Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC MultiVariable™ Mass Flow Transmitter www.rosemount.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Rosemount 3095FC MultiVariable Mass Flow Transmitter The products described in this document are NOT designed for nuclear-qualified applications. Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings. For information on Rosemount nuclear-qualified products, contact an Emerson Process Management Sales Representative.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Table of Contents SECTION 1 Introduction 3095FC Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2 Firmware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Rosemount 3095FC 00809-0100-4832, Rev AA October 2004 Getting Started with the Software . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12 Run the Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12 Log into the Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12 Establishing Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13 Connection Methods. . . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Soft Points Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-20 Opcode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-21 Opcode Table Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 3-22 Radio Power Control Configuration . . . . . . . . . . . . . . . . . . . . . . . 3-23 Meter Run Configuration . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Rosemount 3095FC 00809-0100-4832, Rev AA October 2004 Changing the Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5 APPENDIX A Specifications and Reference Data Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1 Functional Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1 Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0100-4832, Rev AA October 2004 Section 1 Rosemount 3095FC Introduction 3095FC Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-1 3095FC Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-4 Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-5 3095FC OVERVIEW The 3095FC is a 32-bit microprocessor-based transmitter.
Reference Manual Rosemount 3095FC Hardware 00809-0100-4832, Rev AA October 2004 The backplane board provides the power regulation, the routing of the signals to the termination board, the processor board, the backup battery board, the optional communications board, the sensor module, and the battery charger board. The termination board provides connections to the field wiring and is located on the terminal side of the housing.
Reference Manual 00809-0100-4832, Rev AA October 2004 Firmware Rosemount 3095FC The firmware contained in flash ROM on the termination board, determines the functionality of the 3095FC and includes: • • • • • • • • • Accessories Automatic Tests 1992 AGA-3 flow calculations (with user-selectable AGA8 compressibility Detail, Gross I, or Gross II) for a single meter run Memory logging of 240 alarms and 240 events Archival of minute data from the last 60 minutes for 15 points Archival of 60 days of 10-minu
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Low Power Mode Sleep mode is used to place the CPU in a low power mode. The battery voltage is monitored by low voltage detection circuitry and the low voltage limit value is set at 5.4 volts. During Sleep mode, sub-modules are powered down. The 3095FC enters Sleep mode after one minute of inactivity on the communication ports.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Instantaneous Rate Calculations The instantaneous value of the IV is used with the previous calculation period of the Integral Multiplier Value (IMV) to compute the instantaneous flow rate. The IMV is defined as the value resulting from the calculation of all other factors of the flow rate equation not included in the IV. The instantaneous flow rate is used with the volumetric heating value to compute the instantaneous energy rate.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC NOTE: Do not allow the batteries to fully discharge. If the batteries fully discharge, the battery charger board may enter thermal limiting. Rosemount User Interface Software PC Requirements The Rosemount User Interface Software operates on any PC that meets the following requirements: • IBM compatible • Pentium-Class Processor (233 MHz or greater is recommended) • CD-ROM drive • Windows 95 (service release B), 98, ME, NT 4.
Reference Manual 00809-0100-4832, Rev AA October 2004 Section 2 Rosemount 3095FC Installation Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-2 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-4 Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-9 Apply Power . . . . . . . . .
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC INSTALLATION Rosemount 3095FC Piping from the static and DP meter runs connect to female ¼-18 NPT connections. The 3095FC is an upstream device, meaning that the SP line normally connects to the high pressure side (labeled “H” on the sensor body). Installing the Rosemount 3095FC on a Pipestand The following steps must be taken to install the 3095FC on a 2-in. pipestand: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC 9. Calibrate the 3095FC (see “Calibrate” on page 4-1). 10. Connect the 3095FC unit to any other external communication devices or networks. 11. Place the meter run in service and monitor with Rosemount User Interface Software for proper operation. Solar Panels Solar panels generate electrical power for the 3095FC from solar radiation. They are the optimal choice for locations where a DC voltage source is not available.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC supplies significantly more than 1 Amp to the 3095FC. The maximum input is 28 volts. Do not allow the batteries to fully discharge. If the batteries are fully discharged, the battery charger board may enter thermal limiting. Figure 2-1. Solar Insolation in Hours for the United States WIRING The field terminals are all located on a Termination Board.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Figure 2-2. Wiring Terminals Power Supply Wiring RTD Wiring The terminals are labeled CHG+ for positive power connection and CHG- for negative power connection on a label on the termination board. These connections provide the input voltage and power for the battery charging circuitry. The maximum voltage that can be applied to the CHG+ / CHGterminals is 28 Volts dc. Pin Signal Description 1 2 CHG+ CHG– Battery 8.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Communications Wiring The communication ports located on the 3095FC provide a data link to the Rosemount User Interface Software, other 3095FC units, and host systems. NOTE All communication ports for the 3095FC are located on an optional communications card or built into the termination board. Table 2-2.
Reference Manual 00809-0100-4832, Rev AA October 2004 Table 2-3. Local Operator Interface Port Wiring Rosemount 3095FC Signal Label Common LOI Power(1) Common Ready to Send Receive (RX) Transmit (TX) COM TX + V COM RTS RX TX (1) Do not use the LOI to power external devices. Table 2-4.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Table 2-6. Communications Card Signals Signals RTS RX TX Table 2-7. EIA-232 (RS-232) Communications Card Wiring Action The request to send signals that the modem is ready to transmit. The RXD receive data signals that data is being received at the communications card. The TXD transmit data signals that data is being transmitted from the communications card.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Pipelines Without Cathodic Protection The pipeline may provide an adequate earth ground and the 3095FC could mount directly on the meter run using an orifice plate. Use a ground system tester to make sure the pipeline to earth impedance is less than 2 ohms. If the pipeline to earth impedance is greater than 2 ohms, the 3095FC installation should be electrically isolated and a ground rod or grid grounding system installed.
Reference Manual 00809-0100-4832, Rev AA October 2004 APPLY POWER Rosemount 3095FC To prevent unnecessary battery drainage, the 3095FC is delivered with the reset jumper in the OFF position. To apply power to the 3095FC: 1. Complete the necessary wiring (“Wiring” on page 2-4). 1. Unscrew the front end cap cover (LCD end). 2. Place the power jumper in the ON position. The jumper is located on the LCD (if installed) or at J1 on the Battery Charger Board. 3. Screw the front-end cap cover (LCD end).
