Section 6. Service and Troubleshooting
Figure 6-4. Simulation mode
active is indicated in the
WinSetup workspace
NOTE
Simulation continues for the specified period of time. It can also be stopped
manually at any time by pressing the Stop button in the Simulation window.
Advanced Simulation
1. If a Calculate Parameter check-box is selected, the simulation parameter
is calculated based on input data from the holding registers Simulation
HREGS 3800 to 4056. You can simulate one or more parameters
simultaneously.
To simulate Product Temperature, the temperature element positions
must be configured. Right-click the auxiliary tank device (ATD) icon in the
WinSetup workspace, choose the Properties option, and select the
Average Temperature Calculation tab. See the Raptor System
Configuration Manual (Document no. 300510EN) for more information.
The resulting Product Temperature is available in input register IR2100
(tank 1). It is also available in input register area starting with IR30000
(IR30044 for tank 1).
The Volume Calculation function must be activated in order to enable
advanced Volume simulation. See “Volume Configuration” on page C-14
for more information.
The volume calculation result is presented in input register IR4702,
IR3400 (tank 1) and in input register area starting with IR30000 (IR30148
for tank 1).
To simulate Observed Density the Hybrid Density function must be
activated. See “Hybrid Density Calculation” on page C-10 for more
information.
The resulting Observed Density is available in input register IR3500
(tank 1). It is also available in input register area starting with IR30000
(IR30116 for tank 1).
2. Click the Start button to start simulating the selected tank parameters.
Simulation mode active