return the transmitter to service, close the equalizing valve(s) first. L H Drain/ Vent Valve Drain/ Vent Valve Equalize (closed) Isolate (open) Isolate (closed) Process Next, open the isolate valve on the low pressure side of the transmitter.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 LIQUID LEVEL MEASUREMENT Differential pressure transmitters used for liquid level applications measure hydrostatic pressure head. Liquid level and specific gravity of a liquid are factors in determining pressure head. This pressure is equal to the liquid height above the tap multiplied by the specific gravity of the liquid. Pressure head is independent of volume or vessel shape.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Wet Leg Condition Condensation of the gas above the liquid slowly causes the low side of the transmitter piping to fill with liquid. The pipe is purposely filled with a convenient reference fluid to eliminate this potential error. This is a wet leg condition. The reference fluid will exert a head pressure on the low side of the transmitter. Zero elevation of the range must then be made. See Figure 2-20 Figure 2-20. Wet Leg Example.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Bubbler System in Open Vessel A bubbler system that has a top-mounted pressure transmitter can be used in open vessels. This system consists of an air supply, pressure regulator, constant flow meter, pressure transmitter, and a tube that extends down into the vessel. Bubble air through the tube at a constant flow rate.
Reference Manual Rosemount 2051 2-34 00809-0200-4101, Rev AA July 2008
Reference Manual 00809-0200-4101, Rev AA July 2008 Section 3 Rosemount 2051 Configuration Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1 Device Capabilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-2 General Block Information . . . . . . . . . . . . . . . . . . . . . . . . . page 3-2 Resource Block . . . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 DEVICE CAPABILITIES Link Active Scheduler The Rosemount 2051 can be designated to act as the backup Link Active Scheduler (LAS) in the event that the LAS is disconnected from the segment. As the backup LAS, the 2051 will take over the management of communications until the host is restored. The host system may provide a configuration tool specifically designed to designate a particular device as a backup LAS.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Other Types of Modes Other types of modes are Cas, RCas, ROut, IMan and LO. Some of these may be supported by different function blocks in the Rosemount 2051. For more information, see the Function Block manual, document 00809-0100-4783. NOTE When an upstream block is set to OOS, this will impact the output status of all downstream blocks.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 SOFT W LOCK and HARD W LOCK Inputs to the security and write lock functions include the hardware security switch, the hardware and software write lock bits of the FEATURE_SEL parameter, the WRITE_LOCK parameter, and the DEFINE_WRITE_LOCK parameter. The WRITE_LOCK parameter prevents modification of parameters within the device except to clear the WRITE_LOCK parameter.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 ANALOG INPUT (AI) FUNCTION BLOCK Configure the AI block A minimum of four parameters are required to configure the AI Block. The parameters are described below with example configurations shown at the end of this section. CHANNEL Select the channel that corresponds to the desired sensor measurement. The 2051 measures both pressure (channel 1) and sensor temperature (channel 2). Table 3-1.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 L_TYPE is Indirect Square Root When an inferred measurement is made based on the sensor measurement AND the relationship between the inferred measurement and sensor measurement is square root, set the XD_SCALE to represent the operating range that the sensor will see in the process. Determine the inferred measurement values that correspond to the XD_SCALE 0 and 100% points and set these for the OUT_SCALE.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Figure 3-1. Situation #2 Diagram. Full Tank 16 ft 7.0 psi measured at the transmitter Solution to Situation #2 Table 3-3 lists the appropriate configuration settings. Table 3-3. Analog Input function block configuration for a pressure transmitter used in level measurement (situation #1).
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Situation #3 The transmitter in situation #3 is installed below the tank in a position where the liquid column in the impulse line, with an empty tank, is equivalent to 2.0 psi (see Figure 3-2). Figure 3-2. Situation #3 Diagram. 16 ft Empty Tank 0 ft 2.0 psi measured at the transmitter Solution to situation #3 Table 3-4 lists the appropriate configuration settings. Table 3-4.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Solution Table 3-5 lists the appropriate configuration settings. Table 3-5. Analog Input Function Block Configuration for a Differential Pressure Transmitter. Parameter Configured Values L_TYPE XD_SCALE OUT_SCALE Channel Indirect Square Root 0 to 20 in.H2O 0 to 800 gal/min.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Process Alarms Process Alarm detection is based on the OUT value. Configure the alarm limits of the following standard alarms: • High (HI_LIM) • High high (HI_HI_LIM) • Low (LO_LIM) • Low low (LO_LO_LIM) In order to avoid alarm chattering when the variable is oscillating around the alarm limit, an alarm hysteresis in percent of the PV span can be set using the ALARM_HYS parameter.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Advanced Features The AI Function Block provides added capability through the addition of the following parameters: ALARM_SEL ALARM_SEL allows one or more of the process alarm conditions detected by the AI function block to be used in setting its OUT_D parameter. OUT_D OUT_D is the discrete output of the AI function block based on the detection of process alarm condition(s).