Reference Manual 00809-0100-4832, Rev AA October 2004 INSTALL THE ROSEMOUNT USER INTERFACE SOFTWARE Rosemount 3095FC If a previous version of the Rosemount User Interface Software is installed, refer to “Uninstalling the Rosemount User Interface Software” on page 2-12. Software Overview The Rosemount User Interface Software is used to configure the 3095FC. For PC requirements see “I/O wiring requirements are site and application dependent.
Reference Manual 00809-0100-4832, Rev AA October 2004 Install Without Autorun Uninstalling the Rosemount User Interface Software Rosemount 3095FC 1. Insert the Rosemount User Interface Software installation CD-ROM. 2. Click the Windows Start button. 3. Select Run. 4. Click the Browse button 5. Navigate to and select the Select.exe located on the CD-ROM. 6. Click OK in the Navigation Window. 7. Click OK in the Run window. 8. Continue with in “Install With Autorun" steps 2-8, located above.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC ESTABLISHING COMMUNICATION Connection Methods When the user is logged into the Rosemount User Interface Software, the PC must connect to the 3095FC unit so communication can be accomplished. Use one of the following connection methods: • Direct Connect - Connect to the 3095FC using the Local Port (LOI) if the default communication parameters apply.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Connect When off-line, the 3095FC menu displays Connect. To use Connect: 1. Physically connect the 3095FC (see “Installation” on page 2-2). 2. Launch and log into Rosemount User Interface Software (see “Getting Started with the Software” on page 2-12). 3. Perform one of the following: • Select a communications port from the Device Directory and press the key.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC NOTE Double-click the desired communications link (3095FC name) to connect to that 3095FC. Double-clicking an icon is the same as selecting the menu bar or toolbar button Direct Connect or Connect commands. Configuration of the PC Communication Ports to the 3095FC unit cannot be performed within the 3095FC unit configuration screen. Return to the 3095FC Directory (Configuration Tree) screen.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Adding a 3095FC transmitter 1. Right-mouse click on the Device Root directory icon. 2. Select Add a Device 3. Right-mouse click on the New Device and select Rename. Type in the new device name. 4. Press . 5. Configure the 3095FC communication parameters. . NOTE Place a 3095FC connection under a Group by selecting the Group before adding the 3095FC Connection. Deleting a 3095FC transmitter 1.
Reference Manual 00809-0100-4832, Rev AA October 2004 Section 3 Rosemount 3095FC Configuration Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1 Basic Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-4 Custom Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Duplicating a Configuration Duplicate the configuration of a 3095FC using these instruction. 1. File > Save Configuration to save the configuration to a specified file. 2. Establish Communications with the second unit (see page 2-13). 3. File > Download loads the configuration into the unit. 4. After loading the configuration data into the second 3095FC (Step 3), save the configuration to a unique disk file by repeating Step 1.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Download File Use this function to download a previously saved configuration to a 3095FC. Configuration files are created using the Save Configuration function. To download a previously saved configuration: 1. Select File > Download. 2. Select the configuration file name with the extension .FCF 3. Click Open. 4. Select the Point Types to download. Use Select All or Deselect All to change multiple Point Types.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC CONFIGURATION Setting the Clock Immediately after connecting to a 3095FC for the first time, set the Rosemount User Interface Software Clock to ensure proper logging of history. The internal real-time clock provides time-stamping and control of the historical databases, Event Log, Alarm Log, Audit Log, and Contract Hour. NOTE The time stamp reflects the time at the end of the period.
Reference Manual 00809-0100-4832, Rev AA October 2004 Configuring the System Flags Rosemount 3095FC Use System Flags to perform actions that affect the overall operation of the 3095FC. From the Flags screen, a configuration can be saved to Flash memory and the 3095FC can be re-initialized. NOTE Certain Flags cause data to be lost, parameter values to be changed, and configuration memory to be cleared. Confirm Flag function before changing.
Reference Manual Rosemount 3095FC 00809-0100-4832, Rev AA October 2004 The Clear Flash Memory procedure clears all saved restart configuration data contained in Flash memory. Only factory defaults are retained. To return the 3095FC to the original factory default settings: 1. Select Device > Flags > General Tab 2. Select the Clear button and click Yes. 3. Perform a Cold Start using the Cold Start & Clear ALL button. 4. Click Yes, Apply, and OK.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Advanced Tab Use the following instructions to configure the Advanced System Flags tab. See Figure 3-3. 1. Select Device > Flags > Advanced Tab. 2. Enable CRC Check to perform CRC (Cyclical Redundancy Check) check on 3095FC protocol communications. 3. Enable I/O Scanning so the I/O is in normal scan mode. When Disabled, all I/O scanning stops and the last values are used until scanning is resumed. 4.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC 3095FC Communications Ports Configuration The communication ports of the 3095FC provide a link to a PC, such as one running Rosemount User Interface Software or a host PC. The 3095FC can have up to three communication ports. General Tab See Figure 3-4. 1. Select Device > Comm Ports > General Tab 1. Select the Port that the 3095FC is using to communicate.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC RBX Tab To configure the RBX, a modem must be present and appropriately configured. Use the following steps to configure the RBX tab. See Figure 3-5 on page 3-10. 1. Configure the Device > Comm Ports > General Tab (see “General Tab” on page 3-8). 2. Select Device > Comm Ports > RBX Tab. 3. Enable RBX Mode. The RBX (Report-by-Exception) feature allows the 3095FC to call in to a host PC when a configured alarm occurs. 4.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Figure 3-5. Device Comm Port RBX Tab Screen 3095FC Device Configuration / Information This step establishes the Station Name, Address, Group, and other global variables that differentiate a 3095FC. Other system variables set in the information screen must be established for a particular application. General Tab See Figure 3-6 on page 3-11. Use the following instructions to configure the Device Information General tab. 1.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Figure 3-6. 3095FC Differentiation / Information General Screen Points Tab The Points screen allows the user to change the number of certain points that will be active. 1. Select Device > Information > Points Tab Figure 3-7.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Other Information Tab This tab displays information about the firmware (Version Name, Part Number, ID, and Time Created), the boot firmware (Version Name, Part Number, and Time Created), the processor (loading), amount of RAM installed, and the ROM (customer name and serial number). Figure 3-8.
Reference Manual 00809-0100-4832, Rev AA October 2004 Security Configuration Rosemount 3095FC The 3095FC has two types of security. • Rosemount User Interface Security - Enables access to the Rosemount User Interface Software and what menu items the user can access. • 3095FC Security - Enables communication to the transmitter. Rosemount User Interface Security - Menu and Log On See Figure 3-10 on page 3-14.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Figure 3-10. Security Access Level Screen 3095FC Security See Figure 3-11. The 3095FC Security controls access to the device Comm Ports. When enabled, login is required to use the communication ports. Each communication port can be enabled or disabled separately. The Access Level provides security for the 3095FC communication ports depending on the value of the Comm Port Security parameter as defined by the Comm Ports screen.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC LCD User List Configuration LCD User List Setup allows the user to assign up to 16 parameters to be displayed on the LCD. Each parameter is displayed for three seconds before continuing to the next. 1. Select Configure > LCD User List Setup. 2. Use the drop-down list box to select the desired LCD User List Number (List No.) to configure. 3.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Analog Input (AI) Configuration Analog Inputs are analog signals generated by measurement devices, such as pressure and temperature transmitters, including RTD probes.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Figure 3-12. AI General Tab Screen AI Advanced Tab The AI Advanced tab enables the user to configure features, such as filtering, A/D conversions, and clipping for the selected Analog Input. Use the following steps to configure the AI Advanced Tab. See Figure 3-13 on page 3-18. 1. Select Device > I/O > AI Points > Advanced 2.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC 6. 7. 8. 9. Figure 3-13. AI Advanced Tab Screen 3-18 When Temp Compensation is Enabled, a temperature compensation curve is applied to the Analog Input using the board temperature of the 3095FC as a reference. Use this feature to improve the A/D conversion accuracy at temperature extremes for modular Analog Inputs only; built-in Analog Inputs already have temperature compensation.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC AI Alarms Tab See Figure 3-14 on page 3-20. The AI Alarms tab sets the alarm parameters for the AI point. 1. Select Device > I/O > AI Points > Alarms 2. Set the values for the different alarms. There are six different alarms: • Low Alarm: The limit value, in engineering units, to which the I/O must fall to generate a Low Alarm. • High Alarm: The limit value, in engineering units, to which the I/O must rise to generate a High Alarm.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Figure 3-14. AI Alarms Tab Screen Soft Points Configuration Softpoints are data storage areas that can be used by any 3095FC application. Softpoints consist of a Tag identifier, one integer value, and twenty floating values. Softpoints consist of: • tag identifier (10 character string) • 20 floats (floating point values) • 1 integer value (16 bit) • 2 longs (32-bit) • 10 shorts (16-bit) • 10 bytes (8-bit).
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Figure 3-15. Soft Point Screen Opcode Table 3-1. Summary of Opcodes Opcode (operation code) is an instruction from a host system that informs a slave device what actions to take. Table 3-1 contains a summary and brief description of each Opcode. In some cases the number of data bytes returned for an Opcode varies.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Opcode Description 162 165 166 167 180 181 190/195 224 225 255 Sets a single parameter Set or send current configurable historical data Set specified contiguous block of parameters Send specified contiguous block of parameters Send specified parameters Set specified parameters Reserved Send Spontaneous Report-by-Exception (SRBX or RBX) message to host Acknowledge Spontaneous Report-by-Exception message from device Error messages tran
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Figure 3-16. Opcode Table Screen Radio Power Control Configuration Radio Power Control conserves battery power to a radio or any other communicating device. Radio power is controlled either by the DTR signal or by a Discrete Output (DO).
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC 3. 4. 5. 6. Enter the The Radio Power Status, which indicates the current status of the Power Control function of ON, OFF, or RBX. The Active Zone indicates which zone is currently activated for determining the Start Time, On Time, and Off Time. Some of the On Time is also used by the radio during power-up initialization of the receiver, causing part of the On Time to be unavailable for receiving requests.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC NOTE If a Report By Exception (RBX) message needs to be sent to the host PC, the radio power on DO will come on and allow the message to be sent. The hold time should be long enough to allow the 3095FC to receive a response back from the host. 13. Click Apply when configuration is complete. Save the configuration using Device > Flags > Flash Configuration Memory Save. Figure 3-18.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC General Tab The General tab sets the basic parameters for the meter. See Figure 3-19 on page 3-26 1. Select Meter > Setup. 2. Select the Point number to be configured. Enter the meter tag. Enter a unique Meter Description for the meter. 3. Select the Meter Type. Orifice is the default. 4. Select the Calculation Standard and Edition. 5. Select if Alarming is enabled or disabled. 6.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC AGA Meter Inputs Tab See Figure 3-20 on page 3-27. The Inputs tab screen defines the field inputs, including DP and SP to be used in the flow calculation. To setup the meter inputs used in the flow calculation: 1. Select Meter > Setup >Input tab. 2. Click the Differential Pressure TLP button to assign the input that senses the DP (high DP, if Stacked Dp is Enabled). The input units are inH2O (U.S.) or kPa (Metric).