Reference Manual Rosemount 2051 00809-0200-4101, Rev AA July 2008 For each parameter n(n =1 - 4) displayed on the LCD there are several fields in the "Local Display" tab that must be setup. Figure 3-5. Transducer500 Properties Local Display Screen 1. The first parameter is called "BLOCK TAG_n," here you must enter the exact name of the block to be displayed. This must be the same name as the one that is stored in the device. 2. Then select "BLOCK TYPE_n".
Reference Manual 00809-0200-4101, Rev AA July 2008 Section 4 Rosemount 2051 Operation and Maintenance Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1 Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-2 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Electrical shock can result in death or serious injury. • Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock. Performing a 'Restart with defaults' will set all function block information in the device to factory defaults. This includes the clearing of all function block links and schedule, as well as defaulting all Resource and Transducer Block user data.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 NOTE As a safety measure, the switch must be reset every time power is interrupted to the device in order to enable SIMULATE. This prevents a device that is tested on the bench from getting installed in the process with SIMULATE still active. 2. To change both the OUT_VALUE and OUT_STATUS of the AI Block, set the TARGET MODE to AUTO. 3. Set SIMULATE_ENABLE_DISABLE to ‘Active’. 4.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Sensor Calibration, Zero Trim Method Sensor Transducer Block In order to zero the transmitter, run the Zero Trim Method. If your system does not support methods, manually configure the Transducer Block parameters listed below. 1. Set MODE_BLK.TARGET to OOS 2. Apply zero pressure to the sensor and allow the to reading stabilize 3. Set values CAL_POINT_LO to 0 4. Set SENSOR_CAL_DATE to the current date. 5.
Reference Manual 00809-0200-4101, Rev AA July 2008 Section 5 Rosemount 2051 Troubleshooting Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-1 Troubleshooting Guides . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-2 Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-5 Sensor Transducer Block . . . . . . . . . . . . . . .
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 TROUBLESHOOTING GUIDES Figure 5-1. Rosemount 2051 troubleshooting flowchart PROBLEMS WITH COMMUNICATIONS Device does not appear on segment. Device does not stay on segment. 1. Check wiring to device. 2. Recycle power to device. 3. Electronic failure. Refer to “Device does not show up on segment” in Table 5-1 for more information.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Figure 5-2. Problems with communications flowchart COMMUNICATIONS ESTABLISHED BUT HAVE “BLOCK_ERR” OR AN “ALARM” CONDITION. Read the following parameters in the Resource Block to determine the recommended action.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Table 5-1. Troubleshooting guide Symptom(1) Cause Recommended Actions Device does not show up on segment Unknown No power to device Recycle power to device 1. Ensure the device is connected to the segment. 2. Check voltage at terminals. There should be 9–32Vdc. 3. Check to ensure the device is drawing current. There should be approximately 17 mA.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 RESOURCE BLOCK This section describes error conditions found in the Resource block. Read Table 5-2 through Table 5-4 to determine the appropriate corrective action. Table 5-2. Resource Block BLOCK_ERR messages Block Errors Table 5-2 lists conditions reported in the BLOCK_ERR parameter. Condition Name and Description Other Simulate Active: This indicates that the simulation switch is in place.
Reference Manual Rosemount 2051 00809-0200-4101, Rev AA July 2008 SENSOR TRANSDUCER BLOCK This section describes error conditions found in the Sensor Transducer Block. Read Table 5-5 through Table 5-7 to determine the appropriate corrective action. Table 5-5. Sensor Transducer Block BLOCK_ERR messages Condition Name and Description Other Out of Service: The actual mode is out of service. Table 5-6.