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Gas Quality Tab See Figure 3-21 on page 3-28 Gas Quality defines the mole percentage of twenty gas components, the Heating Value Basis, the Heating Value, and the Specific Gravity. NOTE Entering Hexane+ (C6+) and the mole percent of hexane+ will automatically distribute among hexane, heptane, octane, nonane, and decane as specified by the heavy gas distribution parameters under the Advanced tab (“Advanced Meter Setup Tab” on page 3-29.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Advanced Meter Setup Tab See Figure 3-22 on page 3-30 The Meter Setup advanced tab contains a number of additional parameters that affect the flow calculation. 1. Select Meter > Setup > Advanced tab. 2. Select the FPV Method of calculating the compressibility factor under the 1992 AGA scheme. The three methods are: • Detailed - Requires the natural gas composition in mole percent to be entered.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC NOTE Normal recalculation periods are established in Meter Set-up screen using Integral Multiplier period or the Base Multiplier Period. Upon forcing a recalculation, the accumulations are zeroed and the flow value is logged as a new entry. The Force Recalculation parameter is automatically set to Clear after the recalculation. Figure 3-22. Meter Setup Advanced Tab Screen Instrument Calibration Tab See Figure 3-23 on page 3-30.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Meter Setup Alarms Tab See Figure 3-24 on page 3-32. Meter Setup Alarms allows setting the alarm limits, configure RBX Alarming, and view active alarms for the selected meter run. Alarms can be configured for the individual meter runs and/or the stations, generating meter-specific and /or station-wide alarm conditions.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Figure 3-24. Meter Setup Alarms Tab Screen History Points Configuration The History option allows data stored in the current value database to be copied and stored for up to a month in the historical database. The historical database can be configured to log only the values that need to be logged. The values are logged in the standard (minute-hourly-daily) time base.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC History Point 2, History Point 3, History Point 4, and History Point 6 are all setup as an Average Archive Type that employs one of the following techniques: • Flow dependent time-weighted linear averaging (default) • Flow dependent time-weighted formulaic averaging • Flow-weighted linear averaging • Flow-weighted formulaic averaging Averaging Technique The averaging technique is selected using Rosemount User Interface Software.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC • Alarm Log: The Alarm Log contains the change in the state of any alarm signal that has been enabled for alarms. The system Alarm Log has the capacity to maintain and store up to 240 alarms in a “circular” log. The Alarm Log has information fields that include time and date stamp, alarm clear or set indicator, and either the Tag name or a 14-byte detail string in ASCII format.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC General History The Configure > History option allows data to be stored in the historical database. Hourly and daily values are stored for up to 35 days. The historical database can be configured to log only the values that need to be logged. NOTE History points setup in the Meter > History screen override history points setup in the Configure > History screen.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC • Totalize - The difference between the current value and last hour's current value is used for point values polled or received as accumulated values. The Totalization technique assumes that the value being archived is zeroed out by something else at Contract Hour and that no rollover of the value occurs. Totalization occurs at the Minute Historical Log and is summed up for the Hourly and Daily Historical Logs.
Reference Manual 00809-0100-4832, Rev AA October 2004 History, Alarm, Event, and Audit Log Reports Rosemount 3095FC History, Alarm, Event, and Audit Log can be viewed from the View menu. History can viewed from an on-line Rosemount User Interface Software, 3095FC, or from a disk file. History and log files work in a circular fashion; the newest data overrides the oldest data when the log is full.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Collect Data Select 3095FC > Collect Data to save various 3095FC data to disk files. Select the values to be saved for later generating into a report(s). This screen may only be accessed when the user is on-line with the already configured 3095FC from which data will be gathered. Use Save As and the Browse button to either accept the default File name or enter a new File name.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Selecting View > EFM Reports opens the initial screen. The utility program is used in conjunction with the AGA flow calculation capabilities of the 3095FC to display or print previously collected flow data. EFM Reports generate printed and on-screen reports of the historical flow data for a meter point. Selecting EFM Reports causes the Rosemount User Interface Software to suspend operation and load the EFM Reports Utility.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Modbus Configuration The 3095FC has the ability to communicate using Modbus protocol. This makes it possible to integrate with Modbus devices into the same Host/Slave system. The 3095FC can act as a Slave device. The LOI, Comm 1, and Comm 2 ports all support Modbus communications.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC • Remote Terminal Unit (RTU)– Allows for greater character density and better data throughput than ASCII for the same baud rate. Each message is transmitted in a continuous stream. Data is sent in 8-bit binary characters. In the ASCII mode, each RTU character is divided into two 4-bit parts that are represented by their hexadecimal equivalent. RTU mode uses Cyclic Redundancy Check (CRC) error checking. By default, RTU is enabled.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Figure 3-25. Configure Modbus General Tab Screen Scale Values Tab The Scale Value tab allows the user to enter low and high floating point and integer values for converting between integer and floating point numbers. See Figure 3-26 on page 3-43 1. Select Configure > Modbus > Configuration > Scale Values tab. 2. Enter the Integer Scale values.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC 4. Enter the Float Scale # in the Low Value Float Scale and High Value Float Scale fields used when the Host is not able to process floating point numbers. In Host systems that do not accept floating point numbers, eight sets of floating point ranges for values can be specified. This allows floating point values, such as PID Setpoints, to be read and set by the Host as integer values.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Modbus - History Collection The Modbus protocol sends the Hourly (periodic) and Daily History. Refer to “History Access Registers Tab” on page 3-44. Each record contains a time and date stamp and all of the history archives for which the Register Number is configured. The Modbus Function Code 03 and the History Archive Register are used to collect the archived data.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC NOTE The Starting History Point and Ending History Point values must be different with the Starting History Point value being the smaller of the two. The group of history points is specified by the Modbus register value set in the Register Number field. 8. 9. Enter the Archive Type to archive either Hourly or Daily values.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Table 3-5. History, Event, and Alarm Functionality Function Code Register Field Data Field 3 3 3 7160 – Daily Index 7161 – Hourly Index 32 – Event/Alarm Register Ignored Ignored Ignored 5 32 – Event/Alarm Register Ignored 3 703 – 7160 – Daily History History Archive Register (0 to 34) 3 704 – Hourly Index History Archive Register (0 to 8.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Table 3-6.
Reference Manual Rosemount 3095FC 00809-0100-4832, Rev AA October 2004 Register numbers should be unique for a given communication port. Registers may be duplicated as long as they are assigned to separate port or located in a separate Modbus configuration table. If a register number is duplicated within the same Modbus function table, the first occurrence is used.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Table 3-7.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC For example: When using Point Indexing the configuration of: Starting Register Ending Register Device Parameter(s) Indexing Conversion 100 103 AIN, 4-1, EU Point 0 Specifies four Registers (100, 101, 102, and 104) that are mapped to a group of Analog Input (AIN) values in engineering units (EU) starting at the Analog Input in the forth module location, first position (4-1).
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Figure 3-28. Modbus Registers Configuration Screen Modbus Conversion Conversion codes convert the data into a format that is compatible to a Modbus device. Select the Conversion field, on the Modbus Registers or Modbus History screen, (Configure > Modbus > Modbus Register) to specify the type of conversion required, if any, on the data before it is sent to the host or before it is written to the 3095FC.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Table 3-8.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Convert Code Description Slave Function 49 50 51 52 53 54 55 56 57 to 64 65 Deadband, Float Scale 1 Deadband, Float Scale 2 Deadband, Float Scale 3 Deadband, Float Scale 4 Deadband, Float Scale 5 Deadband, Float Scale 6 Deadband, Float Scale 7 Deadband, Float Scale 8 No Conversion IEEE Floating Point Number 3, 4, 6, 16 3, 4, 6, 16 3, 4, 6, 16 3, 4, 6, 16 3, 4, 6, 16 3, 4, 6, 16 3, 4, 6, 16 3, 4, 6, 16 – 3, 4, 16 66 IEEE Floating
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC CUSTOM DISPLAYS This section describes the Custom Display option. The Custom Display option allows the creation of customized “live” displays, loading a display from a disk file, and monitoring flow and I/O points. Display options are located under the View menu. The 3095FC stores displays to disk.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC 9. Press the Test button to display the screen as it will appear in use. Use the Update, Autoscan, Stop Scan, Edit, Save, and Close buttons at the bottom of the screen to perform the following functions: • Update - Use this button to update all TLP (live data) information with the current reading from the 3095FC. The message “Reading Data” appears in the Status Line.
Reference Manual Rosemount 3095FC 3-56 00809-0100-4832, Rev AA October 2004
Reference Manual 00809-0100-4832, Rev AA October 2004 Section 4 Rosemount 3095FC Calibration Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1 Calibrate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1 Verify Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Figure 4-1. Removing the Device from Service Bleed High Pressure Remains Bleed 2 3 1 Operating Shutdown Sequence 8. Apply the low (zero) value. For a pressure input, this would typically be open to atmosphere. 9. Enter the applied value in the Dead Weight / Tester Value field of the Set Zero dialog. For SP on an absolute-pressure device, enter the actual current atmospheric pressure.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC 22. When the Live Reading is stable, click Set Mid 3 to calibrate the reading. The display returns to the Meter Calibration window. 23. When the calibration for a selected point is complete, another input can be calibrated or complete the calibration. If calibration is complete return the device to service.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC • Press Effect is the Zero Shift adjustment value; it is used as an offset to the calibrated EU Values to compensate for the working SP effect on a DP transmitter that was calibrated at atmospheric pressure. • Set EU Value is the Tester Value specified for the last calibration value that was set. Manual EU is the Live Reading for the last calibration value that was set.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Calibration Report The Calibration Report details which parameters were set during calibration. 1. Select View > Calibration Report. 2. Select the Calibration Report to be viewed. The file has the extension *.800 and is located in the default directory C:/Program Files/Rosemount User Interface for Windows/Data directory unless the directory location was changed when the Calibration Report was created. 3. Click Open.
Reference Manual 00809-0100-4832, Rev AA October 2004 VERIFY CALIBRATION Rosemount 3095FC Rosemount User Interface Software can verify the calibration to check if the device requires re-calibration. To verify, perform the following steps: 1. 2. 3. Launch the Rosemount User Interface Software. Connect the 3095FC. Select the Meter > Calibration. Click Freeze. This opens the Meter Calibration window. The current reading displays under each meter input as the Freeze Value.
Reference Manual 00809-0100-4832, Rev AA October 2004 Section 5 Rosemount 3095FC Troubleshooting and Maintenance Backup Configuration Information . . . . . . . . . . . . . . . . . . page 5-1 Communication Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-2 Resetting the 3095FC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-3 After Installing Components . . . . . . . . . . . . . . . . . . . . . . . page 5-4 Replacing the Batteries . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC COMMUNICATION ERRORS Several events can cause a connection failure: • If the Direct Connect communication link fails, use the Connect feature to establish a connection to the 3095FC. The Configuration Tree option allows the user to change the communications port, time-out settings, and other variables used when establishing a communications link to the PC.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC RESETTING THE 3095FC If problems occur that appear to be software related, try resetting with a Warm Start, Cold Start, or Jumper Reset. Warm Start The re-initialization is performed by setting a parameter in the Rosemount User Interface Software Flags. The re-initialization includes the Tasks, Database, Communication Ports, sensor module, and I/O. It does not change the current configuration of any parameters.
Reference Manual 00809-0100-4832, Rev AA October 2004 AFTER INSTALLING COMPONENTS Rosemount 3095FC After removing power to the 3095FC and installing components as needed, perform the following steps to start the 3095FC and reconfigure the data. NOTE Ensure all input devices, output devices, and processes remain in a safe state upon restoring power. An unsafe state could result in property damage. When installing equipment in a hazardous area, ensure that all components are approved for use in such areas.
Reference Manual 00809-0100-4832, Rev AA October 2004 REPLACING THE BATTERIES Rosemount 3095FC The battery pack contains three D-size lead-acid batteries providing 2.5 Amp-hours of current at 6.2 volts nominal. NOTE When installing equipment in a hazardous area, ensure that all components are approved for use in such areas. Check the product labels. Change components only in an area known to be non-hazardous.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC 5-6
Reference Manual 00809-0100-4832, Rev AA October 2004 Appendix A Rosemount 3095FC Specifications and Reference Data Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-1 Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-7 Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-9 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-11 Accessories . . . . . . . .
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Power • Transmitter: operates on terminal voltage of 8 - 28 Vdc • Input current: 5mA nominal, 9.5 mA at 100% duty cycle (battery charging not included) • Internal battery: rechargeable, Nominal 6.2 Vdc (2.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Turn-on Time Process variables will be within specifications less than 4 seconds after power is applied to transmitter. Real Time Clock • Year /month / day / hour / minute / second • Battery Packed Serial Card – EIA-232D Card Standards • Meets EIA-232 standard for single-ended data transmission over distances of up to 50 ft (15 m).