Reference Manual 00809-0200-4101, Rev AA July 2008 ANALOG INPUT (AI) FUNCTION BLOCK Rosemount 2051 This section describes error conditions that are supported by the AI Block. Read Table 5-9 to determine the appropriate corrective action. Table 5-8. AI BLOCK_ERR Conditions.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 1. Put Resource block into "OOS" (Out of Service). 2. Go to the parameter called "SELF_TEST" and write the value Self test (0x2). 3. Observe the LCD screen when you are doing this. All of the segments should light up. 4. Put the Resource block back into "AUTO". Table 5-10. LCD Transducer Block BLOCK_ERR messages Condition Name and Description Other Out of Service: The actual mode is out of service.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 DISASSEMBLY PROCEDURES Do not remove the instrument cover in explosive atmospheres when the circuit is live. Remove from Service Follow these steps: Remove Terminal Block • Follow all plant safety rules and procedures. • Isolate and vent the process from the transmitter before removing the transmitter from service. • Remove all electrical leads and disconnect conduit. • Remove the transmitter from the process connection.
Reference Manual Rosemount 2051 Remove the Electronics Board 00809-0200-4101, Rev AA July 2008 The transmitter electronics board is located in the compartment opposite the terminal side. To remove the electronics board perform the following procedure: 1. Remove the housing cover opposite the field terminal side. 2. If you are disassembling a transmitter with a LCD display, loosen the two captive screws that are visible on the right and left side of the meter display. 3.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 REASSEMBLY PROCEDURES 1. Inspect all cover and housing (non-process wetted) O-rings and replace if necessary. Lightly grease with silicone lubricant to ensure a good seal. 2. Carefully tuck the cable connector completely inside the internal black cap. To do so, turn the black cap and cable counterclockwise one rotation to tighten the cable. 3. Lower the electronics housing onto the module.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 a. Coplanar Process Flange: • Hold the process flange in place by installing the two alignment screws to finger tightness (screws are not pressure retaining). Do not overtighten as this will affect module-to-flange alignment. • Install the four 1.75-in. flange bolts by finger tightening them to the flange. b.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Appendix A Reference Data Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . page A-1 Functional Specifications . . . . . . . . . . . . . . . . . . . . . . . . . page A-4 Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-9 Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-12 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Long Term Stability Models Standard Performance Option, P8 2051C(1) Ranges 2-5 ±0.1% of URL for 2 years ±0.125% of URL for 5 years 2051CD Range 1 ±0.2% of URL for 1 year 2051T(1) Ranges 1-5 ±0.1% of URL for 2 years ±0.125% of URL for 5 years (1) Measured at reference conditions after exposure to temperature changes of up to ±50 °F (28 °C), and line pressure changes up to 1000 psi (6,9 mPa).
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Ambient Temperature Effect per 50°F (28°C) Models Ambient Temperature Effect 2051C Ranges 2-5 ±(0.025% URL + 0.125% span) from 1:1 to 5:1 ±(0.05% URL + 0.25% span) from 5:1 to 100:1 Range 1 ±(0.2% URL + 0.5% span) from 1:1 to 50:1 2051T 2051L Range 2-4 ±(0.05% URL + 0.25% span) from 1:1 to 30:1 ±(0.07% URL + 0.25% span) from 30:1 to 100:1 Range 1 ±(0.05% URL + 0.25% span) from 1:1 to 10:1 ±(0.10% URL + 0.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 FUNCTIONAL SPECIFICATIONS Range and Sensor Limits Range 2051CD, 2051CG, 2051L 1 2 3 4 5 Range and Sensor Limits Lower (LRL) Minimum Span Upper (URL) 2051C Differential 2051C Gage(1) 2051L Differential 2051L Gage(1) 0.5 inH2O (1,2 mbar) 2.