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Range 4 (absolute)/ Range D (gage) • 0–36.26 to 0–3,626 psi (0–2,5 to 0–250,0 bar) (100:1 rangeability is allowed) Accuracy (including Linearity, Hysteresis, Repeatability) • ±0.075% of span for spans from 1:1 to 6:1 of URL • For spans less than 6:1 rangedown, URL Accuracy = 0.03 + 0.0075 -------------- % of span Span Ambient Temperature Effect per 50 °F (28 °C) • ±(0.05% URL + 0.125% of span) spans from 1:1 to 30:1 ±(0.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Process Wetted Parts Isolating Diaphragms • 316L SST or Hastelloy C-276® Drain/Vent Valves • 316 SST or Hastelloy C® Flanges • Plated carbon steel, 316 SST, or Hastelloy C Wetted O-rings • Glass-Filled TFE Non-Wetted Parts Electronics Housing • Low copper aluminum Bolts • Plated carbon steel per ASTM A449, Grade 5; or austenitic 316 SST Fill Fluid • Silicone oil • Inert oil (available for gage pressure ranges only) Paint • Polyurethane
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Memory Specifications Programmable Memory 2 MB x 8 flash EPROM Data Memory 512 kB 5 RAM Boot Memory 128 kB flash EPROM Data Logging Archival • 60 days of 10 minutes data • 35 days of hourly data • 35 days of daily data • minimum/maximum values for a single data Memory Logging • 240 alarms before rollover • 240 events before rollover Flow Specifications A-6 Flow Calculation: • Computed in accordance with ANSI/API 2530-92 (AGA 3, 1992
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC DIMENSIONAL DRAWINGS 3095FC Side View Front View 7.50 (191) Meter Cover Optional 10.71 (272) 1.2 (30.5) Clearance Required to remove cover 3 /4-in.–14 NPT Conduit Plug Terminal Block 6.4 (163) Dimensions are in inches (millimeters) 3095FC with Solar Panel Assembly Side View Front View 6.24 (159) Solar Panel Assembly (optional) 17 (732) 4.48 (114) 10.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Mounting Configurations for 3095FC Transmitter Panel Mount Pipe Mount 7.50 (191) 2.0 (51) 3 /4–14 NPT Conduit Plug 10.25 (260) 6.40 (163) 1.10 (28) 2.81 (71) 5.26 (134) 6.40 (163) Dimensions are in inches (millimeters) A-8 3.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC ORDERING INFORMATION • Available — Not available 3095FB 3095FC Code Product Description 3095F MultiVariable Transmitter Code Output B Process Variable Measurement: Modbus RS-485 Process Variable Measurement: Mass Flow and Data Logging: Modbus RS-485 C Code Differential Pressure Range 2 0 – 2.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC • Available — Not available 3095FB 3095FC Code Terminal Block A C Standard With Integral Transient Protection CE MARK / Compliant with EMC – Transient Protection Included Code Meter 0 None LCD Meter B 1 Code Bracket 0 9 None Coplanar SST Flange Bracket for 2-in. Pipe or Panel Mount, SST Bolts Traditional Flange Bracket for 2-in.
Reference Manual 00809-0100-4832, Rev AA October 2004 OPTIONS Standard Configuration Rosemount 3095FC Unless otherwise specified, the transmitter is shipped as follows: Engineering units: Differential Absolute/gage Output: Flange type: Flange material: O-ring material: Drain/vent: Flow Configuration Parameters: Software tag: Custom Configuration (Option Code C1) inH2O psi (all ranges) Modbus RTU protocol signal Specified model code option Specified model code option Specified model code option Specified
Reference Manual Rosemount 3095FC A-12 00809-0100-4832, Rev AA October 2004
Reference Manual 00809-0100-4832, Rev AA October 2004 Appendix B Rosemount 3095FC Product Certifications Approved Manufacturing Locations . . . . . . . . . . . . . . . . . page B-1 European Directive Information . . . . . . . . . . . . . . . . . . . . page B-1 Hazardous Locations Certifications . . . . . . . . . . . . . . . . . page B-1 APPROVED MANUFACTURING LOCATIONS Rosemount Inc.
Reference Manual Rosemount 3095FC B-2 00809-0100-4832, Rev AA October 2004
Reference Manual 00809-0100-4832, Rev AA March 2004 Appendix C Rosemount 3095FC Rosemount User Interface Software Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page C-1 Point Type Parameter Definitions . . . . . . . . . . . . . . . . . . . page C-1 OVERVIEW To configure the 3095FC, you must be familiar with the structure of the database.
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Point Type 0 Information Table 3 5 lists the parameters for the Configurable Opcode Point Type found in the 3095FC. The parameters for this Point Type consist of a sequence number and 44 device parameter identifications (Point Type, Logical Number, and Parameter Number - TLP).
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Parameter Number Read-Write Data Type Length 39 40 41 42 43 44 R/W R/W R/W R/W R/W R/W TLP TLP TLP TLP TLP TLP 3 3 3 3 3 3 Device Point Types Description Data 39 Data 40 Data 41 Data 42 Data 43 Data 44 The tables in the rest of this section list the parameters for each of the Point Types. Table C-3.
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Parameter Number ReadWrite Data Type Length 16 R/O BIN 1 17 18 19 R/O R/O R/W INT 16 UINT 16 FLP 2 2 4 Description Alarm Code: Bit 7 – Manual Mode Bit 6 – Point Fail Bit 5 – Not Used Bit 4 – Rate Alarm Bit 3 – High High Alarm Bit 2 – High Alarm Bit 1 – Low Low Alarm Bit 0 – Low Alarm Raw A/D Input Actual Scan Time Fault EU Value Abbr. ALARM CURRAW SCAN FAULTVAL Table C-4.