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Load Limitations Maximum loop resistance is determined by the voltage level of the external power supply, as described by: Table A-1. Maximum Loop Resistance = 43.5 * (Power Supply Voltage – 10.5) Load (Ohms) 1387 1000 500 Operating Region 0 10.5 20 30 Voltage (V dc) 42.4 The HART communicator requires a minimum loop resistance of 250Ω for communication.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 LCD Block • Configures the local display. 2 Analog Input Blocks • Processes the measurements for input into other function blocks. The output value is in engineering units or custom and contains a status indicating measurement quality. PID Block • Contains all logic to perform PID control in the field including cascade and feedforward.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 2051L Limit is flange rating or sensor rating, whichever is lower (see Table A-2). Table A-2. 2051L Flange Rating Standard Type CS Rating SST Rating ANSI/ASME Class 150 285 psig 275 psig ANSI/ASME Class 300 740 psig 720 psig At 100 °F (38 °C), the rating decreases with increasing temperature. DIN PN 10–40 40 bar 40 bar DIN PN 10/16 16 bar 16 bar At 248 °F (120 °C), the rating decreases with increasing temperature.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Table A-3. 2051 Process Temperature Limits Inert Fill Sensor(1) 0 to 185 °F (–18 to 85 °C) (2) 2051L High-Side Temperature Limits (Process Fill Fluid) Syltherm® XLT D.C. Silicone 704® D.C.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 PHYSICAL SPECIFICATIONS Electrical Connections 1 Process Connections 2051C • 1/4–18 NPT on 21/8-in. centers • 1/2–14 NPT and RC 1/2 on 2-in.(50.8mm), 21/8-in. (54.0 mm), or 21/4-in. (57.2mm) centers (process adapters) /2–14 NPT, G1/2, and M20 × 1.5 (CM20) conduit.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Reference Process Connection (Transmitter Low Side) Isolating Diaphragms • 316L SST or Alloy C-276 Reference Flange and Adapter • CF-8M (Cast version of 316 SST, material per ASTM-A743) Non-Wetted Parts for 2051C/T/L Electronics Housing Low-copper aluminum or CF-8M (Cast version of 316 SST).
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Shipping Weights Table A-4. Transmitter Weights without Options Transmitter lb. (kg) 2051C 2051L 2051T 4.9 (2,2) Table A-5 below 3.1 (1,4) Table A-5. 2051L Weights without Options Flange 2-in., 150 3-in., 150 4-in., 150 2-in., 300 3-in., 300 4-in., 300 DN 50/PN 40 DN 80/PN 40 DN 100/ PN 10/16 DN 100/ PN 40 Flush lb. (kg) 2-in. Ext. lb (kg) 4-in. Ext. lb (kg) 6-in. Ext. lb (kg) 12.5 (5,7) 17.5 (7,9) 23.5 (10,7) 17.5 (7,9) 22.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 ORDERING INFORMATION Model Transmitter Type (Select One) 2051C Pressure Transmitter • • Model Measurement Type CD CG Differential Gage • — — • CD CG • • • • • • • • • • CD CG • • • • D G Code 1 2 3 4 5 Code A M F Code 2 3(1) 5 7(1) 8(1) 0 Pressure Ranges (Range/Min. Span) 2051CD –25 to 25 inH2O/0.5 inH2O (–62,2 to 62,2 mbar/1,2 mbar) –250 to 250 inH2O/2.
Reference Manual 00809-0200-4101, Rev AA July 2008 Code Rosemount 2051 Options CD CG • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • — — • • • — • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • (2) Alternate Process Connection: Flange H2 Traditional Flange, 316 SST, SST Drain/Vent H3(1) Traditional Flange, Cast C-276, Alloy C-276 Drain/Vent H7(1) Traditional Flange, 316 SST, Alloy C-27
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 IF(11) CSA FISCO Intrinsically Safe IG(11) IECEx FISCO Intrinsically Safe IP(10) Korea (KOSHA) Instrinsic Safety (consult factory for availability) IM(10) GOST Intrinsically Safe (consult factory for availability) IW(10) India (CCOE) Intrinsic Safety Approval (consult factory for availability) K1(10) ATEX Flameproof, Intrinsic Safety, Type n, Dust K2(10) INMETRO Flameproof, Intrinsic Safety, Type n (consult factory for availability) K4(10) T