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Parameter Number ReadWrite Data Type Length 4 R/W BIN 1 5 6 7 8 9 10 11 12 13 14 R/W R/W R/W R/O R/W R/W R/W R/W R/W R/O FLP FLP FLP UINT 16 FLP FLP FLP UINT 8 AC BIN 4 4 4 2 4 4 4 1 30 1 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 Description AGA
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Parameter Number ReadWrite Data Type Length 32 33 34 35 36 37 38 39 40 41 42 43 R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP UINT 8 4 4 4 4 4 4 4 4 4 4 4 1 44 45 46 47 48 49 50 51 52 53 R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W UINT 8 TLP TLP TLP TLP FLP FLP FLP FLP FLP 1 3 3 3 3 4 4 4 4 4 Description C4H10 – i-Butane C5H12 – n-Pentane C5H12 – i-Pentane C6H14 – n-Hexane C7H16 – n-He
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Parameter Number ReadWrite Data Type Length 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 R/O R/O R/O R/O R/O R/O R/O R/O R/O R/O R/O R/W R/W R/W R/O R/W R/W R/W R/O R/W R/W R/W R/O R/W R/W R/W R/O R/W R/W R/W R/O R/W R/W R/W R/O R/W R/W R/W UINT 8 UINT 8 TLP TLP UINT 8 UINT 8 TLP TLP UINT 8 UINT 8 TLP TLP UINT 8 UINT 8 TLP TLP UINT 8 UINT 8 TLP TLP UINT 8 UINT 8 T
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Parameter Number ReadWrite Data Type Length 7 8 9 10 R/O R/O R/O R/O FLP FLP FLP FLP 4 4 4 4 11 12 13 14 15 16 17 18 19 20 R/O R/O R/O R/O R/O R/O R/O R/O R/O R/O FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP 4 4 4 4 4 4 4 4 4 4 Description Flow Yesterday – MCF or km3 Energy Yesterday – MMBTU or GJ Pressure Extension – hwPf IMV (Integral Multiplier Value) – called C prime (C') in AGA3 1985 Sample Time Orifice: Expansion Factor (Y) F
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Parameter Number ReadWrite Data Type Length 10 11 12 13 14 15 R/W R/W R/W R/W R/W R/W UINT 8 UINT 8 UINT 8 UINT 8 UINT 8 UINT 8 1 1 1 1 1 1 16 17 18 19 20 R/W R/W R/W R/W R/W UINT 8 UINT 8 UINT 8 UINT 8 UINT 8 1 1 1 1 1 21 22 23 24 R/W R/W R/W R/W UINT 8 UINT 8 UINT 8 UINT 8 1 1 1 1 25 R/W UINT 8 1 26 R/W UINT 8 1 27 28 29 R/W R/W R/W UINT 8 UINT 8 UINT 8 1 1 1 Description RTS Communications Port 2 Clear Confi
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Table C-9.
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Parameter Number ReadWrite Data Type Length 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W FLP FLP FLP UINT 8 FLP UINT 8 FLP UINT 8 UINT 8 UINT 8 UINT 8 UINT 8 UINT 8 UINT 8 UINT 8 UINT 8 4 4 4 1 4 1 4 1 1 1 1 1 1 1 1 1 Description Disconnect Time Inactivity Time RBX Time Base #1 RBX Retry Count #1 RBX Time Base #2 RBX Retry Count #2 RBX Time Base #3 RBX Retry Count
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Parameter Number ReadWrite Data Type Length 21 R/O BIN 1 22 23 R/O R/O FLP BIN 4 1 24 R/O UINT 16 2 25 R/W UINT 8 1 Description Abbr.
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Table C-12. Point Type 19 – Database Parameters NOTE Point Type 19 is used by Opcode 165 to configure history points and create events. Parameter Number ReadWrite Data Type Length 0 1 2 3 4 5 R/O R/O R/O R/O R/O R/O FLP UINT 8 UINT 8 UINT 8 UINT 8 FLP 4 1 1 1 1 4 Description Pointer to Tag Archive Type Point Type Point / Logical Number Parameter Number Yesterday’s Total Abbr.
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Parameter Number ReadWrite Data Type Length 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W UINT 8 UINT 8 TLP FLP UINT 8 UINT 8 TLP FLP UINT 8 UINT 8 TLP FLP UINT 8 UINT 8 TLP FLP UINT 8 UINT 8 TLP FLP UI
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Table C-14.
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Parameter Number ReadWrite Data Type Length 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W TLP TLP TLP TLP TLP TLP TLP TLP TLP TLP TLP TLP TLP TLP TLP TLP 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Description Data 1 Data 2 Data 3 Data 4 Data 5 Data 6 Data 7 Data 8 Data 9 Data 10 Data 11 Data 12 Data 13 Data 14 Data 15 Data 16 Table C-16.
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Table C-17. Point Type 45 – Meter Calibration and Sampler Parameter Number ReadWrite Data Type Length 0 R/W BIN 1 1 2 3 4 5 6 7 8 9 R/W R/W R/W R/W R/W R/W R/W R/W R/W FLP FLP FLP FLP FLP FLP UINT 8 FLP FLP 4 4 4 4 4 4 1 4 4 Description Calibration Options: Bit 5 through 7 – Not Used Bit 4 – Orifice Thermal Expansion Factor – 1985 Requires Parameters 11 and 12 of Point Type 46 be set.
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Parameter Number ReadWrite Data Type Length 0 1 2 R/W R/W R/W AC AC BIN 10 30 1 3 R/W BIN 1 C-18 Description Point Tag Identification Point Description Calculation Method: Bit 7 – Manual Mode 0 = Normal 1 = Manual Calculation Standard 0 = AGA 1 = ISO Bit 6 – RBX on Set 0 = Disable RBX on Set 1 = Enable RBX on Set Bit 5 – RBX on Clear 0 = Disable RBX on Clear 1 = Enable RBX on Clear Bit 4 – Alarming 0 = Disabled 1 = Enabled Bi
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Parameter Number ReadWrite Data Type Length 4 R/W BIN 1 5 6 7 8 9 R/W R/W R/W R/W R/W UINT 8 FLP FLP FLP UINT 8 1 4 4 4 1 10 11 12 R/W R/W R/W FLP FLP UINT 8 4 4 1 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 Descriptio
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Parameter Number ReadWrite Data Type Length 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/O FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP FLP UINT 8 TLP TLP TLP TLP FLP FLP FLP BIN 4 4 4 4 4 4 4 4 4 4 4 4 4 4 1 3 3 3 3 4 4 4 1 55 56 57 58 R/W R/W R/W R/W FLP FLP UINT 8 UINT 8 4 4 1 1 C-20 Description C4H10 i-
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Table C-19.