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 (6) Not valid with optional code D9 for RC1/2 Adaptors. (7) Not valid with optional codes DF & D9 for Adaptors. (8) Requires option in the Alternate Process Connection: Flange section. (9) Requires Coplanar flange. (10) Not available with Low Power output code M. (11) Only valid with FOUNDATION fieldbus output code F. (12) Not available with FOUNDATION fieldbus output code F.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Model Transmitter Type (Select One) 2051T In-Line Pressure Transmitter Model G A Code 1 2 3 4 5 Code A M F Code 2B 2C 2F Code 2(1) 3(1) Code 1 2 Code A B D J K M Code Measurement Type Gage Absolute Pressure Ranges (Ranges/ Min. Span) 2051TG –14.7 to 30 psi/0.3 psi (–1,01 to 2,1 bar/20,7 mbar) –14.7 to 150 psi/1.5 psi (–1,01 to 10,3 bar/103,4 mbar) –14.7 to 800 psi/8 psi (–1,01 to 55,2 bar/0,55 bar) –14.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 ATEX Intrinsic Safety I1 I2(3) INMETRO Intrinsic Safety (consult factory for availability) I3(3) China Intrinsic Safety (consult factory for availability) I4(3) TIIS Intrinsic Safety (consult factory for availability) I5 FM Intrinsically Safe, Division 2 I6 CSA Intrinsically Safe I7(3) IECEx Intrinsic Safety IA(4) ATEX FISCO Intrinsic Safety IB(4) INMETRO FISCO Intrinsic Safety (consult factory for availability) ID(4) TIIS FISCO Intrinsic S
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Special Certifications Q4 Calibration Certificate Q8 Material Traceability Certification per EN 10204 3.1.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 2051LLT Ordering Inform Model Transmitter Type 2051L Flange-Mounted Liquid Level Transmitter Code 2 3 4 Code A M F Code G0 H0 A0 A2 A4 A6 B0 B2 B4 B6 C0 C2 C4 C6 D0 D2 D4 D6 Code M A B N C D X F G Y H J Q R K T Pressure Ranges (Range/Minimum Span) –250 to 250 inH2O/2.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Code A C D H G N P Code 11 21 22 2A 2B 31 Code Process Fill-High Pressure Side Temperature Limits Syltherm® XLT D.C. Silicone 704 D.C.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 IW(2) India (CCOE) Intrinsic Safety Approval (consult factory for availability) K1(2) ATEX Flameproof, Intrinsic Safety, Type n, Dust K2(2) INMETRO Flameproof, Intrinsic Safety, Type n (consult factory for availability) K4(2) TIIS Flameproof, Intrinsic Safety (consult factory for availability) K5 FM Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 K6 CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 OPTIONS Standard Configuration Unless otherwise specified, transmitter is shipped as follows: Engineering Units 2051C: Engineering Units 2051T: Engineering Units 2051L: 4 mA (1 V dc)(1): 20 mA (5 V dc)(1): Output: Flange type: Flange material: Drain/vent: Integral meter: Alarm(1): Software tag: inH2O (Ranges 1-3), psi (Ranges 4-5) psi (all ranges) inH2O 0 (engineering units above) Upper range limit Linear Specified model code option Specif
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 LCD display M5 Digital Meter • 2-Line, 5-Digit LCD for 4-20 mA HART and FOUNDATION fieldbus • 1-Line, 4-Digit LCD for 1-5 Vdc HART Low Power • Direct reading of digital data for higher accuracy • Displays user-defined flow, level, volume, or pressure units • Displays diagnostic messages for local troubleshooting • 90-degree rotation capability for easy viewing Transient Protection T1 Integral Transient Protection Terminal Block Meets IEEE C6
Reference Manual Rosemount 2051 00809-0200-4101, Rev AA July 2008 Rosemount 2051C Traditional Flange Bracket Options B1 Bracket for 2-in. Pipe Mounting • For use with the traditional flange option • Bracket for mounting on 2-in.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 SPARE PARTS Terminal Block, FOUNDATION fieldbus Part Number Terminal Block Standard terminal block assembly 02051-9005-0021 Transient terminal block assembly (option T1) 02051-9005-0022 FISCO terminal block assembly 02051-9005-0023 Electronics Board Part Number Assembly for FOUNDATION fieldbus 02051-9001-2001 LCD Display, FOUNDATION fieldbus LCD Display Kit(1) Kit for Aluminum Housing Kit for SST Housing LCD Displays Only(2) 03
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Flange Adapter Part Number Nickel-plated carbon steel 02024-0069-0005 316 SST 02024-0069-0002 Cast C-276 02024-0069-0003 Drain/Vent Valve Kits (each kit contains parts for one transmitter) Part Number Differential Drain/Vent Kits 316 SST stem and seat kit 01151-0028-0022 Alloy C-276 stem and seat kit 01151-0028-0023 316 SST ceramic ball drain/vent kit Alloy C-276ceramic ball drain/vent kit Gage Drain/Vent Kits 03031-0378-0022
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Gage Flange and Adapter Bolt Kit (Set of 6) Carbon steel 03031-0307-1001 316 SST 03031-0307-1002 ASTM A 193, Grade B7M 03031-0307-1003 ASTM A 193, Class 2, Grade B8M Manifold/Traditional Flange Bolts 03031-0307-1005 Carbon steel Use bolts supplied with manifold 316 SST Use bolts supplied with manifold LEVEL FLANGE, VERTICAL MOUNT Flange Bolt Kit (Set of 4) Carbon steel 03031-0395-0001 316 SST 03031-0395-0002 Covers Aluminum f
Reference Manual Rosemount 2051 A-28 00809-0200-4101, Rev AA July 2008
Reference Manual 00809-0200-4101, Rev AA July 2008 Appendix B Rosemount 2051 Approval Information Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page B-1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page B-1 Fieldbus Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page B-2 Approval Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 European Directive Information The EC declaration of conformity for all applicable European directives for this product can be found on the Rosemount website at www.rosemount.com. A hard copy may be obtained by contacting an Emerson Process Management representative. ATEX Directive (94/9/EC) All 2051 transmitters comply with the ATEX Directive.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Canadian Standards Association (CSA) E6 Explosion-Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition-Proof for Class II and Class III, Division 1, Groups E, F, and G. Suitable for Class I, Division 2 Groups A, B, C, and D for indoor and outdoor hazardous locations. Enclosure type 4X, factory sealed I6/IF Intrinsically safe approval.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Special Conditions for Safe Use (X): The device is not capable of withstanding the 500V insulation test required by Clause 6.3.12 of EN60079-11. This must be taken into account when installing the apparatus. E1 ATEX Flame-Proof Certification No. KEMA 08ATEX0090X G Ex d IIC T6 (Tamb = –50 to 65 °C) Ex d IIC T5 (Tamb = –50 to 80 °C) IP66 1180 Vmax = 32 V dc II 1/2 G Special Conditions for Safe Use (X): 1.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 IECEx Certifications I7 IECEx Intrinsic Safety Certification No. IECExBAS08.0045X Ex ia IIC T4 (Tamb = –60 to +60 °C) IP66 1180 II 1 G Table B-3. Input Parameters Ui = 30V Ii = 300 mA Pi = 1.3 W Ci = 0 µF Special Conditions for Safe Use (X): The device is not capable of withstanding the 500V insulation test required by Clause 6.3.12 of IEC60079-11. This must be taken into account when installing the apparatus.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Special Conditions for Safe Use (X): 1.Appropriate ex d blanking plugs, cable glands, and wiring needs to be suitable for a temperature of 90 °C. 2.This device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for maintenance shall be followed in detail to assure safety during its expected lifetime.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 China (NEPSI) Certifications (consult factory for availability) E3 Flame-Proof Ex d II B+H2T3~T5 I3 Intrinsic Safety Ex ia IIC T3/T4 IC FISCO Intrinsic Safety Certificate Pending KOSHA Certifications (consult factory for availability) EP Flame-Proof Ex d IIB+H2 T5 IP Intrinsic Safety Ex ia IIC T3 CCoE Certifications (consult factory for availability) IW Intrinsic Safety Ex ia IIC T4 EW Flame-Proof Ex d IIC T5 or T6 Combinations of Cert
Reference Manual Rosemount 2051 APPROVAL DRAWINGS Factory Mutual (FM) B-8 00809-0200-4101, Rev AA July 2008
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 B-9
Reference Manual Rosemount 2051 B-10 00809-0200-4101, Rev AA July 2008
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 B-11
Reference Manual Rosemount 2051 B-12 00809-0200-4101, Rev AA July 2008
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 B-13
Reference Manual Rosemount 2051 B-14 00809-0200-4101, Rev AA July 2008
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 B-15
Reference Manual Rosemount 2051 B-16 00809-0200-4101, Rev AA July 2008
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 B-17