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Parameter Number ReadWrite Data Type Length 50 51 52 53 54 55 56 R/O R/O R/O R/O R/O R/O R/O FLP FLP FLP FLP FLP FLP UINT 8 4 4 4 4 4 4 1 Description Energy Accumulated (MMBTU or GJoules) Uncorrected Today (MCF or km3) Uncorrected Yesterday (MCF or km3) Uncorrected Month (MCF or km3) Uncorrected Previous Month (MCF or km3) Uncorrected Accumulated (MCF or km3) Partial Recalculation Flag Abbr.
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Table C-21.
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Parameter Number ReadWrite Data Type Length 51 52 53 54 55 56 57 58 59 60 R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W TLP UINT 8 UINT 16 UINT 16 TLP UINT 8 UINT 16 UINT 16 TLP UINT 8 3 1 2 2 3 1 2 2 3 1 Description Parameter(s) Conversion Code Start Register #14 End Register #14 Parameter(s) Conversion Code Start Register #15 End Register #15 Parameter(s) Conversion Code Abbr.
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Parameter Number ReadWrite Data Type Length 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W UINT 8 UINT 8 UINT 8 UINT 16 UINT 8 UINT 8 UINT 8 UINT 8 UINT 16 UINT 8 UINT 8 UINT 8 UINT 8 UINT 16 UINT 8 UINT 8 UINT 8 UINT 8 1 1 1 2 1 1 1 1 2 1 1 1 1 2 1 1 1 1 Description End History Point Type of History Archive Conversion Code History Archive Register #8
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Table C-24. Point Type 58 – Revision Information Parameter Number ReadWrite Data Type Length 0 1 2 3 R/O R/O R/O R/O AC AC AC UINT 8 20 10 10 1 Description Device Firmware Description Part Number Version Information Present Flag Abbr. DESC PART# VERSION PRESENT Table C-25.
Reference Manual 00809-0100-4832, Rev AA March 2004 Rosemount 3095FC Parameter Number ReadWrite Data Type Length 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W UINT 8 TLP TLP UINT 8 UINT 8 TLP TLP UINT 8 UINT 8 TLP TLP UINT 8 UINT 8 TLP TLP UINT 8 UINT 8 TLP TLP UINT 8 UINT 8 1 3 3 1 1 3 3 1 1 3 3 1 1 3 3 1 1 3 3 1 1 Description Averaging or Rate Type Point Tag Identification TLP History Log Point #
Reference Manual Rosemount 3095FC C-28 00809-0100-4832, Rev AA March 2004
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Glossary A A/D - Analog to Digital AGA - American Gas Association. AI - Analog Input. AO - Analog Output. Analog - Analog data is represented by a continuous variable, such as an electrical current signal. AP - Absolute Pressure. ASCII - American (National) Standard Code for Information Interchange. Attribute - A parameter that provides information about an aspect of a database point.
Rosemount 3095FC Reference Manual 00809-0100-4832, Rev AA October 2004 Discrete - Input or output that is non-continuous, typically representing two levels such as on/off. DP - Differential Pressure. DSR - Data Set Ready modem communications signal. DTR - Data Terminal Ready modem communications signal. Duty Cycle - Proportion of time during a cycle that a device is activated. A short duty cycle conserves power for I/O channels, radios, and such. DVM - Digital voltmeter.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC I, J IC - Industry Canada, more recently know an Measurement Canada, which grants custody transfer approvals on certain 3095FC units. IC can also mean integrated circuit. ID - Identification IEC - Industrial Electrical Code. IEEE - Institute of Electrical and Electronic Engineers.
Rosemount 3095FC Reference Manual 00809-0100-4832, Rev AA October 2004 On-line - Accomplished while connected (by a communications link) to the target device. For example, on-line configuration is configuring a Rosemount User Interface Software while connected to it, so that current parameter values are viewed and new values can be loaded immediately. OP - Operator Port; see LOI.
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC ROM - Read-only memory. Typically used to store firmware. RTC - Real-time clock. RTD - Resistance Temperature Detector. RTS - Ready to Send modem communications signal. RTU - Remote Terminal Unit. RXD - Received Data communications signal. S Script - An uncompiled text file (such as keystrokes for a macro) that is interpreted by a program to perform certain functions.
Rosemount 3095FC Glossary-6 Reference Manual 00809-0100-4832, Rev AA October 2004
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC Index A Accessories . . . . . . . . . . . 1-3, A-11 After Installing Components . . . . 5-4 Apply Power . . . . . . . . . . . . . 2-10 Approved Manufacturing Locations . B-1 Automatic Tests . . . . . . . . . . . . 1-3 B Backup Configuration Information Basic Functions . . . . . . . . . . . . Display TLP . . . . . . . . . . . Download File . . . . . . . . . . Duplicating a Configuration . New Configuration File . . . . Open File . .
Reference Manual 00809-0100-4832, Rev AA October 2004 Rosemount 3095FC W G P Glossary . . . . . . . . . . . Glossary-1 Grounding . . . . . . . . . . . . . . . . 2-8 Earth . . . . . . . . . . . . . . . . 2-8 Pipelines With Cathodic Protection Power Considerations Power Supply . . . . . . Applying . . . . . . . Batteries . . . . . . . . . . . . . . . . . . . . 2-8 Pipelines Without Cathodic Protection . . . . . . 2-9 H Hardware . . . . . . . . . . . . . . . . 1-2 Hazardous Locations Certifications .
Reference Manual 00809-0100-4832, Rev AA October 2004 This product powers PlantWeb through diagnostics including device temperature limit and low battery voltage. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. PlantWeb is a registered trademark of one of the Emerson Process Management group of companies. All other marks are the property of their respective owners. Emerson Process Management Rosemount Inc. 8200 Market Boulevard Chanhassen, MN 55317 USA T (U.S.