Reference Manual Rosemount 2051 B-18 00809-0200-4101, Rev AA July 2008
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 B-19
Reference Manual Rosemount 2051 B-20 00809-0200-4101, Rev AA July 2008
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Canadian Standards Association (CSA) B-21
Reference Manual Rosemount 2051 B-22 00809-0200-4101, Rev AA July 2008
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 B-23
Reference Manual Rosemount 2051 B-24 00809-0200-4101, Rev AA July 2008
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 B-25
Reference Manual Rosemount 2051 B-26 00809-0200-4101, Rev AA July 2008
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 B-27
Reference Manual Rosemount 2051 B-28 00809-0200-4101, Rev AA July 2008
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 B-29
Reference Manual Rosemount 2051 B-30 00809-0200-4101, Rev AA July 2008
Reference Manual 00809-0200-4101, Rev AA July 2008 Appendix C Rosemount 2051 Block Information TRANSDUCER BLOCK Overview This section contains information on the 2051 Transducer Block (TB). Descriptions of all Transducer Block parameters, errors, and diagnostics are listed. Also, the modes, alarm detection, status handling, application information, and troubleshooting are discussed.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Parameters and Descriptions C-2 Parameter Index Number ALERT_KEY BLOCK_ALM 04 08 BLOCK_ERR 06 CAL_MIN_SPAN 18 CAL_POINT_HI CAL_POINT_LO CAL_UNIT 16 17 19 COLLECTION_DIRECTORY 12 FACT_CAL_RECALL MODE_BLK 33 05 mODULE_TYPE 34 PRIMARY_VALUE 14 Description The identification number of the plant unit. The block alarm is used for all configuration, hardware, connection failure or system problems in the block.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Parameter Index Number PRIMARY_VALUE_RANGE 15 PRIMARY_VALUE_TYPE 13 SECONDARY_VALUE SECONDARY_VALUE_UNIT 29 30 SENSOR_CAL_DATE 25 SENSOR_CAL_LOC 24 SENSOR_CAL_METHOD 23 SENSOR_CAL_TYPE 35 SENSOR_CAL_WHO SENSOR_FILL_FLUID 26 28 SENSOR_ISOLATOR_MTL 27 SENSOR_RANGE 21 SENSOR_SN 22 Description The high and low range limit values, the engineering unit code, and the number of digits to the right of the decimal point to be
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Parameter Index Number SENSOR_TYPE 20 ST_REV STRATEGY TAG_DESC TB_DETAILED_STATUS 01 03 02 31 TRANSDUCER_DIRECTORY 09 TRANSDUCER_TYPE 10 UPDATE_EVT XD_ERROR 07 11 Block/Transducer Errors Description Type of sensor connected with the transducer block. Valid sensor types are the following: 117 = Capacitance 124 = Strain Gauge The revision level of the static data associated with the function block.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Diagnostics In addition to the BLOCK_ERR and XD_ERROR parameters, more detailed information on the measurement status can be obtained via TB_DETAILED_STATUS. The table below lists the potential errors and the possible corrective actions for the given values. The corrective actions are in order of increasing system level compromises.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 In Auto mode, PRIMARY_VALUE reflects the value and status quality of the output channels. Methods Sensor Calibration In order to calibrate the sensor, the following steps are performed by the user calibration method: 1. Set MODE_BLK.TARGET = OOS. 2. Apply desired pressure (low pressure); allow to stabilize. Pressure applied must be between range limits defined in PRIMARY_VALUE_RANGE. 3. Set CAL_POINT_LO to applied pressure. 4.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Parameters and Descriptions The table below lists all of the configurable parameters of the Resource Block, including the descriptions and index numbers for each.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 C-8 Parameter Index Number FLANGE_MTL 69 FLANGE_TYPE 68 FREE_TIME FREE_SPACE GRANT_DENY 25 24 14 HARD_TYPES hardware_rev LIM_NOTIFY MANUFAC_ID 15 52 32 10 MAX_NOTIFY MEMORY_SIZE 31 22 message_date message_text 57 58 MIN_CYCLE_T MODE_BLK 21 05 NV_CYCLE_T 23 O_RING_MTL 69 output_board_sn 53 Description Type of material of the flange. See flange material codes.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Parameter Index Number self_test distributor REM_SEAL_FILL 59 42 73 REM_SEAL_ISO_MAT 70 REM_SEAL_NUM 71 REM_SEAL_TYPE 66 RESTART 16 RS_STATE save_config_blocks 07 62 save_config_now security_IO SHED_RCAS 61 65 26 SHED_ROUT 27 Description Instructs resource block to perform self-test. Tests are device specific. Reserved for use as distributor ID. No Foundation enumerations defined at this time.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Parameter Index Number Simulate_STATE 66 simulate_IO RB_SFTWR_REV_ALL 64 51 RB_SFTWR_REV_BUILD RB_SFTWR_REV_MAJOR RB_SFTWR_REV_MINIOR start_with_defaults 50 48 49 63 STRATEGY ST_REV summary_status TAG_DESC TEST_RW UPDATE_EVT WRITE_ALM WRITE_LOCK 03 01 56 02 08 35 40 34 WRITE_PRI 39 C-10 Description The state of the simulate jumper.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Block Errors The table below lists conditions reported in the BLOCK_ERR parameter. Conditions in bold type are available. Conditions in italics are inactive for the Resource block and are given here only for your reference.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Diagnostics In addition to the BLOCK_ERR parameters, more detailed information on the device status can be obtained via DETAILED_STATUS. Table 5.3 lists potential errors and possible corrective actions for the given values. The first step should always be to reset the transmitter, then if the error persists, try steps in Table 5.3. Start with the first corrective action, and then try the second.
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Symptom Mode will not leave OOS Possible Causes Target mode not set. Memory Failure Block Alarms Will not work Features Notification Corrective Action Set target mode to something other than OOS. BLOCK_ERR will show the memory failure. Check RESTART vallue. Restart the device by setting RESTART to Processor. If the block error does not clear, call the factory. FEATURES_SEL does not have Reports enabled. Enable the Reports bit.
Reference Manual Rosemount 2051 C-14 00809-0200-4101, Rev AA July 2008
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Index A Advanced Features . . . . . . . 3-11 Alarm Configuration procedure . 2-24 Alarm Priority . . . . . . . . . . . . 3-10 ALARM_TYPE . . . . . . . . . . . 3-11 Alarms ALARM_TYPE . . . . . . . 3-11 Priorety . . . . . . . . . . . . 3-10 Process . . . . . . . . . . . . 3-10 Analog Input (AI) Function Block . . . . . . . . . . . . . . 3-5, 5-7 ALARM_TYPE . . . . . . . 3-11 BLOCK_ERR . . . . . . . . . 5-7 Configuration . . . . . . . . .
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 L L_TYPE . . . . . . . . . . . . . . . . 3-5 . . . . . . . . . . . . . . . 3-5, 3-6 LCD meter . . . . . . . . . . . . . 3-11 LCD Transducer block . . . . . . 5-7 Block Error . . . . . . . . . . . 5-8 Self Test . . . . . . . . . . . . . 5-7 Lightning . . . . . . . . . . . . . . . 2-23 LIM_NOTIFY . . . . . . . . . . . . . 3-4 Limited Bad . . . . . . . . . . . . . . . 3-10 Uncertain . . . . . . . . . . . 3-10 Link Active Scheduler . . . . . .
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 T X T1 . . . . . . . . . . . . . . . . . . . . C-1 Tagging . . . . . . . . . . . . . . . . 2-2 Terminal block Installing . . . . . . . . . . . . 5-11 Terminal Side . . . . . . . . . . . 2-10 Torque values . . . . . . . . . . . 2-13 Transducer block methods . . . . . . . . . . . . . C-6 modes . . . . . . . . . . . . . . C-5 parameters BLOCK_ERR . . . . . . C-4 ELECTRONICS_STATUS XD Errors . . . . . . . . . . . .
Reference Manual Rosemount 2051 Index-4 00809-0200-4101, Rev AA July 2008
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 NOTES 1-1
Reference Manual Rosemount 2051 NOTES 1-2 00809-0200-4101, Rev AA July 2008
Reference Manual 00809-0200-4101, Rev AA July 2008 Rosemount 2051 Standard Terms and Conditions of Sale can be found at www.rosemount.com\terms_of_sale The Emerson logo is a trade mark and service mark of Emerson Electric Co. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. Coplanar is a trademark of Rosemount Inc. PlantWeb is a mark of one of the Emerson Process Management companies. HART is a registered trademark of the HART Communications Foundation. Syltherm and D.C.